62
Check of outdoor refrigerant circuit
MXZ-2HA40VF/2HA50VF
Has the operation stopped during pump down?
Was the operation started with the stop valve
closed, and was it opened during operation?
No
Yes
The operation has stopped to prevent the diesel explosion
caused by air trapped in the refrigerant circuit. Close the stop
valve, and disconnect the power plug or turn the breaker OFF.
The unit occasionally stops when the stop valve is opened
or closed during operation. Open the stop valve and start the
cooling operation again.
Yes
No
The refrigerant gas amount may be 60% or less than
the normal amount. Identify where the gas is leaking
from, and fix the leak.
CAUTION:
Do not start the operation again to prevent hazards.
OBH828A