10-5. PRE-HEAT CONTROL
If moisture gets into the refrigerant cycle, or when refrigerant is liquefied and collected in the compressor,
it may interfere the start-up of the compressor. To improve start-up condition, the compressor is energized even while it
is not operating to generate heat at the winding.
The compressor uses about 50 W when pre-heat control is turned ON. Pre-heat control is OFF(
MXZ-2HJ40VA
) / ON
(
MXZ-3HJ50VA
) at the default setting.
MXZ-3HJ50VA
[How to activate pre-heat control]
(1) Turn OFF the breaker and make sure that the LED goes off.
(2) Set the “4” of SW2 as shown figure below to OFF to activate pre-heat control function.
(3) Turn ON the breaker.
MXZ-2HJ40VA
[How to activate pre-heat control]
(1) Turn OFF the breaker and make sure that the LED goes off.
(2) Set the “4” of SW2 as shown figure below to ON to activate pre-heat control function.
(3) Turn ON the breaker.
NOTE:
Pre-heat control will be turned OFF when the breaker is turned OFF.
SW2 on the outdoor display P.C. board
Switch
Pre-heat control
SW2
Deactivated
(Default setting)
Activated
SW2 on the outdoor control P.C. board
Switch
Pre-heat control
SW2
Activated
(Default setting)
Deactivated
OBH709A