5. Installing the unit

5.2. Confirming the unit’s position and fix-

ing hanging bolts

s

s

s

s

s

Use the gage supplied with the panel to confirm that the unit body and

hanging bolts are positioned in place. If they are not positioned in place,

it may result in dew drops due to wind leak. Be sure to check the positional

relationship.

s

s

s

s

s

Use a level to check that the surface indicated by 

A

A

A

A

A

 is at level. Ensure

that the hanging bolt nuts are tightened to fix the hanging bolts.

s

s

s

s

s

To ensure that drain is discharged, be sure to hang the unit at level using

a level.

 Caution:

Be sure to install the unit body at level.

[Fig. 5.2.1] (P.2)

B

Indoor unit’s bottom surface

(Surface to which a decorative panel is attached)

6. Refrigerant pipe and drain pipe specifications

To avoid dew drops, provide sufficient antisweating and insulating work to the re-

frigerant and drain pipes.

When using commercially available refrigerant pipes, be sure to wind commer-

cially available insulating material (with a heat-resisting temperature of more than

100 °C and thickness given below) onto both liquid and gas pipes.

Be  also  sure  to  wind  commercially  available  insulating  material  (with  a  form

polyethylene’s specific gravity of 0.03 and thickness given below) onto all pipes

which pass through rooms.

1

Select the thickness of insulating material by pipe size.

6.2. Refrigerant pipe , drain pipe and filling

port

[Fig. 6.2.1] (P.3)

A

Refrigerant pipe (liquid pipe): HP

B

Drain pipe

C

Hanging bolt pitch

D

Refrigerant pipe (gas pipe): LP

E

Filling port

5.1. Hanging the unit body

s

s

s

s

s

Bring the indoor unit to an installation site as it is packed.

s

s

s

s

s

To hang the indoor unit, use a lifting machine to lift and pass through the

hanging bolts.

s

s

s

s

s

When lifting with a lifting machine, in order to protect against damage,

reverse the unit body as is packed with the packing cap and lift it.
[Fig. 5.1.1] (P.2)

A

Drain pipe side

B

Unit body

C

Packing cap

D

Lifting machine

Pipe size

Insulating material’s thickness

6.4 mm to 25.4 mm

More than 10 mm

28.6 mm to 38.1 mm

More than 15 mm

2

If the unit is used on the highest story of a building and under conditions of

high temperature and humidity, it is necessary to use pipe size and insulating

material’s thickness more than those given in the table above.

3

If there are customer’s specifications, simply follow them.

Refrigerant  pipe

(Flare connection)

6.1. Refrigerant pipe and drain pipe specifi-

cations

6.3. Request for refrigerant piping connection

Description of parts to be used

No.

1

2

3

Work procedures

Mount the provided pipe insula-

tion (1) on the liquid pipe of the

refrigerant piping, and then mount

the flare insulation (2) on the gas

pipe.

Fixing of insulated pipe

Fixing of flare insulation

Reference drawing

[Fig. 6.3.1] (P.3)

[Fig. 6.3.2] (P.3)

[Fig. 6.3.2] (P.3)

[Fig. 6.3.3] (P.3)

(Note *3)

[Fig. 6.3.3] (P.3)

(Note *4)

Detail of work

“INNER” and “OUTER” are marked on the in-

side of the flare insulation. Mount the portion

marked “INNER” near the unit body and the

portion marked “OUTER” on the field piping

side.

• Fasten the insulated pipe with the insula-

tion tape.

• Firmly secure the insulation with the pro-

vided tie band (4) at the position indicated

on the drawing.

• Fasten the flare insulation with the provided

tape (3).

• Fasten with the provided tie band (4) at the

position indicated on the drawing.

Item to be observed

• Using the flare insulation of a different model may

result in condensation forming. Check the model

name on the insulation and be sure to use the cor-

rect one.

• To prevent a gap from forming near the unit’s side

plate, be sure that the flare insulation firmly con-

tacts the unit’s side plate before mounting.

• Incorrectly  mounting  the “INNER”  and “OUTER”

sides of the insulation may result in condensation

forming.

Seal the slit securely so that there are no openings.

Be sure to mount the insulation so that the slit is on

the top.

Seal the slit securely so that there are no openings.

Be sure to mount the insulation so that the slit is on

the top.

Item

Model 20·25·32·40 50 · 63 · 80 100 · 125

Liquid pipe

ø6.35

ø9.52

Gas pipe

ø12.7

ø15.88

ø19.05

Drain pipe

VP-25

Содержание PLFY-P-VLMD-A

Страница 1: ...leggere attentamente questo manuale di installazione prima di installare il condizionatore d aria INSTALLATIEHANDLEIDING Voor een veilig en juist gebruik moet u deze installatiehandleiding grondig doorlezen voordat u de airconditioner installeert MANUAL DE INSTALAÇÃO Para segurança e utilização correctas leia atentamente este manual de instalação antes de instalar a unidade de ar condicionado E XE...

Страница 2: ...2 9 mounting hole G 4 ø2 9 mounting hole 3 2 Fig 3 2 1 H D 630 E 550 40 40 D A E B 102 102 A A B B C F B A D 50 10 G C A Nut B Washer supplied with the unit body C Hanging bolt ø10 M10 screw D Ceiling hole dimensions E Hanging bolt pitch F Hanging bolt G Finished ceiling surface H Hanging bracket A D C B A Drain pipe side B Unit body C Packing cap D Lifting machine B A B Indoor unit s bottom surfa...

Страница 3: ...INNER F Unit body G Provided flare insulation 2 A Tape 3 B Fasten with tape C Provided tie band 4 figure showing the flare insulation D I C H G K I J 3 C 30 cm G Drain hose Accessory s s s s s Be sure to use the supplied drain hose Accessory H Less than 300 mm I Hard vinyl chloride 90 elbow field supply J Hard vinyl chloride VP 25 field supply K Tie band small Accessory D D D E F 2 D Indoor unit E...

Страница 4: ...ON SW14 N0 N0 W254613G03 FP AD P JP2 JP3 JP4 CN82 8 1 6 1 10 1 240V 220V SW5 JP1 SWC SWA 1 3 2 0 SW12 10 0 SW11 1 0 Address board Fig 8 2 5 G I J J J K K K F J J L K H 1 3 L1 L2 L4 l L3 2 G Outdoor unit H Earth I BC controller J Indoor unit K Remote controller L Non polarized 2 wire Fig 8 2 1 A A C TB5 TB5 S M1M2 S M1M2 C B TB3 M1M2 A A C TB5 TB15 TB5 TB15 S M1M2 S M1M2 B TB3 M1M2 2 1 C 2 1 Fig 8 ...

Страница 5: ...y limit even if the refrigerant should leak Consult the dealer regarding the appropriate measures to prevent the safety limit from being exceeded Should the refrigerant leak and cause the safety limit to be exceeded hazards due to lack of oxygen in the room could result When moving and reinstalling the air conditioner consult the dealer or an authorized technician If the air conditioner is install...

Страница 6: ...eteriorate Do not use the following tools that are used with conventional refriger ants Gauge manifold charge hose gas leak detector reverse flow check valve refrigerant charge base vacuum gauge refrigerant recovery equipment If the conventional refrigerant and refrigerator oil are mixed in the R407C the refrigerant may deteriorated If water is mixed in the R407C the refrigerator oil may deteriora...

Страница 7: ...the back surface of each split flow duct end connection is insulating material Use a cutter knife to cut the insulating material along the end connection To adjust the fresh air intake capacity cut the two places as shown in the figure at right and rotate the intake 3 3 Combining indoor units with outdoor units For combining indoor units with outdoor units refer to the outdoor unit installation ma...

Страница 8: ... Packing cap D Lifting machine Pipe size Insulating material s thickness 6 4 mm to 25 4 mm More than 10 mm 28 6 mm to 38 1 mm More than 15 mm 2 If the unit is used on the highest story of a building and under conditions of high temperature and humidity it is necessary to use pipe size and insulating material s thickness more than those given in the table above 3 If there are customer s specificati...

Страница 9: ...e the new refrigerant to deteriorate Store the piping to be used during installation indoors and keep both ends of the piping sealed until just before brazing If dust dirt or water gets into the refrigerant cycle the oil will deteriorate and the compressor may fail Use Suniso 4GS or 3GS small amount refrigerator oil to coat the flare and flange connection part For models using R22 Use ester oil et...

Страница 10: ...cc D Water E Filling port Building clinic hospital or communications station without noise supposedly generated from inverter equipment private power gen erator high frequency medical equipment radio used communications equipment and so on Residence or independent store without noise Facility example for noise judgment All facilities VCTF VCTFK CVV CVS VVR VVF VCT or shielding wire CVVS or CPEVS S...

Страница 11: ...ol board to ON The setting of SW1 7 and SW1 8 as necessary also makes it possible to adjust the air flow at a time when the heating thermometer is OFF 8 2 Connecting remote controller indoor and outdoor transmission cables Remote contoroller is optionally available Connect indoor unit TB5 and outdoor unit TB3 Non polarized 2 wire The S on indoor unit TB5 is a shielding wire connection For specific...

Страница 12: ...t the contact address telephone number on this manual before handing it to the customer The product at hand is based on the following EU regulations Low Voltage Directive 73 23 EEC Electromagnetic Compatibility Directive 89 336 EEC This product is designed and intended for use in the residential commer cial and light industrial environment ...

Отзывы: