21
NOTE:
1. Rating conditions (ISO T1)
Cooling Indoor : D.B. 27
(80°F) W.B. 19
(66°F)
Outdoor : D.B. 35
(95°F) W.B. 24
(75°F)
Heating Indoor : D.B. 20
(68°F)
Outdoor : D.B. 7
(45°F)
W.B. 6
(43°F)
Refrigerant piping length (one way) : 5m (16ft.)
2. Guaranteed operating range
Indoor
Outdoor
Cooling
Upper limit D.B. 35°C, W.B. 22.5°C D.B. 46°C
Lower limit D.B. 19°C, W.B. 15°C
D.B. -5°C
+
Heating
Upper limit D.B. 28°C
D.B. 21°C, W.B. 15°C
Lower limit D.B. 17°C
D.B. -20°C, W.B. -20°C
4. Above data are based on the indicated voltage.
+
If optional air protect guide installed. D.B.-15
Indoor unit
Single phase 230V 50Hz
Single phase 230V 50Hz
Outdoor unit
3. Guaranteed voltage
198~264V, 50Hz
Model name
Indoor unit
PSA-RP71GA
Outdoor unit
PUHZ-RP71VHA4
Cooling
Capacity
Btu/h
24,200
kW
7.1(3.3-8.1)
Total input
kW
2.20
EER
3.23
Energy label class
A
SHF
0.73
Heating
Capacity
Btu/h
25,900
kW
7.6(3.5-10.2)
Total input
kW
2.23
COP
3.41
Energy label class
B
Booster heater
kW
-
Power supply
Phase
:
1
Cycle
Hz
50
Voltage
V
230
Breaker size
A
25
Indoor unit
Air flow
CMM
15-18
(Low-High)
CFM
530-635
External pressure
Pa
0
Sound level
dB(A)
40-45
(Low-High)
External finish
White Munsell 0.70Y 8.59/0.97
Dimension
W : mm
600
D : mm
270
H : mm
1,900
W : inch
23-5/8
D : inch
10-5/8
H : inch
74-13/16
Weight
kg
43
lbs
98
Field drain pipe I.D.
mm
20
inch
13/16
Outdoor unit
Air flow
CMM
60
CFM
2,120
Sound level at cooling
dB(A)
47
Sound level at heating
dB(A)
48
External finish
Ivory Munsell 3Y 7.8/1.1
Dimension
W : mm
950
D : mm
330+30
H : mm
943
W : inch
37-3/8
D : inch
13 + 1-3/16
H : inch
37-1/8
Weight
kg
67
lbs
148
Refrigerant pipe size
Gas side O.D.
mm
15.88
inch
5/8
Liquid side O.D.
mm
9.52
inch
3/8
Refrigerant pipe length
Height difference
m
Max. 30
Length
m
Max. 50
2-5. FLOOR STANDING TYPE