2-1. INSTALLING THE UNIT

•  Be sure to fix the unit’s legs  ith bolts  hen installing it.

•  Be sure to install the unit firmly to ensure that it does not fall by an earthquake or a gust.

•  Refer to the figure in the right for concrete foundation.

•  Do not use the drain socket and the drain caps in the cold region. Drain may freeze and it makes the fan stop.

2-2. CONNECTING   IRES FOR OUTDOOR UNIT

•  Be sure to use special circuits for room air conditioner.

•  Wiring  ork should be based on applicable technical standards.

•  Wiring connections should be made follow ing the diagram.
•  Screw s should be tightened so they  w on’t loosen.

ELECTRICAL SPECIFICATIONS

OUTDOOR UNIT

MXZ-3C24NA3

MXZ-3C30NA3

MXZ-4C36NA3

Po er supply (V, PHASE, Hz)

208/230, 1, 60

Max. Fuse size (time delay)  (A)

25

Min. Circuit Ampacity  (A)

22.1

23.1

Fan motor (F.L.A)

2.43

2.43

Compressor

(R.L.A)

12

12

(L.R.A)

13.7

13.7

Control voltage

Indoor unit-Remote controller : (Wireless)

Indoor unit-Outdoor unit : DC12-24V

1) Remove the service panel.

2) Remove the conduit plate.

3) Attach the conduit connector to conduit plate  ith lock nut then secure 

it to the unit w ith screw s.

4) Connect ground w ires to the TB support.

5) Loosen  terminal  scre ,  and  connect  indoor/outdoor  unit  connecting 

ire (B) from the indoor unit correctly on the terminal block. Be careful 

not to make mis- iring. Fix the  ire to the terminal block securely so 

that no part of its core is appeared, and no external force is conveyed 

to the connecting section of the terminal block. 

6) Firmly tighten the terminal scre s to prevent them from loosening. After 

tightening, pull the  ires lightly to confirm that they do not move.

7 ) Perform 5 ) and 6) for each indoor unit.

8) Connect po er supply cord (A).

9) Close the service panel securely. Make sure that 3-2. PIPE CONNEC

-

TION is completed.

Connecting order

•  Connect  the  terminal  block  in 

follow ing order.

 A

B

C

D

P

CONNECTING  IRES AND CONNECTING GROUND  IRE

•  Use solid conductor Min. AWG14 or stranded conductor Min. AWG14.

•  Use double insulated copper  ire  ith 600 V insulation.

•  Use copper conductors only.
*  

F o l l o w   l o c a l   e l e c t ri c a l   c o d e .

PO ER SUPPL  CABLE AND GROUND  IRE

•  Use solid or stranded conductor Min. AWG12.
•  Use copper conductors only.
*  

F o l l o w   l o c a l   e l e c t ri c a l   c o d e .

  ARNING

U s e   t h e   i n d o o r/ o u t d o o r  u n i t   c o n n e c t i n g   w i re   t h a t   m e e t s   t h e   S t a n d -

ards to connect the indoor and outdoor units and fix the  ire to the 

t e rm i n a l   b l o c k   s e c u re l y   s o   t h a t   n o   e x t e rn a l   fo rc e   i s   c o n v e y e d   t o   t h e  
c o n n e c t i n g   s e c t i o n   o f  t h e   t e rm i n a l   b l o c k .   A n   i n c o m p l e t e   c o n n e c t i o n  

or fixing of the  ire could result in a fire.

Remar

*  A disconnect s itch should be required. Check the local code.

* *   Use a ring tongue terminal in order to connect a ground w ire to terminal.

•   C o n n e c t   w i re s   t o   t h e   m a t c h i n g   n u m b e rs   o f  t e rm i n a l s .
•   B e   s u re   t o   a t t a c h   e a c h   s c re w   t o   i t s   c o rre s p o n d e n t   t e rm i n a l   w h e n  

s e c u ri n g   t h e   c o rd   a n d / o r  t h e   w i re   t o   t h e   t e rm i n a l   b l o c k .

For future servicing, give extra length to the connecting  ires.

Service panel

Screw s

Pow er supply

Terminal block for 

indoor/outdoor unit

Lock nut

Conduit plate

Conduit connector

D unit is for 4C36NA3 only

D unit is for 4C36NA3 only

Fix here w ith 
M10 bolts.

Make the setting 

depth deeper.

Make  ith  ider.

Anchor leg

1-1/6 (30) or less

Anchor bolt length

Anchor bolt pitch

(Unit: inch (mm))

23-5/8

(600)

14-9/16 (370)

Conduit plate

2.  OUTDOOR UNIT INSTALLATION

1-3/8 in. 

(35 mm)

5/8 in.

(15  mm)

Lead w ire

GR

Terminal block

Grounding 
terminal * *

208/230 VAC

1 phase 60 Hz

Grounding 
terminal * *

Terminal block 1

Ground

OUTDOOR UNIT

Pow er supply

208/230 VAC 

1 phase 2 w ires 60 Hz

Disconnect 
sw itch *

Grounding 
terminal * *

Terminal block

Terminal block

INDOOR UNIT

Terminal block

A – C  D

A – C  D

WG79A858H01_01En.indd   4

2021/07/29   16:05:55

Содержание MXZ-3C30NA3

Страница 1: ...inée à l INSTALLATEUR Cette notice ne décrit que l installation de l appareil extérieur Lors de l installation de l appareil intérieur consultez la notice d installation de cet appareil Toute altération structurelle requise pour l installation doit être conforme aux exi gences du code du bâtiment local M a n u a l d e i n s t a l a c i ó n Para el INSTALADOR En este manual só lo se describe la ins...

Страница 2: ...o r i n s t a l l a t i o n The pressure of R410A is 1 6 times more than R22 Not using appropriate tools or materials and incomplete installation could cause the pipes to burst or injury W h e n p u m p i n g d o w n t h e re fri g e ra n t s t o p t h e c o m p re s s o r b e fo re d i s c o n n e c t i n g t h e re fri g e ra n t p i p e s If the refrigerant pipes are disconnected w hile the com...

Страница 3: ...F ro n t b l o w i n g s i d e o p e n As long as space indicated in the figure is provided it is allo ed to install the unit w here obstacles are behind and on the sides of the unit No obstacle above the unit FREE SPACE RE UIRED AROUND OUTDOOR UNIT Service space When installing the unit in an area that is enclosed w ith w alls such as a verandah be sure to have enough space as sho n belo In this ...

Страница 4: ...sleeve 1 L Soft PVC hose 19 32 in 15 mm inner diameter or hard PVC pipe VP16 for drain socket 1 1 N o t e Place indoor outdoor unit connecting ire B and po er supply cord A at least 3 ft 1 m a ay from the TV antenna ire The ty for B to in the above table is quantity to be used per indoor unit More than 3 15 16 in 100 mm Open as a rule More than 19 11 16 in 5 00 mm if the front and both sides are o...

Страница 5: ...ING IRES AND CONNECTING GROUND IRE Use solid conductor Min AWG14 or stranded conductor Min AWG14 Use double insulated copper ire ith 600 V insulation Use copper conductors only F o l l o w l o c a l e l e c t ri c a l c o d e PO ER SUPPL CABLE AND GROUND IRE Use solid or stranded conductor Min AWG12 Use copper conductors only F o l l o w l o c a l e l e c t ri c a l c o d e ARNING U s e t h e i n ...

Страница 6: ...ected pipe size differs depending the models and the capacities of indoor units Indoor unit capacity 06 09 12 15 18 24 Indoor unit M series Liquid pipe size ø6 35 ø6 35 ø6 35 ø9 5 2 1 Gas pipe size ø9 5 2 ø9 5 2 ø12 7 ø15 88 Indoor unit S series Liquid pipe size ø6 35 ø6 35 ø6 35 ø9 5 2 Gas pipe size ø9 5 2 ø9 5 2 ø12 7 ø15 88 Indoor unit P series 2 Liquid pipe size ø6 35 ø6 35 ø6 35 ø9 5 2 Gas pi...

Страница 7: ...R410A Compound pressure gauge for R410A 14 7 psi 0 101MPa Handle Low Handle High Vacuum pump for R410A Charge hose for R410A Close Open Hexagonal w rench Stop valve for LIQUID Pressure gauge for R410A Precautions w hen us ing the control valve When attaching the control valve to the service port valve core may deform or loosen if excess pres sure is applied This may cause gas leak Service port Cha...

Страница 8: ...operation is done hile the po er is supplied Make sure not to contact parts other than the s itch including the P C board This may cause electric shock or burn by hot parts and live parts around the s itch Contacting the live parts may cause P C board damage To prevent electronic control P C board damage make sure to perform static elimination before operating this function This function does not ...

Страница 9: ...n t p e n d a n t l i n s t a l l a t i o n a é re z l a p i è c e Tout contact entre le réfrigérant et une flamme pourrait provoquer l émission de gaz toxiques Des fuites de réfrigérant peuvent provoquer une asphyxie Aérez la pièce A la fin de l installation aucune fuite de réfrigérant ne doit être présente sur le circuit En cas de fuite de réfrigérant dans une pièce et si le réfrigérant entre en...

Страница 10: ...ure extérieure est basse veillez à observer les instructions ci dessous N installez jamais l unité externe dans un endroit où le côté présentant l entrée la sortie d air risque d être directement exposé au vent Pour protéger l unité externe du vent installez la de façon à ce que l entrée d air soit face au mur Pour éviter toute exposition au vent il est recommandé d installer un écran de protectio...

Страница 11: ...contenant des métaux de l étain p ex ou un treillis métallique utiliser un morceau de bois traité d une épais seur de 25 32 po 20 mm minimum entre le mur et la tuyauterie ou isoler la tuyauterie en lui appliquant 7 à 8 couches de ruban isolant en vinyle Pour utiliser la tuyauterie existante effectuer un cycle COOL REFROI DISSEMENT de 30 minutes et lancer l aspiration avant de procéder à la dépose ...

Страница 12: ...liser un conducteur massif ou toronné min AWG12 Utiliser des conducteurs en cuivre uniquement R e s p e c t e r l e c o d e é l e c t ri q u e l o c a l A V E R T I S S E M E N T U t i l i s e r l e c â b l e d e c o n n e x i o n c o n fo rm e a u x n o rm e s t e c h n i q u e s p o u r raccorder les unités interne et externe et fixer le câble fermement sur la bloc de sortie de façon que le côté...

Страница 13: ...sur les raccords de tuyauterie de l appareil extérieur N appliquez pas d huile réfrigérante sur les filetages Un couple de serrage excessif endommagera la vis 2 Pour effectuer le raccordement alignez d abord le centre puis serrez à la main l écrou à évasement de 3 à 4 tours 3 Serrez l écrou évasé avec une clé dynamométrique comme indiqué dans le tableau Un serrage excessif pourrait endommager l éc...

Страница 14: ...A I D E F O N C T I O N N E M E N T 1 Retirez le bouchon de l ouverture de service du robinet d arrêt du côté du conduit de gaz de l unité externe A l origine les robinets d arrêt sont com plètement fermés et recouverts d un capuchon 2 Raccordez la vanne du collecteur à jauge et la pompe à vide à l ouverture de service du robinet d arrêt du côté du conduit de gaz de l unité externe 3 Mettez la pom...

Страница 15: ... n t l e m é c a n i s m e d e p ro t e c t i o n c o n t re u n e re m i s e e n m a rc h e t ro p ra p i d e Lorsque le compresseur s arrête le dispositif de protection contre la remise en marche à trop brève échéance s enclenche Le compresseur restera arrêté trois minutes avant de se remettre en marche afin de protéger le climatiseur F o n c t i o n d e c o rre c t i o n d e c â b l a g e t u y...

Страница 16: ... sistema o averí as en la unidad En el peor de los casos esto podr a llegar a ser un serio impedimento para garantizar el uso seguro del producto N o d e s c a rg u e e l re fri g e ra n t e e n e l a m b i e n t e S i s e p ro d u c e n fu g a s d e re fri g e ra n t e d u ra n t e l a i n s t a l a c i ó n v e n t i l e l a h a b i t a c i ó n Si el refrigerante entra en contacto con una llama p...

Страница 17: ... sea baja observe las instrucciones siguientes No instale nunca la unidad exterior en un lugar en el que el lado de entra da salida de aire quede expuesto directamente al viento Para evitar la exposició n al viento instale la unidad exterior con el lado de entrada de aire hacia la pared Para evitar la exposició n al viento se recomienda instalar una placa de flectora en el lado de salida de aire d...

Страница 18: ... y ambos lados está n abiertos Después de la prueba de fugas aplique material aislante de modo que no queden huecos Cuando los tubos deban instalarse en una pared con contenido metá lico placas de lat n o rejillas met licas ponga un trozo de madera tratada qu micamente de 25 32 pulg 20 mm o m s de grosor entre la pared y los tubos o envuelva los tubos con 7 u 8 vueltas de cinta aislante de vinilo ...

Страница 19: ... R A Utilice un conductor s lido o trenzado con un calibre m n AWG12 Use nicamente conductores de cobre S i g a l a n o rm a t i v a e l é c t ri c a l o c a l A T E N C I Ó N C o n e c t e l a s u n i d a d e s i n t e ri o r y e x t e ri o r c o n e l c a b l e d e c o n e x i ó n normalizado destinado a este fin y su ete bien el cable al panel de t e rm i n a l e s d e m o d o q u e n o q u e d...

Страница 20: ...e tuber as E a partir de la entrada de la unidad exterior Sujete con cinta adhesiva el extremo de la cinta de tuberí as E Cuando las tuberí as deban colocarse por encima del techo en un armario empotrado o en lugares con una temperatura y humedad elevadas tendr que aplicar una cantidad suplementaria de aislante para evitar la conden sació n 1 Corte el tubo de cobre correctamente con un cortador de...

Страница 21: ...terarse en el sistema y afectar a la operaci n normal del acondicionador del aire Recuerde también cargar el refrigerante lí quido poco a poco ya que de lo contrario puede bloquear el compresor Para mantener alta la presi n del cilindro de gas caliente el cilindro de gas con agua caliente a menos de 104 F 40 C en las estaciones fr as Nunca utilice fuego o vapor Unió n Vá lvula de retenció n Tuberí...

Страница 22: ...rtas N o t a Durante la detecció n el funcionamiento de la unidad interior estará controlado por la unidad exterior Durante la detecció n la unidad interior dejará de funcionar au tomá ticamente Esto no es un fallo de funcionamiento Procedimiento Mantenga presionado el interruptor de correcci n de tuber as conexiones SW871 1 minuto o má s tras conectar la alimentació n La correcci n tarda entre 10...

Страница 23: ...A4_white_tombo indd 1 2018 08 09 14 11 29 ...

Страница 24: ...HEAD OFFICE TOKY O BLDG 2 7 3 MARUNOUCHI CHIY ODA KU TOKY O 100 8 3 10 JAPAN WG7 9A8 5 8 H01 WG79A858H01_cover4 indd 2 2021 02 10 8 44 04 ...

Отзывы: