N Check of the outdoor refrigerant circuit
Has the operation stopped
during pump down?
Was the operation started with
the stop valve closed, and was
it opened during operation?
No
Yes
The operation has stopped to pre-
vent the diesel explosion caused by
air trapped in the refrigerant circuit.
Close the stop valve, and disconnect
the power plug or turn the breaker
OFF. *
The unit occasionally stops when the
stop valve is opened or closed during
operation. Open the stop valve and
start the cooling operation again.
Yes
No
The refrigerant gas amount may be
60% or less than the normal amount.
Identify where the gas is leaking from,
and
fi
x the leak.
*
CAUTION : Do not start the opera-
tion again to prevent
hazards.
OBH767