Range of application
The range of working temperatures for both the indoor and outdoor units of the series Y, R2, Multi-S is as below.
Caution:
The use of your air conditioner outside the range of working temperature and humidity can result in serious failure.
Mode
Indoor unit
Outdoor unit
PUHY
PURY
PUMY
Cooling
15 °C - 24 °C WB
–5 °C - 43 °C DB
–5 °C - 43 °C DB
–5 °C - 46 °C DB
Heating
15 °C - 27 °C DB
–15 °C - 15.5 °C WB
–12 °C - 15 °C WB
–12 °C - 15.5 °C WB
Note: As an applicable humidity standard for both indoors and outdoors, we recommend use within a range of 30 - 80% relative humidity.
Warning:
If the air conditioner operates but does not cool or heat (depending on model) the room, consult your dealer since there may be a refrigerant
leak. Be sure to ask the service representative whether there is refrigerant leakage or not when repairs are carried out.
The refrigerant charged in the air conditioner is safe. Refrigerant normally does not leak, however, if refrigerant gas leaks indoors and
comes into contact with the fi re of a fan heater, space heater, stove, etc., harmful substances will be generated.
10. Trouble Shooting
Having trouble?
Here is the solution. (Unit is operating normally.)
Noise is louder than specifi cations.
The indoor operation sound level is affected by the acoustics of the
particular room as shown in the following table and will be higher than
the noise specifi cation, which was measured in an echo-free room.
High sound
absorbing rooms
Normal rooms
Low sound
absorbing rooms
Location
examples
Broadcasting
studio, music
room, etc.
Reception room,
hotel lobby, etc.
Offi ce, hotel
room
Noise levels
3 to 7 dB
6 to 10 dB
9 to 13 dB
Nothing appears in the wireless remote controller display, the display
is faint, or signals are not received by the indoor unit unless the remote
controller is close.
The batteries are low.
Replace the batteries and press the Reset button.
If nothing appears even after the batteries are replaced, make sure
that the batteries are installed in the correct directions (+, –).
The operation lamp near the receiver for the wireless remote controller
on the indoor unit is fl ashing.
The self diagnosis function has operated to protect the air conditioner.
Do not attempt to repair this equipment by yourself.
Turn off the power switch immediately and consult your dealer. Be
sure to provide the dealer with the model name.
Warm air blows from the indoor unit intermittently when heating mode is
off or during fan mode.
When another indoor unit is operating in heating mode, the control
valve opens and closes occasionally to maintain stability in the air
conditioning system. This operation will stop after a while.
* If this will cause an undesirable rise in the room temperature in
small rooms, etc., stop the operation of the indoor unit temporarily.
11. Specifi cations
PLFY-P.VBM-E Series
Model
P32
P40
P50
P63
P80
P100
P125
Power source(Voltage <V>/Frequency<Hz>)
~N/ 220-230-240/50, 220/60
Capacity(Cooling/Heating)
<kW>
3.6/4.0
4.5/5.0
5.6/6.3
7.1/8.0
9.0/10.0
11.2/12.5
14.0/16.0
Dimension(Height)
<mm>
258(35)
298(35)
Dimension(Width)
<mm>
840(950)
Dimension(Depth)
<mm>
840(950)
Net weight
<kg>
22(6)
23(6)
27(6)
Fan airfl ow rate(Low-Middle2-Middle1-High)
<m
3
/min>
11-12-13-14
12-13-14-16
14-15-16-18
16-18-20-22
21-24-27-29
22-25-28-30
Noise level(Low -Middle2-Middle1-High)
<dB>
27-28-29-31
27-28-30-31
28-29-30-32
30-32-35-37
34-37-39-41
35-38-41-43
*1 Cooling/Heating capacity indicates the maximum value at operation under the following condition.
Cooling: Indoor 27 °C DB/19 °C WB, Outdoor 35 °C DB
Heating: Indoor 20 °C DB, Outdoor 7 °C DB/6 °C WB
*2 This fi gure ( ) indicates panel’s.