58
Check of outdoor thermistors
• When thermistor is abnormal.
Replace the thermistor except RT64.
If RT64 is abnormal, replace the outdoor power
P.C. board since RT64 is combined with this board.
Disconnect the connector in the following table and
measure the resistance of the thermistor to check
whether the thermistor is normal or not. (Refer to 12-7.)
Does the unit operate 10 minutes or more without
showing thermistor abnormality?
Normal
Replace the outdoor control P.C. board or the
outdoor power P.C. board.
Reconnect the connector in the following table and
disconnect the lead wire leading to the compressor.
3 minutes after turning ON the power supply,
start EMERGENCY OPERATION.
Thermistor
Defrost
Discharge temperature
Fin temperature
Ambient temperature
Outdoor heat exchanger temperature
Symbol
RT61
RT62
RT64
RT65
RT68
Connector, Pin No.
CN641 pin1 and pin2
CN641 pin3 and pin4
CN642 pin1 and pin2
CN643 pin1 and pin2
CN644 pin1 and pin3
Inverter P.C. board
Board
MXZ-2HA40VF
MXZ-2HA50VF
MXZ-3HA50VF
Normal
Yes
No
Abnormal
Thermistor
Defrost
Discharge temperature
Outdoor heat exchanger temperature
Ambient temperature
Fin temperature
Symbol
RT61
RT62
RT68
RT65
RT64
Connector, Pin No.
Between CNTH1 pin1 and pin2
Between CNTH1 pin3 and pin4
Between CNTH1 pin7 and pin8
Between CNTH2 pin1 and pin2
Between CN171 pin1 and pin2
Outdoor control P.C. board
Outdoor power P.C. board
Board
OBH828A
Содержание MXZ-2HA40VF
Страница 18: ...18 OUTLINES AND DIMENSIONS 6 MXZ 2HA40VF MXZ 2HA50VF Unit mm inch OBH828A ...
Страница 22: ...22 MXZ 3HA50VF E1 MXZ 3HA50VF E2 OBH828A ...
Страница 23: ...23 MXZ 3HA50VF ET1 OBH828A ...