4. Installing the refrigerant piping

Fig. 4-3

   P100-P140

A

  Front piping cover

B

 Piping cover

C

 Stop valve

D

 Service panel

E

  Bend radius : 100 mm-150 mm

A

  Stop valve <Liquid side>

B

  Stop valve <Gas side>

C

 Service port

D

 Open/Close section

Fig. 4-4

Fig. 4-5

Fig. 4-6

C

H

A

I

E

B

(1)

(2)

4.3. Refrigerant piping (Fig. 4-3)

   For P100-P140

Remove the service panel 

D

 (3 screws) and the front piping cover 

A

 (2 screws) and 

rear piping cover 

B

 (2 screws).

1

  Perform refrigerant piping connections for the indoor/outdoor unit when the out-

door unit’s stop valve is completely closed.

2

  Vacuum-purge air from the indoor unit and the connection piping.

3

  After connecting the refrigerant pipes, check the connected pipes and the indoor 

unit for gas leaks. (Refer to 4.4 Refrigerant pipe airtight testing method)

4

  A high-performance vacuum pump is used at the stop valve service port to main-

tain a vacuum for an adequate time (at least 1 hour after reaching –101 kPa (5 
Torr)) in order to vacuum dry the inside of the pipes. Always check the degree of 
vacuum at the gauge manifold. If there is any moisture left in the pipe, the degree 
of vacuum is sometimes not reached with short-time vacuum application. 

   After vacuum drying, completely open the stop valves (both liquid and gas) for the 

outdoor unit. This completely links the indoor and outdoor refrigerant circuits.

 •  

If the vacuum drying is inadequate, air and water vapor remain in the refriger-
ant circuits and can cause abnormal rise of high pressure, abnormal drop of 
low pressure, deterioration of the refrigerant machine oil due to moisture, etc.

 •  

If the stop valves are left closed and the unit is operated, the compressor and 
control valves will be damaged.

 •  

Use a leak detector or soapy water to check for gas leaks at the pipe connec-
tion sections of the outdoor unit.

 •  

Do not use the refrigerant from the unit to purge air from the refrigerant lines.

 •  

After the valve work is completed, tighten the valve caps to the correct torque: 
20 to 25 N·m (200 to 250 kgf·cm).

     Failure to replace and tighten the caps may result in refrigerant leakage. In 

addition, do not damage the insides of the valve caps as they act as a seal to 
prevent refrigerant leakage.

5

  Use sealant to seal the ends of the thermal insulation around the pipe connection 

sections to prevent water from entering the thermal insulation.

4.4. Refrigerant pipe airtight testing method

(1) Connect the testing tools.
 •  

Make sure the stop valves 

A

 

B

 are closed and do not open them.

 •  

Add pressure to the refrigerant lines through the service port 

C

 of the liquid 

stop valve 

A

.

(2)  Do not add pressure to the speci

fi

 ed pressure all at once; add pressure little by 

little.

 

1

  Pressurize to 0.5 MPa (5 kgf/cm²G), wait 5 minutes, and make sure the pres-

sure does not decrease.

 

2

  Pressurize to 1.5 MPa (15 kgf/cm²G), wait 5 minutes, and make sure the pres-

sure does not decrease.

 

3

  Pressurize to 4.15 MPa (41.5 kgf/cm²G) and measure the surrounding tem-

perature and refrigerant pressure.

(3)  If the speci

fi

 ed pressure holds for about one day and does not decrease, the pipes 

have passed the test and there are no leaks.

 •  

If the surrounding temperature changes by 1 °C, the pressure will change by 
about 0.03 MPa (0.3 kgf/cm²G). Make the necessary corrections.

(4)  If the pressure decreases in steps (2) or (3), there is a gas leak. Look for the 

source of the gas leak.

4.5. Stop valve opening method

The stop valve opening method varies according to the outdoor unit model. Use the 
appropriate method to open the stop valves.
(1) Gas side of P100-P140 (Fig. 4-5)

1

  Remove the cap and turn the valve rod counterclockwise as far as it will go with 

the use of a 5 mm hexagonal wrench. Stop turning when it hits the stopper.
(ø 15.88: Approximately 13 revolutions)

2

  Make sure that the stop valve is open completely and rotate the cap back to its 

original position.

(2) Liquid side of P100-P140 (Fig. 4-6)

1

  Remove the cap and turn the valve rod counterclockwise as far as it will go with 

the use of a 4 mm hexagonal wrench. Stop turning when it hits the stopper.

   (ø9.52: Approximately 10 revolutions)

2

  Make sure that the stop valve is open completely and rotate the cap back to its 

original position.

Refrigerant pipes are protectively wrapped for P100-P140
•  

The pipes can be protectively wrapped up to a diameter of ø90 before or after 
connecting the pipes. Cut out the knockout in the pipe cover following the groove 
and wrap the pipes. 

Pipe inlet gap for P100-P140
•  

Use putty or sealant to seal the pipe inlet around the pipes so that no gaps remain. 
(If the gaps are not closed, noise may be emitted or water and dust will enter the 
unit and breakdown may result.)

H

  Double spanner section

 

 (Do not apply a spanner other than to this section. Doing 
so would cause coolant leaks.)

I

 Seal section

 

 (Seal the end of the heat insulation material at the pipe 
connection section with whatever seal material you have 
on hand so that water does not in

fi

 ltrate the heat insula-

tion material.)

A

 Valve

B

 Unit side

C

 Cap

D

  Local pipe side

E

 Pipe cover

F

 Service port

G

 Wrench hole

H

D

E

G

F

A

G

I

D

C

B

Precautions when using the charge valve (Fig. 4-7)

Do not tighten the service port too much when installing it, otherwise, the valve core 
could be deformed and become loose, causing a gas leak.
After positioning section 

B

 in the desired direction, turn section 

A

 only and tighten it.

Do not further tighten sections 

A

 and 

B

 together after tightening section 

A

.

 Warning:

When installing the unit, securely connect the refrigerant pipes before starting 
the compressor

.

* The 

fi

 gure to the left is an example only.

The stop valve shape, service port position,   
etc., may vary according to the model.

* Turn section 

A

 only.

(Do not further tighten sections 

A

 and 

B

 

together.)

C

 Charge hose

D

 Service port

A

B

C

D

Fig. 4-7

E

 Local pipe

F

  Sealed, same way for gas side

G

 Pipe cover

Содержание PUHZ-P HA Series

Страница 1: ...amente este manual y el manual de instalación de la unidad interior antes de instalar la unidad de aire acondicionado El idioma original del documento es el inglés Las versiones en los demás idiomas son traducciones del original MANUALE DI INSTALLAZIONE Per un uso sicuro e corretto leggere attentamente il presente manuale ed il manuale d installazione dell unità interna prima di installare il cond...

Страница 2: ... and moisture enter the unit electric shock or fire may result When installing or relocating or servicing the outdoor unit use only the specified refrigerant R410A to charge the refrigerant lines Do not mix it with any other refrigerant and do not allow air to remain in the lines If air is mixed with the refrigerant then it can be the cause of abnormal high pressure in the refrigerant line and may...

Страница 3: ...r compressor breakdown may result Use ester oil ether oil alkylbenzene oil small amount as the refrigeration oil applied to the flared sections If mineral oil is mixed in the refrigeration oil oil deterioration may result Do not use refrigerant other than R410A refrigerant If another refrigerant is used the chlorine will cause the oil to deteriorate Use a vacuum pump with a reverse flow check valv...

Страница 4: ...ition leave space as shown Do not install the optional air outlet guides for upward airflow 3 Obstacles at front only Fig 2 14 When using an optional air outlet guide the clearance for P125 P140 models is 1000 mm or more 4 Obstacles at front and rear only Fig 2 15 When using an optional air outlet guide the clearance for P125 P140 models is 1000 mm or more 5 Single parallel unit arrangement Fig 2 ...

Страница 5: ...rate thermal insulation for gas and liquid refrigerant pipes The indoor parts of the drain pipe should be wrapped with polyethylene foam insulation materials specific gravity of 0 03 thickness of 9 mm or more Apply thin layer of refrigerant oil to pipe and joint seating surface before tightening flare nut A Use 2 wrenches to tighten piping connections B Use leak detector or soapy water to check fo...

Страница 6: ...kgf cm G wait 5 minutes and make sure the pres sure does not decrease 3 Pressurize to 4 15 MPa 41 5 kgf cm G and measure the surrounding tem perature and refrigerant pressure 3 If the specified pressure holds for about one day and does not decrease the pipes have passed the test and there are no leaks If the surrounding temperature changes by 1 C the pressure will change by about 0 03 MPa 0 3 kgf ...

Страница 7: ... Additional refrigerant charging amount 21 30 m 31 40 m 41 50 m P100 50 m 30 m 0 6 kg 1 2 kg 1 8 kg P125 P140 0 6 kg 1 2 kg 4 Installing the refrigerant piping 4 7 For twin triple combination Refrigerant piping limitation of length height difference are shown in the figure Fig 4 8 A Indoor unit B Outdoor unit C Multi distribution pipe option D Height difference Indoor unit Outdoor unit Max 30 m E ...

Страница 8: ...top valves are completely open A protective sheet covers the surface of the DIP switch panel on the control board of the outdoor unit Remove the protective sheet to operate the DIP switches eas ily 7 2 Test run 7 2 1 Using SW4 in outdoor unit SW4 1 ON Cooling operation SW4 2 OFF SW4 1 ON Heating operation SW4 2 ON After performing the test run set SW4 1 to OFF After power is supplied a small click...

Страница 9: ...of wiring 2 A Outdoor unit B Indoor unit C Master remote controller D Subordinate remote controller E Standard 1 1 Refrigerant address 00 F Simultaneous twin Refrigerant address 01 G Simultaneous triple Refrigerant address 02 E SW 1 3 6 F SW 1 3 6 G SW 1 3 6 Red A B C D E SW1 CNDM 3 1 Fig 8 1 3 Because the unit automatically stops in about 2 to 3 minutes when the refrigerant collecting operation i...

Страница 10: ... The serial number is indicated on the SPEC NAME PLATE Sequential number for each unit 00001 99999 Month of manufacture A 1 B 2 C 3 D 4 E 5 F 6 G 7 H 8 J 9 K 10 L 11 M 12 Year of manufacture western calendar 2014 4 2015 5 ...

Страница 11: ...оком или возникновению пожара При установке перемещении или сервисном обслуживании наружного блока используйте только указанный хладагент R410A для заправки трубопроводов хладагента Не смешивайте его ни с каким другим хлада гентом и не допускайте наличия воздуха в трубопроводах Наличие воздуха в трубопроводах может вызывать скачки давления в результате которых может произойти взрыв или другие повр...

Страница 12: ...ы хладагента может произойти порча масла или поломка компрессо ра Используйте в качестве масла охлаждения для покрытия соединительных муфт масло сложного или простого эфира или алкинбензол в небольшом количестве Если в масле охлаждения присутствует минеральное масло может произойти порча масла Используйте только хладагент R410A В случае использования другого хладагента хлор может испортить масло И...

Страница 13: ... друга Не используйте дополнительные воздуховоды для восходящего потока воздуха 3 Окружающие предметы только спереди Fig 2 14 При использовании дополнительного воздуховода выходного отверстия расстояние для моделей P125 P140 должно быть 1000 мм или более 4 Окружающие предметы только спереди и сзади Fig 2 15 При использовании дополнительного воздуховода выходного отверстия расстояние для моделей P1...

Страница 14: ...ливайте тепловую изоляцию отдельно на трубы с газо образным и жидким хладагентом Внутренняя часть дренажной трубы должна быть обернута в пенополиэтиле новый изолирующий материал удельный вес 0 03 толщина 9 мм или более Нанесите тонкий слой масла хладагента на контактную поверхность труб и соединений перед тем как затягивать гайку с фланцем A Для затягивания трубных соединений используйте два гаечн...

Страница 15: ...4 15 МПа 41 5 кгс см G и измерьте температуру окружающего воздуха и давление хладагента 3 Если указанное давление держится в течение приблизительно одного дня и не уменьшается то трубы выдержали испытание и утечек нет При изменении температуры окружающего воздуха на 1 C давление изменя ется приблизительно на 0 03 МПа 0 3 кгс см G Произведите необходимые подстройки 4 Если на этапах 2 или 3 наблюдае...

Страница 16: ...ладагента для зарядки 21 30 м 31 40 м 41 50 м P100 50 м 30 м 0 6 кг 1 2 кг 1 8 кг P125 P140 0 6 кг 1 2 кг 4 Прокладка труб хладагента 4 7 Для комбинации двух трех блоков Ограничение по длине и разность высоты при прокладке труб показаны на ри сунке Fig 4 8 A Внутренний прибор B Наружный прибор C Распределительная труба опция D Разность высоты Внутренний прибор Наружный прибор макс 30 м E Разность ...

Страница 17: ...ора Для облегчения работы с DIP переключателями удалите защитный лист 7 2 Выполнение испытания 7 2 1 Использование SW4 в наружном блоке SW4 1 ON Вкл Работа в режиме охлаждения SW4 2 OFF Выкл SW4 1 ON Вкл Работа в режиме обогрева SW4 2 ON Вкл После выполнения пробного прогона установите SW4 1 на OFF Выкл После подачи питания внутри наружного прибора могут появиться шумы лег кие щелчки Это работа эл...

Страница 18: ... двойная утроенная выполнение электропроводки 2 не требуется A Наружный прибор B Внутренний прибор C Главный пульт дистанционного управления D Подчиненный пульт дистанционного управления E Стандарт 1 1 Адрес хладагента 00 F Одновременный двойник Адрес хладагента 01 G Одновременный тройник Адрес хладагента 02 E SW 1 3 6 F SW 1 3 6 G SW 1 3 6 Red A B C D E SW1 CNDM 3 1 Fig 8 1 3 Поскольку прибор авт...

Страница 19: ...Последовательные номера для каждого устройства 00001 99999 Месяц изготовления A 1 B 2 C 3 D 4 E 5 F 6 G 7 H 8 J 9 K 10 L 11 M 12 Год изготовления западный календарь 2014 4 2015 5 Название компании ООО Мицубиси Электрик РУС Адрес Россия 115054 Москва Космодамианская наб д 52 стр 1 ...

Страница 20: ...00 500 1000 400 600 1000 2000 100 150 1000 1500 500 800 150 1000 1500 400 600 2000 3000 300 500 Fig 2 6 Fig 2 7 Fig 2 8 Fig 2 9 Fig 2 10 Fig 2 11 Fig 2 12 Fig 2 13 Fig 2 14 Fig 2 15 Fig 2 16 Fig 2 17 Fig 2 18 100 200 200 300 100 200 150 250 150 250 1000 1500 300 500 Max 500 100 150 500 1000 Unit mm P125 P140 ...

Страница 21: ...ομηχανικές εφαρμογές através da presente declara sob sua única responsabilidade que os aparelhos de ar condicionado e bombas de calor abaixo descritos para uso residencial comercial e de indústria ligeira Série PUHZ P YHA é concebida para aplicações comerciais e industriais ligeiras erklærer hermed under eneansvar at de herunder beskrevne airconditionanlæg og varmepumper til brug i privat boligbyg...

Страница 22: ...6 Printed in UNITED KINGDOM HEAD OFFICE TOKYO BUILDING 2 7 3 MARUNOUCHI CHIYODA KU TOKYO 100 8310 JAPAN Please be sure to put the contact address telephone number on this manual before handing it to the customer ...

Отзывы: