8. Electrical work
8.3. Switch setting
SW4
SW5
SW11
SW12
Address setting
ONES DIGIT
Address setting
TENS DIGIT
Model selection
Indoor unit
setting
SW1
Indoor unit
connections
Dip switch setting (Effective only before turning on the power)
1 2 3 4 5 6
ON
OFF
SW1
1 2 3 4 5 6
ON
OFF
SW4
7 8 9 10
When connecting the Cylinder or the Hydro box unit to the unit in the house, connect
the air to air system indoor unit connected in the bedrooms to A to C ports and make
the following switch settings below.
Also, after referring to the outdoor unit installation manual, add refrigerant.
Port A to C are available for setting for up to a maximum of 3 rooms.
SW5
Port setting
4
5
6
Off
Off
Off
Not speci
fi
ed
On
Off
Off
Port A
Off
On
Off
Port B
On
On
Off
Port A+B
Off
Off
On
Port C
On
Off
On
Port A+C
Off
On
On
Port B+C
On
On
On
Port A+B+C
Address switch (Effective only before turning on the power)
Actual indoor unit address setting varies in different systems. Refer to the installation manual for the outdoor unit for details on how to make the address setting.
Each address is set with a combination of the settings for the tens digit and ones digit.
(Example)
• When setting the address to “3”, set the ones digit to 3, and the tens digit to 0.
• When setting the address to “25”, set the ones digit to 5, and the tens digit to 2.
(Example)
•
When setting the address of the branch BOX to “3”, an address is assigned to each indoor unit starting with Unit A as shown below no matter if each indoor unit is con-
nected. (SW1-1~5 ON)
Indoor Unit A
Address 3
Indoor Unit B
Address 4
Indoor Unit C
Address 5
Indoor Unit D
Address 6
Indoor Unit E
Address 7
•
When the address is set to “25” and also 3 indoor units (Unit A, Unit C, and Unit E) are connected. (SW1-1, 1-3, 1-5 ON)
Indoor Unit A
Address 25
Indoor Unit C
Address 26
Indoor Unit E
Address 27
Ports available
for setting
Port A
Port B
Port C
Port D
Port E
Ports available
for setting
Port A
Port B
Port C
Port D
Port E
Switch
OFF
ON
SW4-5
Cooling & Heating system
Cooling only system
(Example)
When the indoor unit is
cooling only system, turn
SW4-5 to on.
•
(Example)
When the indoor units are
connected to Indoor unit
A and C, turn SW1-1 and
SW1-3 to on.
•
Switch
OFF
ON
Indoor Unit A
SW1-1
Not connected
Connected
Indoor Unit B
SW1-2
Not connected
Connected
Indoor Unit C
SW1-3
Not connected
Connected
Indoor Unit D
SW1-4
Not connected
Connected
Indoor Unit E
SW1-5
Not connected
Connected
Not used
SW1-6