27
26
27
OCH715
<How to operate>
1
Press POWER ON/OFF button.
2
Press the operation MODE button to display AUTO.
3
Press the TEMP. button to set the set temperature.
NOTE
: The set temperature changes 1°F when the or
button is pressed one time. Automatic 67 to 83°F
<How to operate>
1
Press ON/OFF button.
2
Press [F1] button to display AUTO.
3
Press [F2] [F3] button to set the set temperature.
NOTE
: The settable temperature range varies with the model
of outdoor units and remote controller.
8-5. AUTO OPERATION [AUTOMATIC COOL/HEAT CHANGE OVER OPERATION]
Control Mode
Control Details
Remarks
1. Initial value of
operation mode
HEAT mode for room temperature < Set temperature
COOL mode for room temperature
]
Set temperature
2. Mode change
(1) HEAT mode → COOL mode
Room temperature
]
Set tempe 3°F or 3 minutes have passed.
(2) COOL mode → HEAT mode
Room temperature
[
Set temperature − 3°F or 3 minutes have passed.
3. COOL mode
Operates as it would in COOL operation.
4. HEAT mode
Operates as it would in HEAT operation.
8-6. WHEN UNIT IS STOPPED CONTROL MODE
Control Mode
Control Details
Remarks
1. Drain pump
1-1. Drain pump control
The drain pump turns ON for the specified amount of time when any of the following
conditions has been satisfied:
1
ON for 3 minutes after the operation mode is switched from COOL or DRY to another
operation mode (FAN).
2
ON for 6 minutes after the float switch is submerged in the water when the float switch
control judges the sensor is in the water.
1-2. Float switch control
• Float switch control judges whether the sensor is in the air or in the water by
turning the float switch ON/OFF.
In the water : Detected that the float switch is ON for 15 seconds.
In the air : Detected that the float switch is OFF for 15 seconds.
• Operates as it would
in COOL operation.
MENU
ON
OFF
RETURN SELECT
HOLD
.