70
13
FUNCTION SETTING
Meaning of "Function setting"
mode02:indoor temperature detecting
No indoor temperature(ta)=
No1. Average data of the
sensor on all the
indoor units
factory
setting
ta=(A+B)/2
ta=(A+B)/2
ta=A
ta=A
No2. the data of the sensor
on the indoor unit that
connected
with remote controller
ta=A
ta=B
ta=A
ta=A
No3 the data of the sensor
on main remote
controller.
ta=C
ta=C
ta=C
ta=C
OUTDOOR
INDOOR
REMOTE
(MAIN)
REMOTE
(SUB)
INDOOR
OUTDOOR
INDOOR
REMOTE
(MAIN)
REMOTE
(SUB)
OUTDOOR
INDOOR
REMOTE
(MAIN)
OUTDOOR
INDOOR
REMOTE
(MAIN)
REMOTE
(SUB)
INDOOR
*2. Can be set only when the outdoor unit is an inverter type.
Function
Settings
Mode No. Setting No.
: Initial setting
(when sent from the factory)
Remarks
Power failure
automatic recovery
Indoor temperature
detecting
W
1
LOSSNAY
connectivity
Power supply
voltage
Auto operating mode
Frost prevention
temperature
Humidifier control
Change of
defrosting control
OFF
ON
Average data from each indoor unit
Data from the indoor unit with remote controller
Data from main remote controller
Not supported
Supported (Indoor unit does not intake outdoor air through LOSSNAY)
Supported (Indoor unit intakes outdoor air through LOSSNAY)
240V
220V,230V
Auto energy-saving operation ON
Auto energy-saving operation OFF
2
:
(Normal)
3
:
When the compressor operates, the humidifier also operates.
When the fan operates, the humidifier also operates.
Standard
For high humidity
1
2
1
2
3
1
2
3
1
2
1
2
1
2
1
2
1
2
01
02
03
04
05
15
16
17
The setting is
applied to all
the units in the
same
refrigerant
system.
w
2
13-1. UNIT FUNCTION SETTING BY THE REMOTE CONTROLLER
Each function can be set according to necessity using the remote controller. The setting of function for each unit can only be
done by the remote controller. Select function available from the table 1.
(1) Functions available when setting the unit number to 00 (Select 00 referring to
4
setting the indoor unit number.)
W
1 The functions below are available only when the wired remote controller is used. The functions are not available for
floor standing models.
w
2 PUHZ-RP·YHA/YHA
1
: Initial Setting No.1
PUHZ-RP·YHA
2
: Initial Setting No.2
<Table 1> Function selections
OC338C-3.qxp 07.5.24 0:53 PM Page 70