Indoor
unit
Max. Height
difference
B
Outdoor unit
Refrigerant Piping
Max. Length
A
ADDITIONAL REFRIGERANT CHARGE (R410A: g)
MAX. HEIGHT DIFFERENCE
Model
Outdoor unit precharged
Refrigerant piping length (one way)
7.5m
10m
15m
20m
MU-GF20VA
650
0
50
150
250
MU-GF25VA
650
0
50
150
250
MU-GF35VA
1,100
0
50
150
250
Calculation: Xg = 20 g/m x (Refrigerant piping length (m) - 7.5)
NOTE
: Refrigerant piping exceeding 7.5 m requires additional refrigerant charge according to the calculation.
MAX. REFRIGERANT PIPING LENGTH and MAX. HEIGHT DIFFERENCE
Refrigerant piping: m
Piping size O.D: mm
Max. Length
A
Max. Height difference
B
Gas
Liquid
MU-GF20VA
20
10
9.52
6.35
MU-GF25VA
20
10
9.52
6.35
MU-GF35VA
25
10
9.52
6.35
MU-GF50VA
30
10
12.7
6.35
MU-GF60VA
30
10
15.88
6.35
MU-GF80VA
30
15
15.88
9.52
Model
Outdoor unit
precharged
Refrigerant piping length (one way)
7 m
10 m
15 m
20 m
25m
30m
MU-GF50VA
1,200
0
50
150
250
350
450
MU-GF60VA
1,300
MU-GF80VA
1,850
Calculation: X g = 20 g/m × (Refrigerant piping length (m) - 7.5)
NOTE
: Refrigerant piping exceeding 7.5 m requires additional refrigerant charge according to the calculation.
MU-GF50VA MU-GF60VA MU-GF80VA
MU-GF20VA MU-GF25VA MU-GF35VA