9-6. HOW TO CHECK THE PARTS
OUTDOOR UNIT : MXZ-8A140VA MXZ-8A140VA
1
MXZ-8A140VA
2
MXZ-8A140VA
3
Parts name
Check points
Disconnect the connector then measure the resistance with a tester.
(At the ambient temperature 10
:
~30
:
)
Thermistor (TH3)
<Outdoor pipe>
Thermistor (TH4)
<Discharge>
Thermistor (TH7)
<Outdoor>
Thermistor (TH8)
<Heatsink>
Normal
160k
"
~410k
"
4.3k
"
~9.6k
"
39k
"
~105k
"
TH4
TH3
TH7
TH8
Abnormal
Open or short
Measure the resistance between the terminals with a tester.
(At the ambient temperature 20
:
)
Solenoid valve coil
<Four-way valve>
(21S4)
Motor for compressor
(MC)
Normal
Abnormal
Open or short
Measure the resistance between the terminals with a tester.
(At the ambient temperature 20
:
)
Normal
1197
±
10
"
Abnormal
Open or short
Solenoid valve coil
<Bypass valve>
(SV2)
Measure the resistance between the terminals with a tester.
(At the ambient temperature 20
:
)
Normal
1327
±
10
"
Abnormal
Open or short
Solenoid valve coil
<Bypass valve>
(SV1)
Fan motor(MF1,MF2)
1370
±
100
"
0.188
"
Measure the resistance between the terminals with a tester.
(Winding temperature 20
:
)
Normal
Abnormal
Open or short
W
V
U
Refer to next page.
MXZ-8A140VA
(1)
MXZ-8A140VA
2, 3
1435
±
150
"
MXZ-8A140VA
(1)
MXZ-8A140VA
2, 3
1450
±
150
"