23
Pb
Error Code
Abnormal point and detection method
Cause
Countermeasure
Inverter-related problem is detected.
1) Power supply environment
3) Wiring fault
2) Static pressure setting error
4) Air passage blockage
5) Parts problem
9) Indoor controller board failure
6) INV board failure
10) Other cause
7) Sensor fault
1
Check the wiring between TB2 and NF
board, NF board and ACL, NF board and
inrush current resistor, NF board and
DB01, NF board and INV board, NF board
and indoor controller board.
2
Check the inrush current resistance.
Measure the interphase resistance of the
resistor (R). 22
Ω
±
10%
3
Check ACL for broken wires.
Check that the resistance between pins 1
and 3 (housing side) of the CNACL
connector is not infinite (
∞
).
4
Check the diode bridge (DB01) for
problem.
Refer to section 9.8.(5) "Troubleshooting
the diode bridge". (page 33)
5
If no problems were found with items
1
through
4
above, replace the NF board.
1
Replace the NF board.
2
If the problem persists after taking step
1
above, replace the INV board.
3
If the problem persists after taking step
2
above, replace the motor.
4
If the problem persists after taking step
3
above, replace the indoor controller board.
5
If the problem persists after taking step
4
above, replace the power supply board.
1
ACCT sensor
Refer to 9-8.(4).
2
THHS sensor
Refer to 9-8.(4).
8) Fan motor error
Find out if there was a (momentary) power
failure. Check whether the power voltage is 198V
or above across all phases.
Check the wiring for proper connection.
(Check all the wiring between the terminal block
and motor.)
Check that the heat sink cooling air passage is
not blocked.
Check that the static pressure setting and the
design static pressure are correct.
Check the voltage at CNVDC (between pins 1
and 3(+)) on the INV board while the inverter is
stopped and if it is less than 220V, check the
following items.
Confirm that DC12V is applied to the connector
CNXB2 (between pins 4 and 5 (+)) on the Indoor
controller board while the inverter is operating.
If not, replace the Indoor controller board.
Check the items listed in section (2)-[2].
Refer to 9-8.(2)-[2].
Check the items listed in section (2)-[4].
Refer to 9-8.(2)-[4].
If no problems were found with items 1) through 9),
HWE17030.qxd 17.11.9 16:28 Page 23
Содержание PEA-RP200WKA
Страница 1: ...HWE17030 qxd 17 11 9 16 28 Page 1 ...
Страница 2: ...HWE17030 qxd 17 11 9 16 28 Page 2 ...
Страница 3: ...CONTENTS HWE17030 qxd 17 11 9 16 28 Page 3 ...
Страница 47: ...45 OPTIONAL PARTS 12 Drain pump PAC KE05DM F HWE17030 qxd 17 11 9 16 28 Page 45 ...
Страница 48: ...HWE17030 qxd 17 11 9 16 28 Page 46 ...