Indication
Error
Check
code*
Outdoor controller board
Contents
Inspection method
LED1 (Green) LED2 (Red)
3 blinking 1 blinking
2 blinking
3 blinking
*
Check code displayed on remote controller
* * Refer to service manual for indoor unit.
4 blinking
5 blinking
6 blinking
7 blinking
1 blinking
2 blinking
3 blinking
4 blinking
4 blinking
Abnormality of discharging
temperature (TH4) and Comp.
surface temperature (TH34)
Abnormality of superheat due
to low discharge temperature
1
Check if stop valves are open.
2
Check if connectors (TH4, LEV -A, and LEV -B ) on outdoor controller
board are not disconnected.
3
Check if unit is filled with specified amount of refrigerant.
4
Measure resistance values among terminals on indoor valve and
outdoor linear exp ansion valve using a tester.
Abnormal high pressure (High
pressure switch 63H operated.)
Abnormal low pressure (Low
pressure switch 63L operated.)
Abnormality of outdoor fan
motor rotational speed
1
Check if indoor/ outdoor units have a short cycle on their air ducts.
2
Check if connector(63H)(63L) on outdoor controller board is not disconnected.
3
Check if heat exch anger and filter is not dirty.
4
Measure resistance values among terminals on linear exp ansion valve
using a tester.
1
Check if stop valves are open.
2
Check looseness, disconnection, and converse connection of
compressor wiring.
3
Measure resistance values among terminals on compressor using a tester.
4
Check if outdoor unit has a short cycle on its air duct.
Compressor overcurrent
breaking(Start-up locked)
Compressor overcurrent breaking
Abnormality of current sensor (P.B .)
Abnormality of power module
Open/ short of outdoor
thermistors (TH4, TH34)
Open/ short of outdoor thermistors
(TH3, TH32, TH33, TH6, TH7
and TH8)
1
Check if connectors(TH3, TH32, TH33, TH4, TH34 and TH7 / 6) on outdoor
controller board and connector (CN3) on outdoor power board are not
disconnected.
2
Measure resistance value of outdoor thermistors.
Abnormality of heatsink
temperature
1
Check if indoor/ outdoor units have a short cycle on their air ducts.
2
Measure resistance value of outdoor thermistor(TH8).
1
Check the outdoor fan motor.
2
Check if connector (TH3) (63HS) on outdoor controller board is disconnected.
Abnormality of voltage
1
Check looseness, disconnection, and converse connection of
compressor wiring.
2
Measure resistance value among terminals on compressor using a tester.
3
Check if power supply voltage decreases.
4
Check the wiring of CN52C.
5
Check the wiring of CNAF.
Abnormality of room temperature thermistor (TH1)
Abnormality of pipe temperature thermistor / Liq uid (TH2)
Abnormality of pipe temperature
thermistor/ Condenser-Evaporator
1
Check if connectors (CN20, CN21, CN29 and CN44) on indoor
controller board are not disconnected.
2
Measure resistance value of indoor thermistors.
Abnormality of drain sensor (DS)
Float switch connector open (FS)
Indoor drain overflow protection
1
Check if connector (CN31)(CN4F) on indoor controller board is not
disconnected.
2
Measure resistance value of indoor thermistors.
3
Measure resistance value among terminals on drain pump using
a tester.
4
Check if drain pump works.
5
Check drain function.
Freezing (cooling)/ overheating
(heating) protection
1
Check if indoor unit has a short cycle on its air duct.
2
Check if heat exch anger and filter is not dirty.
3
Measure resistance value on indoor and outdoor fan motors.
4
Check if the inside of refrigerant piping is not clogged.
Abnormality of pipe
temperature
1
Check if indoor thermistors(TH2 and TH5) are not disconnected from holder.
2
Check if stop valve is open.
3
Check converse connection of ex tension pipe. (on plural units connection)
4
Check if indoor/ outdoor connecting wire is connected correctly.
(on plural units connection)
P.35
P.36
P.35
P.38
P.36
P.38
P.38
P.39
P.38
P.36
P.35
P.36
P.36
P.37
* *
* *
* *
* *
P.41
P.41
Detailed
reference
page
Protection from overheat
operation (TH3)
OCH526C