20
Error Code
Abnormal point and detection method
Cause
Countermeasure
P6
Freezing/overheating protection is
working
1
Freezing protection (Cooling mode)
The unit is in six-minute resume prevention
mode if pipe <liquid or condenser/evap-
orator> temperature stays under
-15
:
for three minutes after the com-
pressor started. Abnormal if it stays
under -15
:
for three minutes again
within 16 minutes after six-minute
resume prevention mode.
2
Overheating protection (Heating mode)
The units is in six-minute resume
prevention mode if pipe <Liquid or con-
denser/evaporator> temperature is
detected as over 70
:
after the com-
pressor started. Abnormal if the temper-
ature of over 70
:
is detected again
within 10 minutes after six-minute
resume prevention mode.
P8
1
Slight temperature difference
between indoor room
temperature and pipe <liquid
or condenser/evaporator>
temperature thermistor
• Shortage of refrigerant
• Disconnected holder of pipe
<liquid or condenser/
evaporator> thermistor
• Defective refrigerant circuit
2
Converse connection of
extension pipe (on plural units
connection)
3
Converse wiring of indoor/
outdoor unit connecting wire
(on plural units connection)
4
Defective detection of indoor
room temperature and pipe
<condenser/evaporator>
temperature thermistor
5
Stop valve is not opened
completely.
(Cooling or drying mode)
1
Clogged filter (reduced airflow)
2
Short cycle of air path
3
Low-load (low temperature)
operation beyond the tolerance
range
4
Defective indoor fan motor
• Fan motor is defective.
• Indoor controller board is
defective.
5
Defective outdoor fan control
6
Overcharge of refrigerant
7
Defective refrigerant circuit
(clogs)
(Heating mode)
1
Clogged filter (reduced airflow)
2
Short cycle of air path
3
Over-load (high temperature)
operation beyond the tolerance
range
4
Defective indoor fan motor
• Fan motor is defective.
• Indoor controller board is
defective.
5
Defective outdoor fan control
6
Overcharge of refrigerant
7
Defective refrigerant circuit
(clogs)
8
Bypass circuit of outdoor unit
is defective.
(Cooling or drying mode)
1
Check clogging of the filter.
2
Remove shields.
4
Refer to 9-8. DC Fan motor (FAN MOTOR/
INDOOR CONTROLLER BOARD)
5
Check outdoor fan motor.
67
Check operating condition of refrigerant
circuit.
(Heating mode)
1
Check clogs of the filter.
2
Remove shields.
4
Refer to 9-8. DC Fan motor (FAN MOTOR/
INDOOR CONTROLLER BOARD)
5
Check outdoor fan motor.
6
~
8
Check operating condition of refrigerant
circuit.
Pipe temperature
<Cooling mode>
Detected as abnormal when the pipe tem-
perature is not in the cooling range 3 min-
utes after compressor start and 6 minutes
after the liquid or condenser/evaporator pipe
is out of cooling range.
Note 1) It takes at least 9 minutes. to
detect.
Note 2) Abnormality P8 is not detected in
drying mode.
Cooling range : -3 deg
]
(TH-TH1)
TH: Lower temperature between: liquid
pipe temperature (TH2) and con-
denser/evaporator temperature (TH5)
TH1: Intake temperature
<Heating mode>
When 10 seconds have passed after the
compressor starts operation and the hot
adjustment mode has finished, the unit is
detected as abnormal when
condenser/evaporator pipe temperature is
not in heating range within 20 minutes.
Note 3) It takes at least 27 minutes to
detect abnormality.
Note 4) It excludes the period of defrosting
(Detection restarts when defrost-
ing mode is over)
Heating range : 3 deg
[
(TH5-TH1)
1
~
4
Check pipe <liquid or condenser/
evaporator> temperature with room
temperature display on remote
controller and outdoor controller circuit
board.
Pipe <liquid or condenser/evaporator>
temperature display is indicated by
setting SW2 of outdoor controller circuit
board.
23
Check converse connection of extension
pipe or converse wiring of indoor/outdoor
unit connecting wire.
Conduct temperature check with outdoor
controller circuit board after connecting
‘A-Control Service Tool(PAC-SK52ST)’.
(
)
HWE17030.qxd 17.11.9 16:28 Page 20
Содержание PEA-RP200WKA
Страница 1: ...HWE17030 qxd 17 11 9 16 28 Page 1 ...
Страница 2: ...HWE17030 qxd 17 11 9 16 28 Page 2 ...
Страница 3: ...CONTENTS HWE17030 qxd 17 11 9 16 28 Page 3 ...
Страница 47: ...45 OPTIONAL PARTS 12 Drain pump PAC KE05DM F HWE17030 qxd 17 11 9 16 28 Page 45 ...
Страница 48: ...HWE17030 qxd 17 11 9 16 28 Page 46 ...