background image

6-3 PIPE CONNECTION

Note:

Fasten a fl are nut with a torque wrench as specifi ed in the table below.
When fastened too tight, a fl are nut may broken after a long period and cause a leakage 
of refrigerant.

1

  Indoor unit connection

Connect both liquid and gas pipings to indoor unit.

  Apply a thin coat of refrigeration oil 

J

 on the seat surface of pipe.

 For connection fi rst align the center, then tighten the fi rst 3 to 4 turns of fl are nut.

  Use tightening torque table below as a guideline for indoor unit side union joint 

section, and tighten using two wrenches. Excessive tightening damages the fl are 
section.

6.  INDOOR/OUTDOOR UNIT CONNECTION 

FINISHING AND TEST RUN

INSTALLATION INFORMATION FOR THE AIR 
CONDITIONER WITH R410A REFRIGERANT

  This room air conditioner adopts an HFC refrigerant (R410A) which will never destroy 

the ozone layer.

  Pay particular attention to the following points, though the basic installation 

procedure is same as that for R22 air conditioners.

1

  As R410A has a working pressure approx. 1.6 times as high as that of R22, some 

special tools and piping parts / materials are required. (Refer to the table below.)

2

 Take 

suffi cient care not to allow water and other contaminations to enter the 

R410A refrigerant during storage and installation, since it is more susceptible to 
contaminations than R22.

3

  For refrigerant piping, use clean, pressure-proof parts / materials specifi cally 

designed for R410A. (Refer to 2. Refrigerant piping.)

4

  Composition change may occur in R410A since it is a mixed refrigerant. When 

charging, charge liquid refrigerant to prevent composition change.

6-1  Tools dedicated for the air conditioner with R410A 

refrigerant

The following tools are required for R410A refrigerant. Some R22 tools can be 
substituted for R410A tools.
The diameter of the service port on the stop valve in outdoor unit has been changed to 
prevent any other refrigerant being charged into the unit. (Cap size has been changed 
from 7/16 UNF with 20 threads to 1/2 UNF with 20 threads.)

R410A tools

Can R22 tools 

be used?

Description

Gauge manifold

No

R410A has high pressures beyond the 
measurement range of existing gauges. Port 
diameters have been changed to prevent any 
other refrigerant from being charged into the 
unit.

Charge hose

No

Hose material and cap size have been changed 
to improve the pressure resistance.

Gas leak detector

No

Dedicated for HFC refrigerant.

Torque wrench

Yes

1/4

No

1/2 and 5/8

Flare tool

Yes

Clamp bar hole has been enlarged to reinforce 
the spring strength in the tool.

Flare gauge

New

Provided for fl aring work (to be used with R22 
fl are tool).

Vacuum pump
adaptor

New

Provided to prevent the back fl ow of oil. This 
adapter enables you to use existing vacuum 
pumps.

Electronic scale
for refrigerant
charging

New

It is diffi cult to measure R410A with a charging 
cylinder because the refrigerant bubbles due to 
high pressure and high-speed vaporization.

No: Not substitutable for R410A  Yes: Substitutable for R410A

Copper pipe

Good

No good

Tilted

Uneven

Burred

Burr

Copper pipe

Spare
reamer

Pipe
cutter

Flare nut

Copper pipe

Smooth all around

Even length 
all around

Inside is shining without any scratches.

90

°

A

Die

Copper pipe

Flare nut

Die

Copper pipe

York 

Flaring tool

Wing nut type

Clutch type

WARNING

Be sure to attach the service panel of the outdoor unit securely. If it is not attached 
correctly, it could result in a fi re or an electric shock due to dust, water, etc.

5 Check

• Compare 

the 

fl ared work with fi gure below.

• If 

fl are is noted to be defective, cut off the fl ared section and do fl aring work again.

•  Firmly hold copper pipe in a die in the dimension shown in the table above.

  4 Flaring work

• Carry 

out 

fl aring work using fl aring tool as shown below.

  3 Putting nut on

• Remove 

fl are nuts attached to indoor and outdoor 

units, then put them on pipe having completed 
burr removal.

 

(not possible to put them on after fl aring work)

•  Flare nut for R410A pipe differs from R22 pipe.
 

Refer to the following table for detail.

  2 Burrs removal

•  Completely remove all burrs from the cut cross section of pipe.
•  Put the end of the copper pipe to downward direction as you remove burrs in order to 

avoid to let burrs drop in the piping.

  1 Pipe cutting

•  Cut the copper pipe correctly with pipe cutter.

mm

Inch

R410A

R22

ø6.35

1/4

17

17

ø9.52

3/8

22

22

ø15.88

5/8

29

27

Outside diameter

A (mm)

Flare tool for R410A

clutch type

Conventional fl are tool

Clutch type

Wing nut type

ø6.35 mm

0 to 0.5

1.0 to 1.5

1.5 to 2.0

ø9.52 mm

0 to 0.5

1.0 to 1.5

1.5 to 2.0

ø15.88 mm

0 to 0.5

1.0 to 1.5

2.0 to 2.5

Be sure to fi x the indoor/outdoor unit 
connecting wire 

A

 and power supply 

cord

K

 using this cord clamp.

Be sure to put the left
portion into the square
hole of the service panel.

Service panel

Fixing screws

Remove the fi xing 
screw to open the 
service panel.

Valve cover

6-2 FLARING WORK

  Main cause of gas leakage is defect in fl aring work.

 

Carry out correct fl aring work in the following procedure.

A

K

Содержание MS-GA60VB

Страница 1: ...inflammable gas leaks If gas leaks and accumulates in the area surrounding the unit it could cause an explosion Q Install an earth leakage breaker depending on the installation place Where it is humid If an earth leakage breaker is not installed it could cause an electric shock Q Perform the drainage piping work securely according to the installation manual If there is a defect in the drainage pipi...

Страница 2: ...nstallation Indoor unit 1 Installation plate 1 2 Installation plate fixing screw 4 25 mm 7 3 Remote controller holder 1 4 Fixing screw for 3 3 5 16 mm Black 2 5 Battery AAA for remote controller 2 6 Wireless remote controller 1 7 Felt tape Used for left or left rear piping 1 8 Air cleaning filter 2 PART TO BE PROVIDED AT YOUR SITE Optional extension pipe A Indoor outdoor unit connecting wire 2 core ...

Страница 3: ...ioning of the holes on the wall 4 2 WALL HOLE DRILLING 1 Determine the wall hole position 2 Drill a 75 mm hole so that outside can be lower than inside 3 Insert the wall hole sleeve C When bolts recessed in the concrete wall are to be utilized secure the installation plate 1 using 11 20 11 26 oval hole 450 mm pitch If the recessed bolt is too long change it for a shorter one available in the marke...

Страница 4: ...lace the drain hose below the refrigerant piping Make sure that the drain hose is not heaved or snaked Do not pull the hose to apply the tape When the drain hose passes the room be sure to wrap insulation material obtainable at a store around it Wrap the felt tape 7 around the pipe and the drain hose then put the pipe in the back space of the indoor unit Drain hose Drain cap Cut off in case of lef...

Страница 5: ...ening pull the wires lightly to confirm that they do not move O If the connecting wire is incorrectly connected to the terminal block the unit does not operate normally WARNING O A means for disconnection of the supply with an isolation switch or similar device in all active conductors shall be incorporated in the fixed wiring O Never cut the power cord and connect it to other wires It may cause a fi...

Страница 6: ...ed for HFC refrigerant Torque wrench Yes 1 4 No 1 2 and 5 8 Flare tool Yes Clamp bar hole has been enlarged to reinforce the spring strength in the tool Flare gauge New Provided for flaring work to be used with R22 flare tool Vacuum pump adaptor New Provided to prevent the back flow of oil This adapter enables you to use existing vacuum pumps Electronic scale for refrigerant charging New It is difficu...

Страница 7: ... 140 to 180 9 52 34 3 to 41 2 350 to 420 15 88 73 5 to 78 4 750 to 800 Tightening torque N m kgf cm Cap for service port 13 7 to 17 7 140 to 180 Cap for stop valve 19 6 to 29 4 200 to 300 Checking the remote infrared signal reception Press the ON OFF button on the remote controller and check that an electronic sound is heard from the indoor unit Press the ON OFF button again to turn the air condit...

Страница 8: ...essor will be locked To maintain the high pressure of the gas cylinder warm the gas cylinder with warm water under 40 C during cold season But never use naked fire or steam 7 2 REMOVING THE INDOOR UNIT Remove the bottom of the indoor unit from the installation plate 1 Remove the front panel See FRONT PANEL REMOVAL shown above 2 Insert flat screwdrivers into the square holes at the left and right bot...

Отзывы: