![Mitsubishi Electric MXZ-8A140VA Скачать руководство пользователя страница 56](http://html.mh-extra.com/html/mitsubishi-electric/mxz-8a140va/mxz-8a140va_technical-and-service-manual_1811338056.webp)
56
BRANCH BOX : PAC-AK50BC
PAC-AK30BC
1
2
3
4
5
6
M
Blue
Brown
Yellow
Orange
Red
White
Parts name
Check points
Disconnect the connector then measure the resistance with a tester.
(At the ambient temperature 10
:
~30
:
)
Disconnect the connector then measure the resistance with a tester.
(Winding temperature 20
:
)
Thermistor (TH-A~E)
<Gas pipe>
Normal
4.3k
"
~9.6k
"
Abnormal
Open or short
Normal
Red - White Red - Orange Brown - Yellow Brown - Blue
Abnormal
46
±
4
"
Linear expansion valve
( LEV-A~E )
Open or short