31
OCH715
9-2. FUNCTION OF DIP SWITCH
PKFY-P04NLMU-E.TH
PKFY-P06NLMU-E.TH
PKFY-P08NLMU-E.TH
PKFY-P12NLMU-E.TH
PKFY-P15NLMU-E.TH
PKFY-P18NLMU-E.TH
The black square ( ) indicates a switch position.
Switch
Pole
Function
Operation by switch
Effective
timing
Remarks
ON
OFF
<Table A>
SW1-7
SW1-8
OFF
OFF
Extra low
ON
OFF
Low
OFF
ON
Setting air flow
ON
ON
stop
Continue to the next page
SW1
Mode
Selection
1
Thermistor
<Intake temperature
detection> position
Built-in remote
controller
Indoor unit
Under
suspension
Address board
ON
OFF
ON
OFF
1 2 3 4 5 6 7 8 9 10
<Initial setting>
*
1
The model is not capable of fresh air intake.
*
2
Refer to <Table A> below.
2
Filter clogging
Provided
Not provided
3
Filter sign indication 2,500 hr
100 hr
4
Air intake*
1
Not effective
Not effective
5
Remote indication
switching
Thermo-ON signal
indication
Fan output indication
6
Humidifier control
Fan operation at Heating
mode
Thermo-ON operation at
heating mode
7
Air flow set in case of
heat thermo-OFF
Low*
2
Extra low*
2
8
Setting air flow*
1
Depends on SW1-7
9
Auto restart function Effective
Not effective
10
Power ON/OFF
Effective
Not effective
SW2
Capacity
code
setting
1–4
Before
power
supply
ON
Indoor controller board
<Initial setting>
Set for each capacity.
SW3
Function
Selection
1
Heat pump/Cool only
Cooling only
Heat pump
Under
suspension
Indoor controller board
<Initial setting>
2
—
—
—
3
—
—
—
4
—
—
—
5
—
—
—
6
—
—
—
7
Changing the opening of
linear expansion valve Effective
Not effective
8
Heating 4 degree up Not effective
Effective
9
—
—
—
10
—
—
—
ON
OFF
1 2 3 4 5 6 7 8 9 0