Manual defrost should be done as follows.
1
Change the DIP SW1-1 on the outdoor controller board from OFF to ON.
2
Manual defrost will start by the above operation
1
if all these conditions written below are satisfied.
• Heat mode setting
• 10 minutes have passed since compressor started operating or previous manual defrost finished.
• Pipe temperature is less than or equal to 8
:
.
Manual defrost will finish if certain conditions are satisfied.
Manual defrost can be done if above conditions are satisfied when DIP SW1-1 is changed from OFF to ON.
After DIP SW1-1 is changed from OFF to ON, there is no problem if DIP SW1-1 is left ON or changed to OFF again. This
depends on the service conditions.
Switch
Type
of
switch
DIP
switch
Push
switch
SW1
1
2
No.
Function
Effective timing
Action by the switch operation
Manual defrost *
1
Start
Normal
When compressor is working
in heating operation.*
1
Abnormal history clear
Refrigerant address
setting
When power supply ON
Clear
Normal
off or operating
SWP
6
5
4
3
Under suspension
Pump down
Start
Normal
SW4
SW8
1
2
1
2
3
No function
No function
Use of existing pipe
Used
Not used
No function
—
—
—
—
—
—
—
—
Separate indoor/outdoor
unit power supplies
Used
Not used
Always
—
When power supply ON
ON
OFF
1 2 3
0
1
2
3
4 5 6
ON
1 2 3 4 5 6
ON
1 2 3 4 5 6
ON
1 2 3 4 5 6
ON
1 2 3
4
5
4 5 6
ON
1 2 3 4 5 6
ON
Continue to the next page
9-7. FUNCTION OF SWITCHES, CONNECTORS AND JUMPERS
(1) Function of switches
PUHZ-SHW80VAA.UK PUHZ-SHW112VAA.UK
PUHZ-SHW80VAA-BS.UK
PUHZ-SHW112VAA-BS.UK
PUHZ-SHW80YAA.UK PUHZ-SHW112YAA.UK
PUHZ-SHW80YAA-BS.UK
PUHZ-SHW112YAA-BS.UK
PUHZ-SW75VAA.UK PUHZ-SW100VAA.UK
PUHZ-SW75VAA-BS.UK
PUHZ-SW100VAA-BS.UK
PUHZ-SW75YAA.UK PUHZ-SW100YAA.UK
PUHZ-SW75YAA-BS.UK
PUHZ-SW100YAA-BS.UK
OCH651