background image

9

GB

D

F

I

NL

E

P

GR

RU

TR

[Fig. 6.3.1]

 

(P.3)

A

“0-0 gas” mark

B

“INNER” mark

C

“OUTER” mark

D

Flare insulation (2)

E

Refrigerant piping (gas)

F

Refrigerant piping (liquid)

G

Field refrigerant piping

H

Pipe insulation (1)

I

Insulation material

J

Flare

K

Pull in this direction.

L

Insulation material

M

Flare

N

There must be no gap.

O

Move to the original position.

[Fig. 6.3.2]

 

(P.3)

(figure showing the flare insulation)

A

Field refrigerant piping

B

There must be no gap.

C

Unit body plate

D

OUTER

E

INNER

F

Unit body

G

Provided flare insulation (2)

[Fig. 6.3.3]

 

(P.3)

A

Tape (3)

B

Fasten with tape.

C

Provided tie band (4)

Notes:

*1

Insert the flare nut into the field refrigerant piping. Pull the insulation

material back at the area where it will be flared, then return it to its

original position after performing the flare work.

Exposing copper piping may result in condensation forming. Be ex-

tremely careful when performing this operation.

*2

There must be no gap.

*3, *4 There must be no gap. Slit should be on the top.

7. Connecting refrigerant pipes and drain pipes

7.1. Refrigerant piping work

This piping work must be done in accordance with the installation manuals for both

outdoor unit and BC controller (simultaneous cooling and heating series R2).

Series R2 is designed to operate in a system that the refrigerant pipe from an

outdoor unit is received by BC controller and branches at the BC controller to

connect between indoor units.

For constraints on pipe length and allowable difference of elevation, refer to

the outdoor unit manual.

The method of pipe connection is flare connection.

Cautions on refrigerant piping

s

s

s

s

s

Be sure to use non-oxidative brazing for brazing to ensure that no for-

eign matter or moisture enter into the pipe.

s

s

s

s

s

Be sure to apply refrigerating machine oil over the flare connection seat-

ing surface and tighten the connection using a double spanner.

s

s

s

s

s

Provide a metal brace to support the refrigerant pipe so that no load is

imparted to the indoor unit end pipe. This metal brace should be pro-

vided 50 cm away from the indoor unit’s flare connection.

 Warning:

When installing and moving the unit, do not charge it with refrigerant other

than the refrigerant (R407C or R22) specified on the unit.

- Mixing of a different refrigerant, air, etc. may cause the refrigerant cycle to mal-

function and result in severe damage.

 Caution:

• Use refrigerant piping made of C1220 (CU-DHP) phosphorus deoxidized

copper as specified in the JIS H3300 “Copper and copper alloy seamless

pipes and tubes”. In addition, be sure that the inner and outer surfaces of

the pipes are clean and free of hazardous sulphur, oxides, dust/dirt, shav-

ing particles, oils, moisture, or any other contaminant.

• Never use existing refrigerant piping.

- The large amount of chlorine in conventional refrigerant and refrigerator oil

in the existing piping will cause the new refrigerant to deteriorate.

• Store the piping to be used during installation indoors and keep both

ends of the piping sealed until just before brazing.

- If dust, dirt, or water gets into the refrigerant cycle, the oil will deteriorate and

the compressor may fail.

• Use Suniso 4GS or 3GS (small amount) refrigerator oil to coat the flare

and flange connection part. (For models using R22)

• Use ester oil, ether oil or alkylbenzene (small amount) as the refrigerator

oil to coat flares and flange connections. (For models using R407C)

- The refrigerant used in the unit is highly hygroscopic and mixes with water

and will degrade the refrigerator oil.

7.2. Drain piping work

[Fig. 7.2.1] (P.3)

A: 25 cm
B: 1.5 – 2 m

A

Downward pitch of more than 1/100

B

Insulating material

C

Metal brace

[Fig. 7.2.2] (P.3)

D

Indoor unit

E

Take as large as possible. About 10 cm

F

Collected pipes

[Fig. 7.2.3] (P.3)

C: 30 cm

G

Drain hose (Accessory)

s

s

s

s

s

Be sure to use the supplied drain hose (Accessory).

H

Less than 300 mm

I

Hard vinyl chloride 90° elbow (field supply)

J

Hard vinyl chloride (VP-25) (field supply)

K

Tie band (small) (Accessory)

s

s

s

s

s

Connect each connection with vinyl chloride adhesive. But never use

any adhesive over the indoor unit discharge port. Otherwise the drain-up

mechanism cannot be serviced later. Also, the end connection may be

eroded by resin and so cracked.

1. Ensure that the drain piping is downward (pitch of more than 1/100) to the

outdoor (discharge) side. Do not provide any trap or irregularity on the way.

(

1

)

2. Ensure that any cross-wise drain piping is less than 20 m (excluding the differ-

ence of elevation). If the drain piping is long, provide metal braces to prevent it

from waving. Never provide any air vent pipe. Otherwise drain may be ejected.

3. Use a hard vinyl chloride pipe VP-25 (with an external diameter of 32 mm) for

drain piping.

4. Ensure that collected pipes are 10 cm lower than the unit body’s drain port as

shown in 

2

.

5. Do not provide any odor trap at the drain discharge port.
6. Put the end of the drain piping in a position where no odor is generated.
7. Do  not  put  the  end  of  the  drain  piping  in  any  drain  where  ionic  gases  are

generated.

8. The intake of the drain piping can be made 30 cm higher than the drain dis-

charge port. If there are some obstacles under the ceiling, use elbows to make

it at least height according to the site. (

3

)

Note:

If the rise portion is long, there will be a lot of returned water in an operation

stop, generating slime or odor during off-season. Ensure that the rise por-

tion is at a minimum.

 Caution:

Pipe the drain piping to ensure that it discharges drain, and insulate it to

prevent dew condensation. A failure to the piping work may cause water

leakage and so wet your property.

7.3. Confirming drain discharge

s

s

s

s

s

Make sure that the drain-up mechanism operates normally for discharge

and that there is no water leakage from the connections.

Be sure to confirm the above in a period of heating operation.

Be sure to confirm the above before ceiling work is done in the case of a new

construction.

Содержание PLFY-P-VLMD-A

Страница 1: ...leggere attentamente questo manuale di installazione prima di installare il condizionatore d aria INSTALLATIEHANDLEIDING Voor een veilig en juist gebruik moet u deze installatiehandleiding grondig doorlezen voordat u de airconditioner installeert MANUAL DE INSTALAÇÃO Para segurança e utilização correctas leia atentamente este manual de instalação antes de instalar a unidade de ar condicionado E XE...

Страница 2: ...2 9 mounting hole G 4 ø2 9 mounting hole 3 2 Fig 3 2 1 H D 630 E 550 40 40 D A E B 102 102 A A B B C F B A D 50 10 G C A Nut B Washer supplied with the unit body C Hanging bolt ø10 M10 screw D Ceiling hole dimensions E Hanging bolt pitch F Hanging bolt G Finished ceiling surface H Hanging bracket A D C B A Drain pipe side B Unit body C Packing cap D Lifting machine B A B Indoor unit s bottom surfa...

Страница 3: ...INNER F Unit body G Provided flare insulation 2 A Tape 3 B Fasten with tape C Provided tie band 4 figure showing the flare insulation D I C H G K I J 3 C 30 cm G Drain hose Accessory s s s s s Be sure to use the supplied drain hose Accessory H Less than 300 mm I Hard vinyl chloride 90 elbow field supply J Hard vinyl chloride VP 25 field supply K Tie band small Accessory D D D E F 2 D Indoor unit E...

Страница 4: ...ON SW14 N0 N0 W254613G03 FP AD P JP2 JP3 JP4 CN82 8 1 6 1 10 1 240V 220V SW5 JP1 SWC SWA 1 3 2 0 SW12 10 0 SW11 1 0 Address board Fig 8 2 5 G I J J J K K K F J J L K H 1 3 L1 L2 L4 l L3 2 G Outdoor unit H Earth I BC controller J Indoor unit K Remote controller L Non polarized 2 wire Fig 8 2 1 A A C TB5 TB5 S M1M2 S M1M2 C B TB3 M1M2 A A C TB5 TB15 TB5 TB15 S M1M2 S M1M2 B TB3 M1M2 2 1 C 2 1 Fig 8 ...

Страница 5: ...y limit even if the refrigerant should leak Consult the dealer regarding the appropriate measures to prevent the safety limit from being exceeded Should the refrigerant leak and cause the safety limit to be exceeded hazards due to lack of oxygen in the room could result When moving and reinstalling the air conditioner consult the dealer or an authorized technician If the air conditioner is install...

Страница 6: ...eteriorate Do not use the following tools that are used with conventional refriger ants Gauge manifold charge hose gas leak detector reverse flow check valve refrigerant charge base vacuum gauge refrigerant recovery equipment If the conventional refrigerant and refrigerator oil are mixed in the R407C the refrigerant may deteriorated If water is mixed in the R407C the refrigerator oil may deteriora...

Страница 7: ...the back surface of each split flow duct end connection is insulating material Use a cutter knife to cut the insulating material along the end connection To adjust the fresh air intake capacity cut the two places as shown in the figure at right and rotate the intake 3 3 Combining indoor units with outdoor units For combining indoor units with outdoor units refer to the outdoor unit installation ma...

Страница 8: ... Packing cap D Lifting machine Pipe size Insulating material s thickness 6 4 mm to 25 4 mm More than 10 mm 28 6 mm to 38 1 mm More than 15 mm 2 If the unit is used on the highest story of a building and under conditions of high temperature and humidity it is necessary to use pipe size and insulating material s thickness more than those given in the table above 3 If there are customer s specificati...

Страница 9: ...e the new refrigerant to deteriorate Store the piping to be used during installation indoors and keep both ends of the piping sealed until just before brazing If dust dirt or water gets into the refrigerant cycle the oil will deteriorate and the compressor may fail Use Suniso 4GS or 3GS small amount refrigerator oil to coat the flare and flange connection part For models using R22 Use ester oil et...

Страница 10: ...cc D Water E Filling port Building clinic hospital or communications station without noise supposedly generated from inverter equipment private power gen erator high frequency medical equipment radio used communications equipment and so on Residence or independent store without noise Facility example for noise judgment All facilities VCTF VCTFK CVV CVS VVR VVF VCT or shielding wire CVVS or CPEVS S...

Страница 11: ...ol board to ON The setting of SW1 7 and SW1 8 as necessary also makes it possible to adjust the air flow at a time when the heating thermometer is OFF 8 2 Connecting remote controller indoor and outdoor transmission cables Remote contoroller is optionally available Connect indoor unit TB5 and outdoor unit TB3 Non polarized 2 wire The S on indoor unit TB5 is a shielding wire connection For specific...

Страница 12: ...t the contact address telephone number on this manual before handing it to the customer The product at hand is based on the following EU regulations Low Voltage Directive 73 23 EEC Electromagnetic Compatibility Directive 89 336 EEC This product is designed and intended for use in the residential commer cial and light industrial environment ...

Отзывы: