Check of LEV (Expansion valve)
K
Heating/Cooling does not work sufficiently.
Replace the LEV.
Expansion valve operates in
full-opening direction.
Is LEV properly fixed to the
expansion valve?
OK
Do you hear the expansion
valve "click, click·······"?
Do you feel the expansion
valve vibrate on touching it ?
Does the resistance of LEV
have the characteristics?
(Refer to 11-4.)
Measure each voltage between connector pins
of CN724 on the inverter P.C. board.
1.Pin
3
(-) Pin
1
(+)
2.Pin
4
(-) Pin
1
(+)
3.Pin
5
(-) Pin
1
(+)
4.Pin
6
(-) Pin
1
(+)
Is there about 3~5 VAC between each?
NOTE: Measure the voltage by an analog tester.
No
Yes
Yes
Yes
No
Yes
No
No
Properly fix the LEV to the
expansion valve.
Replace the inverter P.C. board.
NOTE : After check of LEV, do the undermentioned operations.
1. Turn OFF the power supply and turn ON it again.
2. Press RESET button on the remote controller.
Replace the LEV.
W
1. Regardless of normal or abnormal condition,
a short beep is emitted once the signal is received.
Turn ON the power supply.
<Preparation of the remote controller>
1
While pressing both OPERATION SELECT
button and TOO COOL button on the remote
controller at the same time, press RESET button.
2
First, release RESET button.
And release the other two buttons after all LCD
except the set temperature in operation display
section of the remote controller is displayed after
3 seconds.
Press OPERATE/STOP(ON/OFF) button of the remote
controller (the set temperature is displayed) with the
remote controller headed towards the indoor unit.
W
1