9-11. Outdoor fan motor control
The AC fan motor turns ON/OFF, interlocking with the compressor.
[ON] The AC fan motor turns ON 5 seconds before the compressor starts up.
[OFF] The AC fan motor turns OFF 15 seconds after the compressor has stopped running.
In COOL mode, the two indoor coil thermistor (one main and one sub) sense temperature ununiformity (super heat)
at the heat exchanger, and when temperature difference have developed, the indoor coil thermistors adjust LEV
opening to get approximate 10 degrees lower temperature than the target temperature in the table above, thus
diminishing super heat.
(2) Time chart
OFF Time
Time
ON
The operational frequency
of the compressor
Commanded
to open
Standard
opening
degree
Opening degree is
corrected according
to discharge
temperature.
Positioning
Air conditioner ON
Air conditioner OFF
(thermostat off)
LEV opening degree
13 min.
(3) Control data
06
05
04
03
02
01
LEV opening degree
A(target discharge temperature)
B
C
D
E
F
30
50
70
The operational frequency of the compressor
90
110
130
(Hz)
A
58/49
B
63/58
C
69/66
D
74/71
E
74/76
F
74/78
(a) Reference value of target discharge temperature
(COOL/HEAT
:
)
01
150/70
02
170/90
03
180/110
04
190/140
05
200/150
06
200/160
(b) Reference value of LEV standard degree opening
(COOL/ HEAT pulse)
57/48
60/57
67/66
75/71
78/76
78/78
MSZ-G09SV -
MSZ-G09SV -
E2
E1
MSZ-G12SV -
MSZ-G12SV -
E2
E1
160/90 190/120 200/140 220/160 240/180 255/200
MSZ-G09SV -
MSZ-G09SV -
E2
E1
MSZ-G12SV -
MSZ-G12SV -
E2
E1