9-7. TEST POINT DIAGRAM
9-7-1. Outdoor controller circuit board
MXZ-8A140VA MXZ-8A140VA
1
MXZ-8A140VA
2
Communication
power supply
ZD71 Voltage
developed across:
16-30V DC
–
+
CNS
(Branch box/outdoor unit connecting wire)
CNAC
2
to
4
: Power supply for
outdoor controller
circuit board
(220V-240V AC)
1
to
3
: Power supply for
indoor and branch box /
outdoor unit connection
wire (220V-240V AC)
CN2
Connect to the outdoor
power circuit board (CN2)
1
-
5
:
Power circuit board
➔
Transmitting signal to
the controller circuit board
(0-5V DC)
2
-
5
: Zero cross signal
(0-5V DC)
3
-
4
: Not used
6
-
5
: 18V DC
7
-
5
: 18V DC
[
5
: –
1
,
2
,
6
,
7
: + ]
21S4
Four-way valve
63H
High pressure switch
63L
Low pressure switch
SV2
Solenoid valve2
CN4
Transmission
to outdoor
power circuit
board (CN4)
LED3
SW10
SW2
SW4
Test operation
SW6
Model setup
SW5
Function switch
SW1
Forced defrost,
detect history
record reset
CNDM
1
to
2
: Input of low noise mode
1
to
3
: Input of external
contact point
TH4
Thermistor
<Discharge>
TH3
Thermistor
<Outdoor pipe>
TH7
Thermistor<Outdoor>
TH6
Thermistor
<Outdoor 2-phase pipe>
CNDC
DC280V-350V
Connect from
outdoor power
circuit board
(CNDC)
–
+
}
V
CC
(TEST POINT
2
)
(voltage between pins of C6B): DC 15V
V
DC
(TEST POINT
1
)
(voltage between pins of
C5E): DC280V-350V
V
FB
(TEST POINT
4
)
(voltage between right
pins of PC5C and
PC5D, pin 3 and pin 4)
V
SP
(TEST POINT
3
)
(voltage between pins of
C5A, C5B): DC 0V (when
stopped), DC 1– 6.5V
(when operated)
SV1
Solenoid valve1
52C
Contactor
<CAUTION> TEST POINT
1
is high voltage.
63HS
High pressure
sensor
SW7
SW9
CN3S
CN51