ADDITIONAL REFRIGERANT CHARGE (R410A : g)
Model
Outdoor unit
precharged
Refrigerant piping length (one way)
7 m
10 m
15 m
20 m
25 m
30 m
MUZ-GB50VA
1,500
0
60
160
260
360
460
Calculation : X g = 20 g/m × (Refrigerant piping length (m) - 7)
NOTE
: Refrigerant piping exceeding 7 m requires additional refrigerant charge according to the calculation.
MAX. REFRIGERANT PIPING LENGTH and MAX. HEIGHT DIFFERENCE
Refrigerant piping : m
Piping size O.D : mm
Max. Length
A
Max. Height difference
B
Gas
Liquid
MUZ-GB50VA
30
15
12.7
6.35