background image

10

This air conditioner (outdoor unit) can detect refrigerant leakage which may happen
during a long period of use. In order to enable the leakage detection, the following
settings are required to let the unit memorize the initial conditions (initial learning).

Caution:

Make sure to perform the “7. Test run” and confi rm the unit works without 
any problems, before starting the following settings.

 How to select the “Refrigerant Leakage Detection” mode

Detection is possible regardless the unit’s operation (ON or OFF).

1

 Press             button for more than three seconds to switch to the maintenance

mode.
[Display    ] 

MAINTENANCE

 How to start the initial learning

2

 Press                          button and select the [GAS LEAK TEST START] (Fig. 8-2)

* The initial learning for the leakage detection is always done once after the new

installation or the data reset.

TEST

A

 CLOCK 

7. Test run

7.1. Before test run

  After completing installation and the wiring and piping of the indoor and 

outdoor units, check for refrigerant leakage, looseness in the power sup-
ply or control wiring, wrong polarity, and no disconnection of one phase in 
the supply.

  Use a 500-volt megohmmeter to check that the resistance between the 

power supply terminals and ground is at least 1.0M

"

.

  Do not carry out this test on the control wiring (low voltage circuit) termi-

nals.

 Warning:

Do not use the air conditioner if the insulation resistance is less than 1.0M

"

.

Insulation resistance

After installation or after the power source to the unit has been cut for an extended 
period, the insulation resistance will drop below 1 M

"

 due to refrigerant accumulat-

ing in the compressor. This is not a malfunction. Perform the following procedures.
1.  Remove the wires from the compressor and measure the insulation resistance of 

the compressor.

2.  If the insulation resistance is below 1 M

"

, the compressor is faulty or the resis-

tance dropped due the accumulation of refrigerant in the compressor.

3.  After connecting the wires to the compressor, the compressor will start to warm 

up after power is supplied. After supplying power for the times indicated below, 
measure the insulation resistance again.

 •  

The insulation resistance drops due to accumulation of refrigerant in the com-
pressor. The resistance will rise above 1 M

"

 after the compressor is warmed 

up for four hours.

 

 

 (The time necessary to warm up the compressor varies according to atmo-
spheric conditions and refrigerant accumulation.)

 •  

To operate the compressor with refrigerant accumulated in the compressor, 
the compressor must be warmed up at least 12 hours to prevent breakdown.

4.  If the insulation resistance rises above 1 M

"

, the compressor is not faulty.

 Caution:

•  

The compressor will not operate unless the power supply phase connec-
tion is correct.

•  

Turn on the power at least 12 hours before starting operation.

-  

Starting operation immediately after turning on the main power switch can result 
in severe damage to internal parts. Keep the power switch turned on during the 
operational season.

  The followings must be checked as well.

•  

The outdoor unit is not faulty. LED1 and LED2 on the control board of the out-
door unit fl ash when the outdoor unit is faulty.

•  

Both the gas and liquid stop valves are completely open.

•  

A protective sheet covers the surface of the DIP switch panel on the control 
board of the outdoor unit. Remove the protective sheet to operate the DIP 
switches easily.

7.3. Test run

7.3.1. Using SW4 in outdoor unit

SW4-1

ON

Cooling operation

SW4-2

OFF

SW4-1

ON

Heating operation

SW4-2

ON

*  After performing the test run, set SW4-1 to OFF.
•  

After power is supplied, a small clicking noise may be heard from the inside of 
the outdoor unit. The electronic expansion valve is opening and closing. The unit 
is not faulty.

•  

A few seconds after the compressor starts, a clanging noise may be heard from 
the inside of the outdoor unit. The noise is coming from the check valve due to 
the small difference in pressure in the pipes. The unit is not faulty.

The test run operation mode cannot be changed by DIP switch SW4-2 during 
the test run. (To change the test run operation mode during the test run, stop 
the test run by DIP switch SW4-1. After changing the test run operation mode, 
resume the test run by switch SW4-1.)

7.3.2. Using remote controller

Refer to the indoor unit installation manual.

Note : Occasionally, vapor that is made by the defrost operation may seem
           as if smoke come up from the outdoor unit.

7.2. Unit replacement operation

 

When reusing existing pipes that carried R22 refrigerant, replacement op-

eration must be performed before performing a test run.

• If new pipes are used, these procedures are not necessary.

Replacement operation procedures

1

 Supply power.

2

 Set DIP switch SW8-2 on the control board of the outdoor unit to ON to start

replacement operation.
* The replacement operation is performed using the cooling system. Cool air will
   fl ow from the indoor unit during the replacement operation.
* During the replacement operation, TEST RUN is displayed on the remote 

controller and LED1 and LED2 on the control board of the outdoor unit fl ash 
together.

3

 The duration of the replacement operation is determined by the length of the 

piping. Always perform the replacement operation for longer than the stipulated 
time.
* Use one of the following methods to complete the replacement operation. 

When the replacement operation ends, the unit will automatically stop.

(1)Set SW8-2 from ON to OFF (when ending a replacement operation of less

than 2 hours).
• Because the replacement operation restarts each time SW8-2 is set from

OFF to ON, always perform the replacement operation for longer than the
stipulated time.
Required replacement operation times

Pipe Length

Replacement Operation Time

0 to 20 meters

30 minutes or more

21 to 30 meters

45 minutes or more

31 to 50 meters

60 minutes or more

(2)Allow the replacement operation to automatically stop after 2 hours (opera-

tion stops while SW8-2 is still in the ON position).
• When the replacement operation has ended automatically after 2 hours of

operation, there is no need to set SW8-2 from ON to OFF; normal air con-
ditioning operation is possible with SW8-2 set to ON. However, to repeat 
the replacement operation, SW8-2 fi rst has to be set to OFF and then to 
ON.

* If the indoor temperature is less than 15°C, the compressor will operate inter-

mittently but the unit is not faulty.

8.Initial settings for refrigerant leakage detection function

[Display

]

Remote control button positions

D

A

C

B

Operation mode Compressor information Outdoor unit information Indoor unit information

Confirm

Activate/cancel maintenance mode

GAS LEAK

JUDGE

GAS LEAK

TEST START 

Refrigerant leakage
detection judgment

Refrigerant
leakage detection
(initial teaching)

A

Fig. 8-1

Fig. 8-2

Содержание PUHZ-HA2

Страница 1: ...n de airconditioner begint MANUAL DE INSTALACIÓN Para un uso correcto y seguro lea detalladamente este manual y el manual de instalación de la unidad interior antes de instalar la unidad de aire acondicionado MANUALE DI INSTALLAZIONE Per un uso sicuro e corretto leggere attentamente il presente manuale ed il manuale d installazione dell unità interna prima di installare il condizionatore d aria EΓ...

Страница 2: ... air conditioner use only the specified refrig erant R410A to charge the refrigerant lines Do not mix it with any other refrigerant and do not allow air to remain in the lines Air enclosed in the lines can cause pressure peaks resulting in a rupture and other hazards Use only accessories authorized by Mitsubishi Electric and ask a dealer or an authorized technician to install them If accessories a...

Страница 3: ...eration The refrigerant pipes are hot or cold depending on the condition of the flowing refrigerant If you touch the pipes burns or frostbite may result After stopping operation be sure to wait at least five minutes before turn ing off the main power switch Otherwise water leakage or breakdown may result 1 5 Using R410A refrigerant air conditioners Caution Do not use refrigerant other than R410A r...

Страница 4: ...de by side In addition leave space as shown Do not install the optional air outlet guides for upward airflow 3 Obstacles at front only Fig 2 14 When using an optional air outlet guide the clearance for HRP71 100 125 models is 1000 mm or more 4 Obstacles at front and rear only Fig 2 15 When using an optional air outlet guide the clearance for HRP71 100 125 models is 1000 mm or more 5 Single paralle...

Страница 5: ...hoons or strong winds An incorrectly installed unit may fall down and cause damage or injuries mm M10 3 8 bolt Base As long as possible Vent Max 30 Set deep in the ground 600 600 Min 360 175 175 Min 10 950 25 330 370 4 Installing the refrigerant piping 4 1 Precautions for devices that use R410A refrigerant Refer to page 3 for precautions not included below on using air conditioners with R410A refr...

Страница 6: ...88 5 8 0 0 5 1 0 1 5 ø19 05 3 4 0 0 5 1 0 1 5 4 Installing the refrigerant piping Fig 4 3 AFront piping cover BPiping cover CStop valve DService panel EBend radius 100mm 150mm 4 3 Refrigerant piping Fig 4 3 Remove the service panel D three screws and the front piping cover A two screws and rear piping cover B two screws 1 Perform refrigerant piping connections for the indoor outdoor unit when the ...

Страница 7: ...ockout in the pipe cover following the groove and wrap the pipes Pipe inlet gap Use putty or sealant to seal the pipe inlet around the pipes so that no gaps re main If the gaps are not closed noise may be emitted or water and dust will enter the unit and breakdown may result 4 6 Addition of refrigerant Additional charging is not necessary if the pipe length does not exceed 30 m If the pipe length ...

Страница 8: ...s to confirm if the pipes can be used If the diameter of the existing gas side pipe is bigger than the specified diameter turn SW8 1 on Measure the existing pipe thickness and check for damage The existing pipe thickness meets specifica tions and the pipes are not damaged Check if the existing air conditioner can operate After operating the cooling system for about 30 minutes do a pump down work D...

Страница 9: ...rminals are NOT electrically insulataed by the transformer or other device Notes 1 Wiring size must comply with the applicable local and national code 2 Power supply cords and Indoor Outdoor unit connecting cords shall not be lighter than polychloroprene sheathed flexible cord Design 60245 IEC 57 3 Use an earth wire which is longer than the other cords so that it will not become disconnected when ...

Страница 10: ...l on the control board of the outdoor unit Remove the protective sheet to operate the DIP switches easily 7 3 Test run 7 3 1 Using SW4 in outdoor unit SW4 1 ON Cooling operation SW4 2 OFF SW4 1 ON Heating operation SW4 2 ON After performing the test run set SW4 1 to OFF After power is supplied a small clicking noise may be heard from the inside of the outdoor unit The electronic expansion valve is...

Страница 11: ...win Refrigerant address 01 G Simultaneous triple Refrigerant address 02 E SW 1 3 6 F SW 1 3 6 G SW 1 3 6 Red A B C D E SW1 CNDM 3 1 Fig 9 1 3 Because the unit automatically stops in about two to three minutes after the refrigerant collecting operation LED1 and LED2 are lit be sure to quickly close the gas stop valve When LED1 and LED2 are lit and the outdoor unit is stopped open the liquid stop va...

Страница 12: ......

Страница 13: ...ig 2 14 Fig 2 15 Fig 2 16 Fig 2 17 Fig 2 18 Fig 2 10 Fig 2 9 Fig 2 8 Fig 2 6 150 300 1000 Max 500 200 300 200 1000 150 1000 250 250 1500 500 Max 500 300 1500 500 1500 Max 300 1500 1500 500 1000 600 2000 150 1500 600 3000 500 1500 800 150 ...

Страница 14: ...RMAN HOUSE 1 GEORGE STREET UXBRIDGE MIDDLESEX UB8 1QQ U K RG79D355H03 Printed in Japan This product is designed and intended for use in the residential commercial and light industrial environment The product at hand is based on the following EU regulations Low Voltage Directive 73 23 EEC Electromagnetic Compatibility Directive 89 336 EEC ...

Отзывы: