28
11-4. SELF-DIAGNOSIS ACTION TABLE
<Abnormalities detected when the power is turned on> (Note 1) Refer to indoor unit section for code P and code E.
Error Code
Abnormal points and detection method
Case
Judgment and action
None
—
1
No voltage is supplied to terminal
block(TB1) of outdoor unit.
a) Power supply breaker is
turned off.
b) Contact failure or discon-
nection of power supply
terminal
c) Open phase (L or N phase)
2
Electric power is not supplied
to power supply terminal of
outdoor power circuit board.
a) Contact failure of power
supply terminal
b) Open phase on the outdoor
power circuit board
:Disconnection of connector
TABT or TABS
3
Electric power is not supplied to
outdoor controller circuit board.
a) Disconnection of connector
(CNDC)
4
Disconnection of reactor (DCL)
5
Disconnection of outdoor noise
filter circuit board or parts failure
in outdoor noise filter circuit
board
It is especially needed to check
the resistance RS1 on the noise
filter cuircuit board.
6
Defective outdoor power circuit
board
7
Defective outdoor controller
circuit board
1
Check following items.
a) Power supply breaker
b) Connection of power supply terminal block
(TB1)
c) Connection of power supply terminal block
(TB1)
2
Check following items.
a) Connection of power supply terminal block
(TB1)
b) Connection of terminal on outdoor power
circuit board
Disconnection of connector TABT or TABS
Refer to 11-9.
3
Check connection of the connector (CNDC)
on the outdoor controller circuit board.
Check connection of the connector (CNDC)
on the outdoor power circuit board
Refer to 11-9.
4
Check connection of reactor. (DCL)
Check connection of “L1” and “L2” on the
active filter module.(ACTM)
5
a) Check connection of outdoor noise filter
circuit board.
b) Replace outdoor noise filter circuit board.
Refer to 11-9.
6
Replace outdoor power circuit board.
7
Replace outdoor controller circuit board (When
items above are checked but the units cannot
be repaired).
F5
(5201)
63H connector open
Abnormal if 63H connector circuit is open
for 3 minutes continuously after power sup-
ply.
63H: High-pressure switch
1
Disconnection or contact failure
of 63H connector on outdoor
controller circuit board
2
Disconnection or contact failure
of 63H
3
63H is working due to defective
parts.
4
Defective outdoor controller
circuit board
1
Check connection of 63H connector on
outdoor controller circuit board.
Refer to 11-9.
2
Check the 63H side of connecting wire.
3
Check continuity by tester.
Replace the parts if the parts are defective.
4
Replace outdoor controller circuit board.
OCH415A-1.qxp 08.2.21 8:17 AM Page 28