12
•PFAV-P900VM-E-F
Minimum necessary dimension.
Indoor unit
Required space for service and air flow
Secure the proper space for installation work
such as piping and wiring separately.
Please secure the size of *sign when you serve
the air filter from the right side of the main body.
Notes 1.Please secure the size in the service space of the air filter(*sign)
for a left side or a right side of the unit.
2.Be sure to wire the transmission line and power line separately.
3.When the room in which the unit is installed is airtight,
the pressure in the room may become negative.
This may result in problems such as the door to becoming difficult
to open etc.
To avoid these kinds of problems please ensure that a small amount of
air is able to ventilate the room via some kind of small hole or vent.
4.Connect by using the connecting pipes that are supplied.
(Size on inside)
(Size on inside)
2
5
6
3
4
(Size on inside)
8
7
2
1
5
6
Air filter
12
5
6
1
(Size on inside)
476
56
439
606
30
12
476
110X4=440
18
20-ø4.3Holes
606
110X4=440
83
42
750
500
1000
400
580
100
875
810
740
450
220
150
112
493
994
741
70
35
10
1212
106
200X5=1000
(599)
106
300
195
715
25
30
*750
(106)
1460
200X7=1400
(146)
*750
30
200
10
(50)
1722
50
1045
976
300
1830
30
615
75
1822
1774
1750
140
100
490
220
150
191
261
Supply air duct flange
28-ø4.3Holes
note:1
Air filter service space
Remote controller
Supply air duct flange
Drain hole<Lower side>······Rc 1
Earth terminal(installed in the control box)······M5
Wiring hole(The outdoor unit connection,Transmission line)······ø38
For mounting anchor bolt 4-ø15 Holes
Wiring hole······ø62
Drain hole<Upper part>······Rc 1 1/4
Refrigerant pipe<Liquid>···ø19.05 brazed
Refrigerant pipe<Gas>···ø34.93 brazed
Designation
NO.
1
2
3
4
5
6
7
8
Unit:mm
Содержание PUHY-P250YHM-A
Страница 1: ...Model PUHY P Y S HM A PFAV P VM E F DATA BOOK AIR CONDITIONING SYSTEMS ...
Страница 91: ...89 4 An Example of a System to which an MA Remote Controller is connected P750 P900 F models only ...
Страница 92: ...90 ...
Страница 93: ...91 L2 L31 L4 L32 200m 656ft ...
Страница 95: ...93 3 Emergency Operation Mode ...
Страница 96: ...94 ...
Страница 98: ...96 ...
Страница 99: ...97 ...