13
OCH671
7
WIRING SPECIFICATIONS
1
2
S1
S2
S3
S1
S2
S3
Indoor/outdoor
unit connection
cable
Indoor
unit
Unit
power
supply
Outdoor
unit
Remote
controller
L
B
N
B
Earth leakage breaker
C
wiring circuit breaker or
isolating switch
C
1:1 system
Electrical wiring
Notes: 1. Wiring size must comply with the applicable local and national code..
2. Power supply cables and Indoor/Outdoor unit connecting cables shall not be lighter than polychloroprene sheathed flexible cable.
3. Install an earth line longer than power cables.
Warning:
In case of A-control wiring, there is high voltage potential on the S3 terminal caused by electrical circuit design that has no electrical insulation between
power line and communication signal line. Therefore, please turn off the main power supply when servicing. And do not touch the S1, S2, S3 terminals
when the power is energized. If isolator should be used between indoor unit and outdoor unit, please use 3-pole type.
(Design 60245 IEC 57)
S1
S2
S3
S1
S2
S3
A-Control
Outdoor Unit
3 poles isolator
Power supply
Isolator
A-Control
Indoor Unit
Never splice the power cable or the indoor-outdoor connection cable, otherwise it may result in a smoke, a fire or communication failure.
7-1. FIELD ELECTRICAL WIRING (power wiring specifications)
Outdoor unit model
PUHZ-SP125VKA
PUHZ-SP140VKA
PUHZ-SP100/125/140YKA
Outdoor unit power supply
~/N (single), 50 Hz, 230 V
~/N (single), 50 Hz, 230 V
3N~ (3 ph 4-wires), 50 Hz, 400 V
Outdoor unit input capacity Main switch (Breaker)
*1
32 A
40 A
16 A
Wiring Wire
No. × size
(mm
2
)
Outdoor unit power supply
3 × Min. 4
3 × Min. 6
5 × Min. 1.5
Indoor unit-Outdoor unit
*2
3 × 1.5 (Polar)
3 × 1.5 (Polar)
3 × 1.5 (Polar)
Indoor unit-Outdoor unit earth
*2
1 × Min. 1.5
1 × Min. 1.5
1 × Min. 1.5
Remote controller-Indoor unit
*3
2 × 0.3 (Non-polar)
2 × 0.3 (Non-polar)
2 × 0.3 (Non-polar)
Circuit rating
Outdoor unit L-N (single)
Outdoor unit L1-N, L2-N, L3-N (3 phase)
*4
230 V AC
230 V AC
230 V AC
Indoor unit-Outdoor unit S1-S2
*4
230 V AC
230 V AC
230 V AC
Indoor unit-Outdoor unit S2-S3
*4
24 V DC
24 V DC
24 V DC
Remote controller-Indoor unit
*4
12 V DC
12 V DC
12 V DC
*1. A breaker with at least 3.0 mm contact separation in each pole shall be provided. Use earth leakage breaker (NV).
Make sure that the current leakage breaker is one compatible with higher harmonics.
Always use a current leakage breaker that is compatible with higher harmonics as this unit is equipped with an inverter.
The use of an inadequate breaker can cause the incorrect operation of inverter.
*2. Max. 45 m
If 2.5 mm² used, Max. 50 m
If 2.5 mm² used and S3 separated, Max. 80 m
• Use one cable for S1 and S2 and another for S3 as shown in the picture.
• Max. 50 m Total Max. for PEY. Wiring size 3 × 1.5 (Polar).
*3. The 10 m wire is attached in the remote controller accessory.
*4. The figures are NOT always against the ground.
S3 terminal has DC 24 V against S2 terminal. However between S3 and S1, these terminals are NOT electrically insulated by the transformer or other device.
Caution: Be sure to install N-Line. Without N-Line, it could cause damage to the unit.