9. Multiple outdoor units control
Signal inputs
Name Terminal block Connector Item
OFF (Open)
OFF (Short)
RC
TBI.2 1-2
CN22
Communication cable between indoor units
—
—
IN2
TBI.1 11-12
—
Flow switch input
Refer to SW2-2 in <9.6 Dip Switch Functions>.
Wiring specification and local supply parts
Item
Name
Model and specifications
Signal input function
Signal input wire
Use sheathed vinyl coated cord or cable.
Max. 10 m
Wire type: CV, CVS or equivalent
Wire size: Stranded wire 0.5 mm² to 1.25 mm²
Solid wire: ø0.65 mm to ø1.2 mm
Switch
Non-voltage “a” contact signals
Remote switch: minimum applicable load 12V DC, 1mA
Thermistor inputs
Name Terminal block Connector Item
Optional part model
TH2
—
CN21
Thermistor (Ref. liquid temp.)
—
THW1
—
CNW12 1-2 Thermistor (Flow water temp.)
—
THW2
—
CNW12 3-4 Thermistor (Return water temp.)
—
Note:
Do not splice the wiring to extend or shorten it, or this could affect correct monitoring of each temperature.
If the wiring is too long, bundle it with a strap to adjust the length.
Outputs
Name Terminal block Connector Item
OFF
ON
Signal/Max. current
OUT1
TBO.1 1-2
CNP1
Water circulation pump 1 output
OFF
ON
230V AC 1.0 A Max.
OUT4
TBO.2 4-6
CNV1
3-way valve (2-way valve 1) output
Heating
DHW
230V AC 0.1 A Max.
OUT13 TBO.4 1-2
—
2-way valve 2 output
DHW
Heating
230V AC 0.1 A Max.
<Fig. 9.7.7>
1
3
CN3C
(BLU)
1
3
CNPWM
(WHT)
LED1
LED2
LED3
LED4
CN108
5
1
5
1
5
1
CNRF
(WHT)
CN105
(RED)
TBO.1
TBO.2
TBO.3
TBO.4
CNP1
(WHT)
CNP4
(RED)
CNV1
(WHT)
CN22
(BLU)
CNIT
(BLU)
CN01
(WHT)
F2
F1
6.3A 250V
10A 250V
SW1
SW2
SW3
SW4
SW5
1
8
1
8
1
1
5
1
3
1
3
8
1
1
2
3
4
5
6
1
2
3
4
5
6
1
2
3
4
5
6
7
8
1
2
3
4
5
6
8
1
6
1
2
4
6
CNBH
(WHT)
CNBC
(GRY)
1
1
3
1
2
1
2
1
2
CNBHT
(BLK)
1
3
7
1
3
CNIH
(ORN)
1
4
1
3
CNW5
(WHT)
CN21
(YLW)
CNW12
(RED)
CN20
(RED)
TBI.2
12
6
10
14
8
13
7
11
9
4
5
3
2
1
TBI.3
2 4 6 8 10 12 14
1 3 5 7 9 11 13
1
4
CN1A
(WHT)
2 4 6 8 10 12 14
1 3 5 7 9 11 13
TBI.1
L
N
OUT13
1 2 3 4 5 6
TBO.1
1 2 3 4 5 6
TBO.2
TBO.3 1 2 3 4 5 6 7 8
1 2 3 4
6
5
TBO.4
L
N
OUT1
N
L
OUT4
FTC
Hydrobox
<Fig. 9.7.6>
When the wires are wired to adjacent terminals use ring terminals and insu-
late the wires.
Note:
1. Do not connect multiple water circulation pumps directly to each output (OUT1). In such
a case, connect them via (a) relay(s).
2. Do not connect water circulation pumps to both TBO.1 1-2 and CNP1 at the same time.
3. Stranded wire should be processed with insulation-covered bar terminal (DIN46228-4
standard compatible type).
Item
Name
Model and specifications
External output function
Outputs wire
Use sheathed vinyl coated cord or cable.
Max. 30 m
Wire type: CV, CVS or equivalent
Wire size: Stranded wire 0.25 mm² to 1.5 mm²
Solid wire: 0.25 mm² to 1.5 mm²
Wiring specification and local supply parts
<Fig. 9.7.8>
Connect them using either way as shown above.
How to use TBO.1 to 4
Tool
Tool
Conductor
Conductor
Outline view
Top view