( 5 ) O p eration data during emergenc y op eration
O p eration data
I ntake temp erature ( T H1 )
I ndoor p ip e temp erature ( T H2 )
I ndoor 2 - p h ase p ip e temp erature ( T H5 )
S et temp erature
P ressure saturation temp erature ( T
6 3HS
)
L iq uid temp erature ( T H3)
D isc h arge p ip e temp erature ( T H4 )
2 - p h ase p ip e temp erature ( T H6 )
A mb ient temp erature ( T H7 )
T emp erature differenc e c ode ( intake temp erature
−
set temp erature) ( T j )
D isc h arge sup erh eat ( S Hd)
S ub - c ool ( S C )
O p eration mode
C O O L
27
:
5
:
5
:
25
:
50
:
45
:
80
:
50
:
35
:
5
30
:
5
:
HE A T
20.5
:
45
:
50
:
22
:
50
:
5
:
80
:
5
:
7
:
5
30
:
5
:
(* 1)
(* 1)
(* 1)
(* 1)
(* 1)
(* 2)
(* 2)
R emarks
* 1: If the thermistor temperature data is normal (not open/ short), that data is loaded into the control as valid data.
When the unit enters emergency operation and TH values are mismatched, set the thermistors
to open/ short. And the unit runs emegency operation with the values listed above.
* 2: If one thermistor is set to open/ short, the values for each will be different from the list above.
[Ex ample] When liq uid pipe temperature thermistor (TH3) has an open or short circuit.
C O O L
45
:
Ta
Tc
5
:
5
:
Te
HE A T
5
:
Tb
Td
50
:
45
:
Tf
T h ermistor
TH3
TH6
TH4
TH5
TH2
T
63HS
Regard normal figure as effective data.
Regard normal figure as effective data.
—
—
—
—
—
Discharge superheat (SHd)
Cooling = TH4 T
63HS
= Tc Te
Heating = TH4 T
63HS
= Td Tf
Degree of subcooling (SC)
Cooling = T
63HS
H3 = Te 45
Heating = T
63HS
TH2 = Tf 45
Regard normal figure as effective data.
OCH526C