28
11-4. Trouble criterion of main parts
MUZ-FD25VA
MUZ-FD35VA
MUZ-FD25VAH
MUZ-FD35VAH
Part name
Figure
Check method and criterion
Outdoor fan motor (MF)
R.V. coil (21S4)
Expansion valve coil (LEV)
Measure the resistance between the terminals with a tester.
(Part temperature –20 ~ 40 ˚C)
WHT – BLK
BLK – RED
RED – WHT
Normal
Measure the resistance between the terminals with a tester.
(Part temperature –10 ~ 40 ˚C)
Normal
1.32 k
"
~ 1.62 k
"
WHT – RED
RED – ORN
YLW – BRN
BRN – BLU
Normal
40
"
~ 50
"
Measure the resistance with a tester.
(Part temperature –10 ~ 40 ˚C)
Measure the resistance with a tester.
Refer to 11-7. "Test point diagram and voltage", 1. "Inverter P.C. board",
the chart of thermistor.
Refer to 11-7. "Test point diagram and voltage", 1. "Inverter P.C. board",
the chart of thermistor.
Color of the lead wire
Color of the lead wire
Discharge temperature
thermistor (RT62)
Measure the resistance with a tester.
Before measurement, hold the thermistor with your hands to warm it up.
Defrost thermistor
(RT61)
Fin temperature
thermistor (RT64)
Ambient temperature
thermistor (RT65)
11
"
~ 16
"
Measure the resistance between the terminals with a tester.
(Part temperature –20 ~ 40 ˚C)
Compressor (MC)
U-V
U-W
V-W
Normal
0.82
"
~ 1.06
"
Measure the resistance with a tester.
(Part temperature –10 ~ 40 ˚C)
2
3
W
U
V
1
WHT
RED BLK
2
3
W
U
V
1
WHT
RED BLK
Defrost heater (H)
Normal
349
"
~ 428
"
MUZ-FD25/35VAH
Outdoor heat exchanger
temperature thermistor
(RT68)
LEV
WHT
6
RED
1
ORN
4
YL
W
5
BRN
2
BLU
3
OBH489--1.qxp 07.8.9 11:53 AM Page 28
Содержание MUZ-FD25VA
Страница 2: ...2 ...
Страница 8: ...8 6 WIRING DIAGRAM MUZ FD25VA MUZ FD35VA ...
Страница 9: ...9 MUZ FD25VAH MUZ FD35VAH ...
Страница 42: ...42 ...
Страница 43: ...43 ...