background image

7

4. Installing the refrigerant piping

A

A

  Stop valve <Liquid side>

B

  Stop valve <Gas side>

C

 Service port

D

 Open/Close section

E

 Local pipe

F

  Sealed, same way for gas side

G

 Pipe cover

Do not use a wrench here.

     Refrigerant leakage may result.

Use two wrenches here.

D

B

C

G

F

E

D

C

A

Fig. 4-4

Fig. 4-5

Fig. 4-6

4.4. Refrigerant pipe airtight testing method (Fig.4-4)

(1) Connect the testing tools.
 •  

Make sure the stop valves 

A

 

B

 are closed and do not open them.

 •  

Add pressure to the refrigerant lines through the service port 

C

 of the liquid 

stop valve 

A

.

(2)  Do not add pressure to the specifi ed pressure all at once; add pressure little by 

little.

 

1

  Pressurize to 0.5 MPa (5 kgf/cm

2

G), wait five minutes, and make sure the 

pressure does not decrease.

 

2

  Pressurize to 1.5 MPa (15 kgf/cm

2

G), wait fi ve minutes, and make sure the 

pressure does not decrease.

 

3

  Pressurize to 4.15 MPa (41.5 kgf/cm

2

G) and measure the surrounding tem-

perature and refrigerant pressure.

(3)  If the specifi ed pressure holds for about one day and does not decrease, the 

pipes have passed the test and there are no leaks.

 •  

If the surrounding temperature changes by 1 °C, the pressure will change by 
about 0.01 MPa (0.1 kgf/cm

2

G). Make the necessary corrections.

(4)  If the pressure decreases in steps (2) or (3), there is a gas leak. Look for the 

source of the gas leak.

4.5. Stop valve opening method

The stop valve opening method varies according to the outdoor unit model. Use the 
appropriate method to open the stop valves.
(1) Gas side (Fig. 4-5)

1

  Remove the cap, pull the handle toward you and rotate 1/4 turn in a counter-

clockwise direction to open.

2

  Make sure that the stop valve is open comletely, push in the handle and rotate 

the cap back to its original position.

(2) Liquid side (Fig. 4-6)

1

  Remove the cap and turn the valve rod counterclockwise as far as it will go with 

the use of a 4 mm hexagonal wrench. Stop turning when it hits the stopper.

 

 (ø9.52: Approximately 10 revolutions)

2

  Make sure that the stop valve is open completely, push in the handle and rotate 

the cap back to its original position.

Refrigerant pipes are protectively wrapped
•  

The pipes can be protectively wrapped up to a diameter of ø90 before or after 
connecting the pipes. Cut out the knockout in the pipe cover following the groove 
and wrap the pipes. 

Pipe inlet gap
•  

Use putty or sealant to seal the pipe inlet around the pipes so that no gaps re-
main. (If the gaps are not closed, noise may be emitted or water and dust will 
enter the unit and breakdown may result.)

4.6. Addition of refrigerant

•  

Additional charging is not necessary if the pipe length does not exceed 30 m.

•  

If the pipe length exceeds 30m, charge the unit with additional R410A refrigerant 
according to the permitted pipe lengths in the chart below.

 *  

When the unit is stopped, charge the unit with the additional refrigerant 
through the liquid stop valve after the pipe extensions and indoor unit have 
been vacuumized.

 

 

 When the unit is operating, add refrigerant to the gas check valve using a 
safety charger. Do not add liquid refrigerant directly to the check valve.

 *  

After charging the unit with refrigerant, note the added refrigerant amount on 
the service label (attached to the unit).

 

 

 Refer to the “1.5. Using R410A refrigerant air conditioners” for more informa-
tion.

•  

Be careful when installing multiple units. Connecting to an incorrect indoor unit 
can lead to abnormally high pressure and have a serious effect on operation 
performance.

Model

Permitted 

pipe 

length

Permitted 

vertical 

difference

Additional refrigerant charging amount

31 - 40 m 41 - 50 m 51 - 60 m 61 - 75 m

HRP71,

100,125

-75 m

-30 m

0.6 kg

1.2 kg

1.8 kg

2.4 kg

I

  Double spanner section

 

 (Do not apply a spanner other than to this section. 
Doing so would cause coolant leaks.)

J

 Seal section

 

 (Seal the end of the heat insulation material at 
the pipe connection section with whatever seal 
material you have on hand so that water does not 
infi ltrate the heat insulation material.)

A

 Valve

B

 Unit side

C

 Handle

Cap

E

  Local pipe side

F

 Pipe cover

G

 Service port

H

 Wrench hole

I

H

B

Precautions when using the charge valve (Fig.4-7)

Do not tighten the service port too much when installing it, otherwise, the valve core
could be deformed and become loose, causing a gas leak.
After positioning section 

B

 in the desired direction, turn section 

A

 only and tighten it.

Do not further tighten sections 

A

 and 

B

 together after tightening section 

A

.

* The fi gure to the left is an example only.
  The stop valve shape, service port position,
  etc., may vary according to the model.
* Turn section 

A

 only.

  (Do not further tighten sections 

A

 and 

B

   together.)

C

 Charge hose

D

 Service port

A

B

C

D

Fig. 4-7

(1)

(2)

Содержание PUHZ-HA2

Страница 1: ...n de airconditioner begint MANUAL DE INSTALACIÓN Para un uso correcto y seguro lea detalladamente este manual y el manual de instalación de la unidad interior antes de instalar la unidad de aire acondicionado MANUALE DI INSTALLAZIONE Per un uso sicuro e corretto leggere attentamente il presente manuale ed il manuale d installazione dell unità interna prima di installare il condizionatore d aria EΓ...

Страница 2: ... air conditioner use only the specified refrig erant R410A to charge the refrigerant lines Do not mix it with any other refrigerant and do not allow air to remain in the lines Air enclosed in the lines can cause pressure peaks resulting in a rupture and other hazards Use only accessories authorized by Mitsubishi Electric and ask a dealer or an authorized technician to install them If accessories a...

Страница 3: ...eration The refrigerant pipes are hot or cold depending on the condition of the flowing refrigerant If you touch the pipes burns or frostbite may result After stopping operation be sure to wait at least five minutes before turn ing off the main power switch Otherwise water leakage or breakdown may result 1 5 Using R410A refrigerant air conditioners Caution Do not use refrigerant other than R410A r...

Страница 4: ...de by side In addition leave space as shown Do not install the optional air outlet guides for upward airflow 3 Obstacles at front only Fig 2 14 When using an optional air outlet guide the clearance for HRP71 100 125 models is 1000 mm or more 4 Obstacles at front and rear only Fig 2 15 When using an optional air outlet guide the clearance for HRP71 100 125 models is 1000 mm or more 5 Single paralle...

Страница 5: ...hoons or strong winds An incorrectly installed unit may fall down and cause damage or injuries mm M10 3 8 bolt Base As long as possible Vent Max 30 Set deep in the ground 600 600 Min 360 175 175 Min 10 950 25 330 370 4 Installing the refrigerant piping 4 1 Precautions for devices that use R410A refrigerant Refer to page 3 for precautions not included below on using air conditioners with R410A refr...

Страница 6: ...88 5 8 0 0 5 1 0 1 5 ø19 05 3 4 0 0 5 1 0 1 5 4 Installing the refrigerant piping Fig 4 3 AFront piping cover BPiping cover CStop valve DService panel EBend radius 100mm 150mm 4 3 Refrigerant piping Fig 4 3 Remove the service panel D three screws and the front piping cover A two screws and rear piping cover B two screws 1 Perform refrigerant piping connections for the indoor outdoor unit when the ...

Страница 7: ...ockout in the pipe cover following the groove and wrap the pipes Pipe inlet gap Use putty or sealant to seal the pipe inlet around the pipes so that no gaps re main If the gaps are not closed noise may be emitted or water and dust will enter the unit and breakdown may result 4 6 Addition of refrigerant Additional charging is not necessary if the pipe length does not exceed 30 m If the pipe length ...

Страница 8: ...s to confirm if the pipes can be used If the diameter of the existing gas side pipe is bigger than the specified diameter turn SW8 1 on Measure the existing pipe thickness and check for damage The existing pipe thickness meets specifica tions and the pipes are not damaged Check if the existing air conditioner can operate After operating the cooling system for about 30 minutes do a pump down work D...

Страница 9: ...rminals are NOT electrically insulataed by the transformer or other device Notes 1 Wiring size must comply with the applicable local and national code 2 Power supply cords and Indoor Outdoor unit connecting cords shall not be lighter than polychloroprene sheathed flexible cord Design 60245 IEC 57 3 Use an earth wire which is longer than the other cords so that it will not become disconnected when ...

Страница 10: ...l on the control board of the outdoor unit Remove the protective sheet to operate the DIP switches easily 7 3 Test run 7 3 1 Using SW4 in outdoor unit SW4 1 ON Cooling operation SW4 2 OFF SW4 1 ON Heating operation SW4 2 ON After performing the test run set SW4 1 to OFF After power is supplied a small clicking noise may be heard from the inside of the outdoor unit The electronic expansion valve is...

Страница 11: ...win Refrigerant address 01 G Simultaneous triple Refrigerant address 02 E SW 1 3 6 F SW 1 3 6 G SW 1 3 6 Red A B C D E SW1 CNDM 3 1 Fig 9 1 3 Because the unit automatically stops in about two to three minutes after the refrigerant collecting operation LED1 and LED2 are lit be sure to quickly close the gas stop valve When LED1 and LED2 are lit and the outdoor unit is stopped open the liquid stop va...

Страница 12: ......

Страница 13: ...ig 2 14 Fig 2 15 Fig 2 16 Fig 2 17 Fig 2 18 Fig 2 10 Fig 2 9 Fig 2 8 Fig 2 6 150 300 1000 Max 500 200 300 200 1000 150 1000 250 250 1500 500 Max 500 300 1500 500 1500 Max 300 1500 1500 500 1000 600 2000 150 1500 600 3000 500 1500 800 150 ...

Страница 14: ...RMAN HOUSE 1 GEORGE STREET UXBRIDGE MIDDLESEX UB8 1QQ U K RG79D355H03 Printed in Japan This product is designed and intended for use in the residential commercial and light industrial environment The product at hand is based on the following EU regulations Low Voltage Directive 73 23 EEC Electromagnetic Compatibility Directive 89 336 EEC ...

Отзывы: