OPERATING PROCEDURE
PHOTOS
Photo 6
4. Removing the compressor
(1) Remove the cabinet. (Refer to 1.)
(2) Remove the relay panel.
(3) Remove the soundproof felt.
(4) Remove the terminal cover.
(5) Pull out the lead wires from the glass terminal of the com-
pressor.
(6) Recover gas from the refrigerant circuit.
NOTE:
Recover gas from the pipes until the pressure gauge
shows 0 kg/cm
2
(0 MPa).
(7) Disconnect the brazed parts of the suction pipe and dis-
charge pipe.
(8) Remove the nuts fixing the compressor and the compres-
sor.
Glass
terminal
Brazed part of the
discharge pipe
Brazed part of the
suction pipe
Compressor nuts
Compressor
OBH622A