10
6.5. Setting addresses (Fig. 6-4)
(Be sure to operate with the main power turned OFF.)
• There are two types of rotary switch setting available: setting addresses 1 to 9
and over 10, and setting branch numbers.
1
How to set addresses
Example: If Address is “3”, remain SW12 (for over 10) at “0”, and match SW11
(for 1 to 9) with “3”.
2
How to set branch numbers SW14 (Series R2 only)
Match the indoor unit’s refrigerant pipe with the BC controller’s end connection
number.
Remain other than series R2 at “0”.
• The rotary switches are all set to “0” when shipped from the factory. These
switches can be used to set unit addresses and branch numbers at will.
• The determination of indoor unit addresses varies with the system at site. Set
them referring to the Data Book.
6.6. Sensing room temperature with the built-in
sensor in a remote controller
If you want to sense room temperature with the built-in sensor in a remote
controller, set SW1-1 on the control board to “ON”. The setting of SW1-7 and SW1-
8 as necessary also makes it possible to adjust the air flow at a time when the
heating thermometer is OFF.
7. Test run (Fig. 7-1)
1
Turn on the power at least 12 hours before the test run.
2
Press the [TEST] button twice.
“TEST RUN” liquid crystal display
3
Press the [Mode selection] button.
Make sure that wind is blown out.
4
Press the [Mode selection] button and switch to the cooling (or heating) mode.
Make sure that cold (or warm) wind is blown out.
5
Press the [Fan speed] button.
Make sure that the wind speed is switched.
6
Check operation of the outdoor unit fan.
7
Release test run by pressing the [ON/OFF] button.
Stop
8
Register a telephone number.
The telephone number of the repair shop, sales office, etc., to contact if an
error occurs can be registered in the remote controller. The telephone number
will be displayed when an error occurs. For registration procedures, refer to the
operation manual for the indoor unit.
6. Electrical work
Fig. 6-4
SW14
0
SW11
SW12
1 2 3 4 5 6 7 8 9 10
ON
OFF
SW1
SWA
CN82
CN43
3
2
1
F
E
D
C
B
A 9 8 7
6
5
4
3
2
1
5
0
4
9
3
8
2
7
1
6
5
0
4
9
3
8
2
7
1
6
ಽጘญ0Qࡍࠕ0Q
㧔$4#0%*0Q
㧔U&+)+6
㧔VJU&+)+6
A
Fig. 7-1
°C
°C
SIMPLE
PAR-21MAA
ON/OFF
FILTER
CHECK
OPERATION
CLEAR
TEST
TEMP.
MENU
BACK
DAY
MONITOR/SET
CLOCK
ON/OFF
TEST RUN
COOL, HEAT
A
F
C
E
D
B
M
I
HG
A
ON/OFF button
B
Test run display
C
Indoor temperature liquid
line temperature display
D
ON/OFF lamp
E
Power display
F
Error code display
Test run remaining time
display
G
Set temperature button
H
Mode selection button
I
Fan speed button
M
TEST button