66
1
ON
2 3 4 5 6
°C
Discharge superheat. SHd
0~255
Cooling = TH4-TH6
Heating = TH4-TH5
0~255
(When the temperature is 100°C or more, hundreds
digit, tens digit and ones digit are displayed by
turns.)
°C
Sub cool. SC
0~130
Cooling = TH6-TH3
Heating = TH5-TH4
0~130
(When the temperature is 100°C or more, hundreds
digit, tens digit and ones digit are displayed by turns.)
0.1 A
Input current of outdoor unit
0~500
(When it is 100 or more, hundreds digit, tens digit
and ones digit are displayed by turns.)
Hz
Targeted operation frequency
0~255
0~255
(When it is 100Hz or more, hundreds digit, tens
digit and ones digit are displayed by turns.)
DC bus voltage
180~370
180~370
(When it is 100V or more, hundreds digit, tens
digit and ones digit are displayed by turns.)
V
1
ON
2 3 4 5 6
1
ON
2 3 4 5 6
1
ON
2 3 4 5 6
1
ON
2 3 4 5 6
SW2 setting
1
ON
2 3 4 5 6
Display detail
Explanation for display
Unit
:
1
ON
2 3 4 5 6
1
ON
2 3 4 5 6
1
ON
2 3 4 5 6
Indoor setting temperature
17~30
Outdoor pipe temperature / Cond./
Eva. (TH6)
-39~88
Outdoor heatsink temperature (TH8)
-40~200
17~30
:
:
:
-39~88
(When the temperature is 0
:
or less, “–” and
temperature are displayed by turns.)
-40~200
(When the temperature is 0
:
or less, “–” and
temperature are displayed by turns.)
(When the thermistor detects 100
:
or more,
hundreds digit, tens digit and ones digit are
displayed by turns.)
Outdoor outside temperature (TH7)
-39~88
-39~88
(When the temperature is 0
:
or less, “–” and
temperature are displayed by turns.)
OCH415A-3.qxp 08.2.21 8:14 AM Page 66