24
REFRIGERANT SYSTEM DIAGRAM
8
Stop valve
(with strainer #100)
LEV A
LEV B
Compressor
Defrost
thermistor RT61
Distributor
Muffler
4-way valve
Indoor unit
A
Indoor unit
B
Indoor unit
A
Indoor unit
B
Capillary tube
Capillary tube
Capillary tube
Strainer
#100
Stop valve
(with strainer #100)
R.V. coil
OFF
ON
Refrigerant flow in cooling
Refrigerant flow in heating
Ambient
temperature
thermistor
RT65
Outdoor heat
exchanger
temperature
thermistor RT68
FAN-OUT
HEX-OUT
Discharge
temperature
thermistor RT62
Stop valve
(with service port)
Stop valve
(with service port)
Sub muffler
UNIT: mm
MXZ-2HA40VF MXZ-2HA50VF
MAX REFRIGERANT PIPING LENGTH
Piping length each indoor unit (a, b)
20 m
Total piping length (a+b)
30 m
Bending point for each unit
30
Total bending point
20
*It is irrelevant which unit is higher.
a
b
Outdoor
unit
Indoor
units
15 m
10 m
15 m
Max.
Height
difference
UNIT: mm (inch)
Outdoor unit union diameter
For
Indoor unit A
Liquid
6.35(1/4)
Gas
9.52(3/8)
Indoor unit B
Liquid
6.35(1/4)
Gas
9.52(3/8)
ADDITIONAL REFRIGERANT CHARGE
Outdoor unit
precharged
(g)
Refrigerant piping length (one way, 2 unit total)
30 m
900
0
OBH828A