3. Outdoor unit failure mode table
MUZ-GB50VA-
E1
/
E2
The left lamp of
OPERATION INDICATOR
lamp (Indoor unit)
Abnormal point
(Failure mode / protection)
LED indication
(Outdoor P.C.
board)
Condition
Remedy
Indoor/
outdoor unit
failure mode
recall function
LED1
LED2
OFF
None (Normal)
—
—
—
—
—
2-time
fl
ash
Outdoor power system
Lighting Lighting Overcurrent protection stop is continuously
performed 3 times within 1 minute after the
compressor gets started, or when converter
protection stop or bus-bar voltage protection
stop is continuously performed 3 times within 3
minutes after start-up.
• Check the connection of the
compressor connecting wire.
• Refer to 11-5. "How to
check inverter/compressor".
• Check the stop valve.
○
3-time
fl
ash
Discharge temperature
thermistor
Lighting
Once
Thermistor shorts or opens during compressor
running.
• Refer to 11-5. "Check of
outdoor thermistors".
○
Defrost thermistor
Lighting
Once
Ambient temperature
thermistor
Lighting
Twice
Fin temperature thermistor
Lighting 3 times
P.C. board temperature
thermistor
Lighting 4 times
• Replace the outdoor
electronic control P.C. board.
Outdoor heat exchanger
temperature thermistor
Lighting 9 times
• Refer to 11-5. "Check of
outdoor thermistors".
4-time
fl
ash
Overcurrent
Once
Goes out 28 A current
fl
ows into intelligent power module.
• Reconnect compressor
connector.
• Refer to 11-5. "How to
check inverter/compressor.
• Check the stop valve.
—
5-time
fl
ash
Discharge temperature
Lighting Lighting Discharge temperature exceeds 116°C during
operation. Compressor can restart if discharge
temperature thermistor reads 100°C or less 3
minutes later.
• Check refrigerant circuit and
refrigerant amount.
• Refer to 11-5. "Check of
LEV".
—
6-time
fl
ash
High pressure
Lighting Lighting The outdoor heat exchanger temperature
exceeds 70°C during cooling or the indoor gas
pipe temperature exceeds 70°C during heating.
• Check refrigerant circuit and
refrigerant amount.
• Check the stop valve.
—
7-time
fl
ash
Fin temperature
3 times Goes out The
fi
n temperature exceeds 87°C during
operation.
• Check around outdoor unit.
• Check outdoor unit air
passage.
• Refer to 11-5. "Check of
outdoor fan motor".
—
P.C. board temperature
4 times Goes out The P.C. board temperature exceeds 70°C during
operation.
8-time
fl
ash
Outdoor fan motor
Lighting Lighting Failure occurs continuously three times within 30
seconds after the fan gets started.
• Refer to 11-5. "Check of
outdoor fan motor".
—
9-time
fl
ash
Nonvolatile memory data
Lighting 5 times Nonvolatile memory data cannot be read
properly.
• Replace the outdoor
electronic control P.C. board.
○
10-time
fl
ash Discharge temperature
Lighting Lighting The frequency of the compressor is kept 80 Hz
or more and the discharge temperature is kept
under 39°C for more than 20 minutes.
• Check refrigerant circuit and
refrigerant amount.
• Refer to 11-5. "Check of
LEV".
—
11-time
fl
ash
Communication error between
P.C. boards
Lighting 6 times Communication error occurs between the
electronic control P.C. board and power board for
more than 10 seconds.
• Check the connecting wire
between outdoor electronic
control P.C. board and power
board.
—
The communication between boards protection
stop is continuously performed twice.
○
Current sensor
Lighting 7 times A short or open circuit is detected in the current
sensor during compressor operating.
• Replace the power board.
—
Current sensor protection stop is continuously
performed twice.
○
Zero cross detecting circuit
5 times Goes out Zero cross signal cannot be detected while the
compressor is operating.
• Check the connecting wire
among electronic control P.C.
board, noise
fi
lter P.C. board
and power board.
—
The protection stop of the zero cross detecting
circuit is continuously performed 10 times.
○
Converter
5 times Goes out A failure is detected in the operation of the
converter during operation.
• Check the voltage of power
supply.
• Replace the power board.
—
Bus-bar voltage
(1)
5 times Goes out The bus-bar voltage exceeds 400 V or falls to
200 V or below during compressor operating.
Bus-bar voltage
(2)
Even if this protection stop
is performed continuously 3
times, it does not mean the
abnormality in outdoor power
system.
6 times Goes out The bus-bar voltage exceeds 400 V or falls to 50
V or below during compressor operating.
• Check the voltage of power
supply.
• Replace the outdoor
electronic control P.C. board.