191
CHAPTER 8 FUNCTIONS
8
8.
3 T
e
mperat
ure Cont
rol
M
ode
(8) Conditions where self-tuning does not complete due to errors
The following operations and conditions cause an abend of self-tuning. At the abend, CH
Self-tuning error (b10
of RWr14 to RWr17) turns 1 (ON).
• When 6000s (1 hour and 40 minutes) or longer passes after the start of ST
• When the change rate of the temperature process value (PV) during ST is less than 1.125 (
/minute)
• When CH
Temperature process value (PV) (RWr8 to RWrB) is outside the temperature measurement
range (
• When the manipulated value (MV) does not reach the upper limit output limiter value or lower limit output
limiter value before the measurement is completed and necessary measurement data is not obtained
• When self-tuning is started with the starting ST and the temperature process value (PV) that is supposed to
rise drops by 1
(
) or more
• When self-tuning is started with the starting ST and the temperature process value (PV) that is supposed to
drop rises by 1
(
) or more
• When the setting for the remote buffer memory areas in the following table is changed during self-tuning
*1
Changing the setting causes an abend only during the activation of ST by start ST.
Remote buffer memory area name
Remote buffer memory address
Reference
CH1
CH2
CH3
CH4
CH
Set value (SV) setting
101H
131H
161H
191H
CH
Proportional band (P) setting
102H
132H
162H
192H
CH
Integral time (I) setting
103H
133H
163H
193H
CH
Derivative time (D) setting
104H
134H
164H
194H
CH
Upper limit output limiter
105H
135H
165H
195H
CH
Lower limit output limiter
106H
136H
166H
196H
CH
Output variation limiter setting
107H
137H
167H
197H
CH
Setting change rate limiter
108H
138H
168H
198H
CH
Control output cycle setting
10CH
13CH
16CH
19CH
CH
Primary delay digital filter setting
10DH
13DH
16DH
19DH
CH
AUTO/MAN mode shift
113H
143H
173H
1A3H
CH
Forward/reverse action setting
115H
145H
175H
1A5H
CH
Sensor correction value setting
280H
281H
282H
283H
Содержание NZ2GF2B-60TCRT4
Страница 1: ...CC Link IE Field Network Temperature Control Module User s Manual NZ2GF2B 60TCTT4 NZ2GF2B 60TCRT4 ...
Страница 2: ......
Страница 86: ...84 Memo ...
Страница 233: ...231 CHAPTER 8 FUNCTIONS 8 8 4 CC Link IE Field Network Function 3 Click the OK button on the following window ...
Страница 268: ...266 Memo ...
Страница 377: ...375 APPENDICES A Appendix 6 External Dimensions Memo ...
Страница 383: ...I 4 4 7 8 381 Memo ...
Страница 387: ......