5.  OUTDOOR UNIT INSTALLATION

INDOOR/OUTDOOR UNIT CONNECTING WIRE 
CONNECTION AND OUTDOOR POWER SUPPLY CORD 
CONNECTION

  Connect the indoor/outdoor unit connecting wire 

A

 from the indoor unit correctly 

on the terminal block.

  For future servicing, give extra length to connecting wire.

INDOOR UNIT INSTALLATION

  Insert the drain hose into the wall hole sleeve 

C

, and hook the upper part of 

indoor unit on the installation plate 

1

. Then, move the unit to the very edge of the 

left side for putting the piping easily in the back space of the indoor unit. After that, 
cut the part of packing material (spacer assembly) to hook it on the back rib and 
lift the indoor unit as shown in the fi gure below.

Loosen terminal screw.

Terminal block

Lead wire

<Connection details>

Cut part of packing material (spacer assembly) to
hook it on the back rib.

Downward
slope

Water 
leakage

Do not raise.

Water 
leakage

Accumulated
drain water

Waving

Water 
leakage

Tip of drain 
hose dipped 
in water.

Ditch

Air

Soft hose
I.D. 15 mm

Drain hose

Less than 
50 mm gap

4  Insert the drain hose into the section to which the drain hose is 

to be attached at the rear right of the indoor unit.

Drain hose

  If the drain hose provided with the indoor unit is too short, connect it with drain 

hose

I

 that should be provided at your site. (Fig. 6)

  When connecting the drain hose to the hard vinyl chloride pipe, be sure to insert it 

securely into the pipe. (Fig. 7)

 

(Fig. 4) 

              (Fig. 5)

 

(Fig. 1) 

(Fig. 2) 

(Fig. 3)

  Connect the refrigerant piping with the extension pipe 

B

.

  Thrust the lower part of the indoor unit into the installation plate 

1

.

4-7 DRAIN PIPING

  If the extension drain hose has to pass through a room, be sure to wrap it with 

commercially sold insulation.

  The drain hose should point downward for easy drain fl ow. (Fig. 1)

 

Do not make drain piping as shown in Fig. 2 to 5.

CAUTION

O

  Use care not to make mis-wiring.

O

  Firmly tighten the terminal screws to prevent them from loosening.

O

  After tightening, pull the wires lightly to confi rm that they do not move.

O

  If the connecting wire is incorrectly connected to the terminal block, the unit 

does not operate normally.

WARNING

O

  A means for disconnection of the supply with an isolation switch, or similar 

device, in all active conductors shall be incorporated in the fi xed wiring.

O

  Never cut the power cord and connect it to other wires.

 

It may cause a fi re.

Power supply cord 
Specifi cation

3-core 2.5 mm

2

 or more, in conformity 

with Design 60245 IEC 57.

10 m or less

Indoor and Outdoor 
connecting wire 
Specifi cation

Cable 2-core 1.0 mm

2

, in conformity with 

Design 60245 IEC 57.

Drain hose

70 cm 
or more

Hard vinyl 
chloride pipe 
I.D. 30 mm

Be sure to insert the 
drian hose securely 
into the pipe.

Different 
diameter joint

  

(Fig. 

6) 

(Fig. 

7)

Rated

Voltage

Breaker

capacity

•  Connect to the supply terminals and leave a 

contact separation of at least 3 mm at each pole 
to disconnect the source power pole. (When the 
power switch is shut off, it must disconnect all 
poles.)

• Max. Permissive System Impedance 0.17(

Ω

) for 

71/80 types

230 V

25 A

O

  Peel off both ends of connecting wire (extension wire).

 

When too long, or connected by cutting off the middle, 
peel off power supply wire to the size as shown in the 
right.

O

  Be careful not to contact connecting wire with piping.

O

  Make earth wire a little longer than the others. 

 

(more than 35 mm)

35 mm

15 mm

  For the power supply cord and the indoor/outdoor unit connecting wires, be sure to 

use the ones in compliance with the standards.

  Be sure to push the core until it is hidden and pull each cable to make sure that it is 

not pulled up incomplete insertion may cause a risk of burning the terminal blocks.

Power supply cord 

K

Indoor
terminal
block

Outdoor
terminal
block

Indoor/outdoor unit
connecting wire 

A

2-core 1.0 mm

2

3 N

3 N

N~

L~

MS Type and MSH Type

Securely attach the spacer 
assembly in the concave 
part of the rib, taking care its 
direction is correct as shown 
in the fi gure right.

Spacer

Spacer assembly

Insert the drain hose fully into the drain pan. Check if the hose is hooked securely to 
the projection of its inserting part at the drain pan.

Содержание MS-GA60VB

Страница 1: ...inflammable gas leaks If gas leaks and accumulates in the area surrounding the unit it could cause an explosion Q Install an earth leakage breaker depending on the installation place Where it is humid If an earth leakage breaker is not installed it could cause an electric shock Q Perform the drainage piping work securely according to the installation manual If there is a defect in the drainage pipi...

Страница 2: ...nstallation Indoor unit 1 Installation plate 1 2 Installation plate fixing screw 4 25 mm 7 3 Remote controller holder 1 4 Fixing screw for 3 3 5 16 mm Black 2 5 Battery AAA for remote controller 2 6 Wireless remote controller 1 7 Felt tape Used for left or left rear piping 1 8 Air cleaning filter 2 PART TO BE PROVIDED AT YOUR SITE Optional extension pipe A Indoor outdoor unit connecting wire 2 core ...

Страница 3: ...ioning of the holes on the wall 4 2 WALL HOLE DRILLING 1 Determine the wall hole position 2 Drill a 75 mm hole so that outside can be lower than inside 3 Insert the wall hole sleeve C When bolts recessed in the concrete wall are to be utilized secure the installation plate 1 using 11 20 11 26 oval hole 450 mm pitch If the recessed bolt is too long change it for a shorter one available in the marke...

Страница 4: ...lace the drain hose below the refrigerant piping Make sure that the drain hose is not heaved or snaked Do not pull the hose to apply the tape When the drain hose passes the room be sure to wrap insulation material obtainable at a store around it Wrap the felt tape 7 around the pipe and the drain hose then put the pipe in the back space of the indoor unit Drain hose Drain cap Cut off in case of lef...

Страница 5: ...ening pull the wires lightly to confirm that they do not move O If the connecting wire is incorrectly connected to the terminal block the unit does not operate normally WARNING O A means for disconnection of the supply with an isolation switch or similar device in all active conductors shall be incorporated in the fixed wiring O Never cut the power cord and connect it to other wires It may cause a fi...

Страница 6: ...ed for HFC refrigerant Torque wrench Yes 1 4 No 1 2 and 5 8 Flare tool Yes Clamp bar hole has been enlarged to reinforce the spring strength in the tool Flare gauge New Provided for flaring work to be used with R22 flare tool Vacuum pump adaptor New Provided to prevent the back flow of oil This adapter enables you to use existing vacuum pumps Electronic scale for refrigerant charging New It is difficu...

Страница 7: ... 140 to 180 9 52 34 3 to 41 2 350 to 420 15 88 73 5 to 78 4 750 to 800 Tightening torque N m kgf cm Cap for service port 13 7 to 17 7 140 to 180 Cap for stop valve 19 6 to 29 4 200 to 300 Checking the remote infrared signal reception Press the ON OFF button on the remote controller and check that an electronic sound is heard from the indoor unit Press the ON OFF button again to turn the air condit...

Страница 8: ...essor will be locked To maintain the high pressure of the gas cylinder warm the gas cylinder with warm water under 40 C during cold season But never use naked fire or steam 7 2 REMOVING THE INDOOR UNIT Remove the bottom of the indoor unit from the installation plate 1 Remove the front panel See FRONT PANEL REMOVAL shown above 2 Insert flat screwdrivers into the square holes at the left and right bot...