52
Fig.9-1
9-5. SPECIAL FUNCTIONS
9-5-1. Low noise mode (on-site modification) (Fig. 9-1)
By performing the following modification, operation noise of the outdoor unit can be reduced by about 3-4 dB.
The low noise mode will be activated when a commercially available timer or the contact input of an ON/OFF switch is added
to the CNDM connector (optional parts) on the control board of the outdoor unit.
• The capacity may be insufficient according to the outdoor temperature and conditions, etc.
1
Complete the circuit as shown when using the external input adapter (PAC-SC36NA). (Optional parts)
SW1
X
CNDM
X
B
C
H
I
J
G
D
1
3
A
E
F
1
2
3
A
Remote control panel
B
Relay circuit
C
External input adapter (PAC-SC36NA)
D
Outdoor unit control board
E
Replay power supply
F
Procure locally
G
Max. 10m
H
Orange
I
Brown
J
Red
~
Fig.9-2
9-5-2. Demand function (on-site modification) (Fig. 9-2)
• It is possible to reduce electricity consumption within a range from 0 to 100 % by performing the following on-site
installation.
The demand function can be enabled by adding a commercially available input contact point ON/OFF switch to the CNDM
connector (the contact point demand input, optional parts).
1
Incorporate the “Adapter for external input (PAC-SC36NA)” into the circuit as shown in the diagram below.
2
By switching SW7-1 on the control circuit board for the outdoor unit, the following power consumption restrictions
(compared to rated power) can be set.
CN51
X
5
4
3
A
C
D
5
E
1
1
3
B
G
Y
L
1
: Error display lamp
L
2
: Compressor operation lamp
X, Y : Relay (Coil standard of 0.9W or less for DC 12V)
F
A
C
D
E
B
G
F
CN3S
X
Y
SW1
SW2
1
2
3
X, Y : Relay (DC1mA)
SW1
SW2
ON
Heating
Validity of SW1
OFF
Cooling
Invalidity of SW1
A
Distant control board
B
Relay circuit
C
External output adapter (PAC-SA88HA-E)
D
Outdoor unit control board
A
Remote control panel
B
Relay circuit
C
External input adapter (PAC-SC36NA)
D
Outdoor unit control board
E
Relay power supply
F
Procure locally
G
Max. 10m
w
The indoor unit, which is operating in the mode different from
the one determined by external signal (CN3S), will be a state of standby.
w
The setting becomes effective when the outdoor unit is under stop.
w
The operation mode specified by test run will be prior to the mode of this function.
E
Lamp power supply
F
Procure locally
G
Max. 10m
F
E
A
B
C
H
I
J
D
1
3
G
~
~
Y
X
Y
X
L
1
L
2
Y
CNDM
SW2
1
2
3
A
Remote control panel
B
Relay circuit
C
External input adapter (PAC-SC36NA)
D
Outdoor unit control board
E
Replay power supply
F
Procure locally
G
Max. 10m
H
Orange
I
Brown
J
Red
~
Y
SW7-1
Power consumption when SW2 is on
OFF
0% (Forced compressor stop)
ON
50%
9-5-3.Error and compressor operation monitoring function (CN51)
Fig.9-3
9-5-4. Auto change over - Operation mode locking function by external signal (CN3S)
Fig.9-4