Mode

Operation Indicator lamp

1

COOL

 (Light) 

(Off)

2

STOP

 (Off) 

(Off)

6-5 TEST RUN

  Before performing the test run, recheck for any wrong wiring.

 

Wrong wiring prevents normal operation or results in blown fuse disabling operation.

  The test run can be started by pressing EMERGENCY OPERATION switch. When 

the EMERGENCY OPERATION switch is once pressed, the unit will start the test run 
(continuous operation) for 30 minutes.

  A thermostat does not work during this time. After 30 minutes the unit will start the 

EMERGENCY OPERATION at a fi xed temperature setting of 24 °C in COOL MODE.

  Perform test run in the following procedure.

PURGING PROCEDURES

Connect the refrigerant pipes (both liquid pipe and the gas pipe) between the indoor 
and the outdoor unit.

Remove the service port cap of the stop valve on the side of the outdoor unit gas 
pipe. (The stop valve will not work in its initial state fresh out of the factory (totally 
closed with cap on).)

Connect the gauge manifold valve and the vacuum pump to the service port of the 
stop valve on the gas pipe side of the outdoor unit.

Run the vacuum pump. (Vacuumize for more than 15 minutes.)

Check the vacuum with the gauge manifold valve, then close the gauge manifold 
valve, and stop the vacuum pump.

Leave as it is for one or two minutes. Make sure the pointer gauge manifold valve 
remains in the same position. Confi rm that the pressure gauge shows–0.101 Mpa 
[Gauge] (–760 mmHg).

Pipe length up to 7 m 
No gas charge is needed.

Pipe length exceeding 7 m
Charge the prescribed amount 
of gas. (refer to 3)

Remove the gauge manifold valve quickly from the service port of the stop valve.

After refrigerant pipes are connected and evacuated, fully open all stop valves on 
both sides of gas pipe and liquid pipe.
Operating without fully opening lowers the performance and this causes trouble.

Tighten the cap to the service port to obtain the initial status.

Retighten the cap.

Leak test

Close

Open

Hexagonal wrench

Stop valve

Gauge manifold valve

Gas pipe

Hexagonal
wrench

Caps

Service port

Vacuum pump

Charge
hose

Stop valve

Mode

Operation Indicator lamp

1

COOL

 (Light) 

(Off)

2

HEAT

 (Off) 

(Light)

3

STOP

 (Off) 

(Off)

6-4  PURGING PROCEDURES·LEAK TEST

INSULATION AND TAPING

1

  Cover piping joints with pipe cover.

2

  For outdoor unit side, surely insulate every piping including valves.

3

  Using piping tape 

G

, apply taping starting from the entry of outdoor unit.

  Stop the end of piping tape 

G

 with tape (with adhesive agent attached).

  When piping have to be arranged through above ceiling, closet or where the 

temperature and humidity are high, wind additional commercially sold insulation for 
prevention of condensation.

2

  Outdoor unit connection

Connect pipes to stop valve pipe joint of the outdoor unit in the same manner applied for 
indoor unit.

  For tightening, use a torque wrench or spanner and use the same tightening torque 

applied for indoor unit.

Pipe diameter

Tightening torque

mm

N·m

kgf·cm

6.35

13.7 to 17.7

140 to 180

9.52

34.3 to 41.2

350 to 420

15.88

73.5 to 78.4

750 to 800

Tightening torque

N·m

kgf·cm

Cap for service port

13.7 to 17.7

140 to 180

Cap for stop valve

19.6 to 29.4

200 to 300

Checking the remote (infrared) signal reception

Press the ON/OFF button on the remote controller and check that an electronic sound is 
heard from the indoor unit. Press the ON/OFF button again to turn the air conditioner off.

If the indoor unit is operated with the remote controller, both the test 
run and the emergency operation are released by commands from 
the remote controller.

  Once the compressor stops, the restart preventive device operates so the compressor 

will not operate for three minutes to protect the air conditioner.

6-6  EXPLANATION TO THE CUSTOMER

  Using the OPERATING INSTRUCTIONS, explain the following to the customer, how to

  control temperature, how to remove the air fi lters, how to remove or put the remote
 

controller in the remote controller holder, how to clean, precautions for operation, etc.

  Recommend the customer to read the OPERATING INSTRUCTIONS carefully.

PROCEDURE

  Press the EMERGENCY OPERATION switch.

1

  Press it once, and after test run for 30 minutes the EMERGENCY COOL MODE starts.

If the left side lamp of the operation indicator blinks every 0.5 seconds, inspect 
the indoor/outdoor unit connecting wire 

A

 for mis-wiring.

2

  Press it once more, and the EMERGENCY HEAT MODE starts.

3

  Press it once more, and the operation stops.

 

(The operation mode changes in order of 

1

 ~ 

3

 every time the EMERGENCY 

OPERATION switch is pressed.)

  In starting the heating operation, indoor unit fan may not operate to prevent blowing 

cool air. Please wait for a few minutes until the temperature of heat exchanger rises 
and warm air blows out.

Service port

Close

Open

Charge hose

Control Valve

A

Body

Precautions when using the control valve

When attaching the control valve to the 
service port, valve core may deform or 
loosen if excess pressure is applied.
This may cause gas leak.

When attaching the control valve to the 
service port, make sure that the valve core 
is in closed position, and then tighten part 

A

.

Do not tighten part 

A

 or turn the body when 

valve core is in open position.

EMERGENCY
OPERATION switch

MS Type

PROCEDURE

  Press the EMERGENCY OPERATION switch.

1

  Press it once, and after test run for 30 minutes the EMERGENCY COOL MODE starts.

2

  Press it once more, and the operation stops.

 

((The operation mode alternates between 

1

 and 

2

 every time the EMERGENCY 

OPERATION switch is pressed.)

EMERGENCY
OPERATION switch

MSH Type

  Before performing the test run, recheck any wrong wiring.

 

Wrong wiring prevents normal operation or results in blown fuse disabling operation.

  The test run can be started by pressing EMERGENCY OPERATION switch. When 

the EMERGENCY OPERATION switch is once pressed, the unit will start the test run 
(continuous operation) for 30 minutes.

 

A thermostat does not work during this time. After 30 minutes the unit will start the 
EMERGENCY OPERATION at a fi xed temperature setting of 24°C in COOL MODE 
or HEAT MODE.

  Perform test run in the following procedure.

Liquid pipe

Stop valve

MS Type and MSH Type

Содержание MS-GA60VB

Страница 1: ...inflammable gas leaks If gas leaks and accumulates in the area surrounding the unit it could cause an explosion Q Install an earth leakage breaker depending on the installation place Where it is humid If an earth leakage breaker is not installed it could cause an electric shock Q Perform the drainage piping work securely according to the installation manual If there is a defect in the drainage pipi...

Страница 2: ...nstallation Indoor unit 1 Installation plate 1 2 Installation plate fixing screw 4 25 mm 7 3 Remote controller holder 1 4 Fixing screw for 3 3 5 16 mm Black 2 5 Battery AAA for remote controller 2 6 Wireless remote controller 1 7 Felt tape Used for left or left rear piping 1 8 Air cleaning filter 2 PART TO BE PROVIDED AT YOUR SITE Optional extension pipe A Indoor outdoor unit connecting wire 2 core ...

Страница 3: ...ioning of the holes on the wall 4 2 WALL HOLE DRILLING 1 Determine the wall hole position 2 Drill a 75 mm hole so that outside can be lower than inside 3 Insert the wall hole sleeve C When bolts recessed in the concrete wall are to be utilized secure the installation plate 1 using 11 20 11 26 oval hole 450 mm pitch If the recessed bolt is too long change it for a shorter one available in the marke...

Страница 4: ...lace the drain hose below the refrigerant piping Make sure that the drain hose is not heaved or snaked Do not pull the hose to apply the tape When the drain hose passes the room be sure to wrap insulation material obtainable at a store around it Wrap the felt tape 7 around the pipe and the drain hose then put the pipe in the back space of the indoor unit Drain hose Drain cap Cut off in case of lef...

Страница 5: ...ening pull the wires lightly to confirm that they do not move O If the connecting wire is incorrectly connected to the terminal block the unit does not operate normally WARNING O A means for disconnection of the supply with an isolation switch or similar device in all active conductors shall be incorporated in the fixed wiring O Never cut the power cord and connect it to other wires It may cause a fi...

Страница 6: ...ed for HFC refrigerant Torque wrench Yes 1 4 No 1 2 and 5 8 Flare tool Yes Clamp bar hole has been enlarged to reinforce the spring strength in the tool Flare gauge New Provided for flaring work to be used with R22 flare tool Vacuum pump adaptor New Provided to prevent the back flow of oil This adapter enables you to use existing vacuum pumps Electronic scale for refrigerant charging New It is difficu...

Страница 7: ... 140 to 180 9 52 34 3 to 41 2 350 to 420 15 88 73 5 to 78 4 750 to 800 Tightening torque N m kgf cm Cap for service port 13 7 to 17 7 140 to 180 Cap for stop valve 19 6 to 29 4 200 to 300 Checking the remote infrared signal reception Press the ON OFF button on the remote controller and check that an electronic sound is heard from the indoor unit Press the ON OFF button again to turn the air condit...

Страница 8: ...essor will be locked To maintain the high pressure of the gas cylinder warm the gas cylinder with warm water under 40 C during cold season But never use naked fire or steam 7 2 REMOVING THE INDOOR UNIT Remove the bottom of the indoor unit from the installation plate 1 Remove the front panel See FRONT PANEL REMOVAL shown above 2 Insert flat screwdrivers into the square holes at the left and right bot...

Отзывы: