2. Temperature range
Cooling
Heating
Indoor temperature
Wet-bulb temperature
10~25˚C [50~77˚F] (Note 1)
Dry-bulb temperature
15~28˚C [59~82˚F]
Outdoor temperature
Dry-bulb temperature
-5~43˚C [23~109˚F]
Wet-bulb temperature
-20~15.5˚C [-4~60˚F]
Standard type
Note 1. If units are operated for a long time at the dew point temperature of 23˚C [73˚F] or more, condensate may collect and drip from the indoor
units. If the units are operated under such conditions, cover the entire surface of all indoor units with insulating materials with a thickness of
between 0 and 20 mm [13/16 in.] to prevent condensate from collecting.
Cooling
Heating (Note 2)
Indoor temperature
Wet-bulb temperature
15~35˚C [50~95˚F]
Dry-bulb temperature
0~20˚C [32~68˚F]
Outdoor temperature
Dry-bulb temperature
20~43˚C [68~109˚F]
Wet-bulb temperature
-4~15.5˚C [24~60˚F]
Fresh air intake type
Note 2. If the indoor intake air is pretreated to 0
˚C
in the primary treatment, the unit can be operated in the outdoor intake air temperature range of
between -20 and 15.5
˚C
WB [-4 and 60˚FWB].