background image

VG79Y132H02

HEAD OFFICE: TOKYO BUILDING, 2-7-3, MARUNOUCHI, CHIYODA-KU, TOKYO 100-8310, JAPAN

Importer:

Mitsubishi Electric Europe B.V.

Capronilaan 46, 1119 NS, Schiphol Rijk, The Netherlands

French Branch

25, Boulevard des Bouvets, 92741 Nanterre Cedex, France

German Branch

Mitsubishi-Electric-Platz 1, 40882 Ratingen, Germany

Belgian Branch

Autobaan 2, 8210 Loppem, Belgium

Irish Branch

Westgate Business Park, Ballymount, Dublin 24, Ireland

Italian Branch

Centro Direzionale Colleoni, Palazzo Sirio-Ingresso 1 Viale Colleoni 7, 20864 Agrate Brianza

(MB), Italy

Norwegian Branch

Gneisveien 2D, 1914 Ytre Enebakk, Norway

Portuguese Branch

Avda. do Forte, 10, 2799-514, Carnaxide, Lisbon, Portugal

Spanish Branch

Carretera de Rubi 76-80 - Apdo. 420 08173 Sant Cugat del Valles (Barcelona), Spain

Scandinavian Branch

Hammarbacken 14, P.O. Box 750 SE-19127, Sollentuna, Sweden

UK Branch

Travellers Lane, Hatfield, Herts., AL10 8XB, England, U.K.

Polish Branch

Krakowska 50, PL-32-083 Balice, Poland

MITSUBISHI ELECTRIC TURKEY ELEKTRİK ÜRÜNLERI A.Ş.

Şerifali Mah. Kale Sok. No: 41 34775 Ümraniye, İstanbul / Turkey

VG79Y132H02_backcover.indd   3

2020/02/05   15:20:30

Содержание MXZ-6F122VF

Страница 1: ...eve apenas a instalação da unidade exterior Quando proceder à instalação da unidade interior consulte o manual de instalação da unidade interior Installationshåndbog Til INSTALLATØREN Denne håndbog beskriver kun hvordan udendørsenheden installeres Vedrørende installation af indendørsenheden henvises til installationshåndbogen for indendørsenheden Installationsanvisning För INSTALLATÖREN Denna inst...

Страница 2: ...лі а потім мову BG Посетете горепосочения уебсайт за да изтеглите ръководства като изберете име на модел и след това език PL Odwiedź powyższą stronę internetową aby pobrać instrukcje wybierz nazwę modelu a następnie język CS Příručky naleznete ke stažení na internetové stránce zmíněné výše poté co zvolíte model a jazyk SK Na webovej stránke vyššie si môžete stiahnuť návody Vyberte názov modelu a z...

Страница 3: ...efrigerant circuit Any presence of foreign substance such as air can cause abnormal pressure rise and may result in explosion or injury The use of any refrigerant other than that specified for the system will cause mechanical failure system malfunction or unit breakdown In the worst case this could lead to a serious impediment to securing product safety Do not discharge the refrigerant into the at...

Страница 4: ...isk of combustible gas leakage When installing the unit be sure to secure the unit legs Where it is at least 3 m away from the antenna of TV set or radio Operation of the air conditioner may interfere with radio or TV reception in areas where reception is weak An amplifier may be required for the affected device Install the unit horizontally Please install it in an area not affected by snowfall or...

Страница 5: ...or more Blowing guide PAC SH96SG E Height of the obstacle is 1200 or less OK OK OK NG R32 is heavier than air as well as other refrigerants so tends to accumulate at the base in the vicinity of the floor If R32 accumulates around base it may reach a flammable concentration in case room is small To avoid ignition maintaining a safe work environment is required by ensuring appropriate ventilation If...

Страница 6: ...nt C Create an appropriate ventilation open area Make sure that the width of the open area is 0 9 m or more and the height of the open area is 0 15 m or more However the height from the bottom of the installation space to the bottom edge of the open area should be 0 125 m or less Open area should be 75 or more opening B Install in a space with a depression height of 0 125 m M kg Amin m 1 0 12 1 5 ...

Страница 7: ...ended cassette and ceiling concealed 2 2 m or more When installing floor standing refer to indoor unit Installation manual There are restrictions in installation height for each model so read the installation manual for the particular unit M kg Amin m 1 0 3 1 5 4 5 2 0 6 2 5 7 5 3 0 9 3 5 12 4 0 15 5 4 5 20 5 0 24 5 5 29 6 0 35 6 5 41 7 0 47 7 5 54 For wall mounted ceiling suspended cassette and c...

Страница 8: ...drain socket to one of the several drain holes Fix the drain socket into the drain hole of the base using the catches to secure it in place 4 Connect the soft PVC hose I D 15 mm as shown in the illustration 5 Make sure to provide drain piping with a downhill grade for easy drain flow 6 Glue the drain caps to close all the other unnecessary holes with the glue Prepare in the field Note Apply the gl...

Страница 9: ...ctly on the terminal block Be careful not to make mis wiring Fix the wire to the terminal block securely so that no part of its core is appeared and no external force is conveyed to the connecting section of the terminal block 3 Firmly tighten the terminal screws to prevent them from loosening After tightening pull the wires lightly to confirm that they do not move 4 Perform 2 and 3 for each indoo...

Страница 10: ...tion to prevent condensation Copper pipe 1 Cut the copper pipe correctly with pipe cutter Fig 1 2 2 Completely remove all burrs from the cut cross section of pipe Fig 3 Aim the copper pipe downward while removing burrs to prevent burrs from dropping in the pipe 3 Remove flare nuts attached to indoor and outdoor units then put them on pipe having completed burr removal Not possible to put them on a...

Страница 11: ...orque 24 4 to 30 4 N m 250 to 310 kgf cm Service port cap Torque 10 to 12 N m 100 to 120 kgf cm Service port cap Torque 10 to 12 N m 100 to 120 kgf cm Stop valve cap Torque 21 5 to 27 5 N m 220 to 280 kgf cm Make sure to replace the cap after the operation R32 4 2 GAS CHARGE Perform gas charge to unit 1 Connect gas cylinder to the service port of stop valve 2 Perform air purge of the pipe or hose ...

Страница 12: ...low 3 Turn on the main power for the air conditioner SW2 ON 1 2 3 4 5 6 20A ON 1 2 3 4 5 6 Factory setting Full SW1 ON 1 2 3 4 5 6 SW1 ON 1 2 3 4 5 6 SW1 ON 1 2 3 4 5 6 Lower the operating noise How to lower the operating noise 1 Be sure to turn off the main power for the air conditioner before making the setting 2 Set the 5 of SW1 on the outdoor controller board to ON to enable this function 3 Tu...

Страница 13: ... press the piping wiring correction switch SW871 again When the result is Not completed press the piping wiring correction switch SW871 again to cancel this function Then confirm the wiring and piping combination in a conventional manner by operating the indoor units one by one The operation is done while the power is supplied Make sure not to contact parts other than the switch including the P C ...

Страница 14: ...Information of spec name plate VG79Y132H02_backcover indd 1 2020 02 05 15 20 30 ...

Страница 15: ...m beskrivs nedan för användning i bostäder kommersiella miljöer och lätta industriella miljöer ev ticaret ve hafif sanayi ortamlarında kullanım amaçlı üretilen ve aşağıda açıklanan klima ve ısıtma pompalarıyla ilgili aşağıdaki hususları yalnızca kendi sorumluluğunda beyan eder декларира на своя собствена отговорност че климатиците и термопомпите описани по долу за употреба в жилищни търговски и ле...

Страница 16: ...zionale Colleoni Palazzo Sirio Ingresso 1 Viale Colleoni 7 20864 Agrate Brianza MB Italy Norwegian Branch Gneisveien 2D 1914 Ytre Enebakk Norway Portuguese Branch Avda do Forte 10 2799 514 Carnaxide Lisbon Portugal Spanish Branch Carretera de Rubi 76 80 Apdo 420 08173 Sant Cugat del Valles Barcelona Spain Scandinavian Branch Hammarbacken 14 P O Box 750 SE 19127 Sollentuna Sweden UK Branch Travelle...

Отзывы: