REFRIGERANT SYSTEM DIAGRAM
Unit:mm
MUZ-FD25VA
MUZ-FD25VAH
MUZ-FD35VA
MUZ-FD35VAH
Outdoor
heat
exchanger
Flared connection
Defrost
thermistor
RT61
Discharge
temperature
thermistor
RT62
Flared connection
Stop valve
(with strainar)
Stop valve
(with service port)
Refrigerant flow in cooling
Compressor
4-way valve
Refrigerant flow in heating
Refrigerant pipe
[
9.52
(with heat insulator)
Refrigerant pipe
[
6.35
(with heat insulator)
R.V. coil
heating ON
cooling OFF
Strainer
#100
Capillary tube
[
3.0
✕
[
1.8
✕
600(
✕
2)
LEV
Ambient
temperature
thermistor
RT65
Muffler
Capillary tube
[
3.0
✕
[
2.0
✕
240
Outdoor heat
exchanger
temperature
thermistor
RT68
Muffler
ADDITIONAL REFRIGERANT CHARGE (R410A:g)
Outdoor unit
precharged
14m
7m
6m
5m
11m
Model
Refrigerant piping length (one way)
8m
9m
10m
12m
13m
15m
20m
270
0
0
0
180
90
120
150
210
240
300
450
1,150
MUZ-FD25VA
MUZ-FD25VAH
MUZ-FD35VA
MUZ-FD35VAH
Max. length
A
Max. Height
difference
B
Indoor
unit
Outdoor unit
MAX. REFRIGERANT PIPING LENGTH and MAX. HEIGHT DIFFERENCE
Max. length
A
20
Max. Height difference
B
12
Model
Gas
9.52
Liquid
6.35
Piping size O.D : mm
Refrigerant piping : m
MUZ-FD25VA
MUZ-FD25VAH
MUZ-FD35VA
MUZ-FD35VAH
Calculation : Xg=30 g/m
✕
(Refrigerant piping length (m)–7)
NOTE: Refrigerant piping exceeding 7 m requires additional refrigerant charge according to the calculation.
OBH489--1.qxp 07.8.9 11:53 AM Page 10