background image

8

6. Electrical work

Models (Outdoor unit)

Indoor unit power supply

Outdoor unit

Phase

Power supply

Frequency & Voltage

Input capacity

Indoor unit (A)

Main switch/Fuse

Outdoor unit (A)

Outdoor unit

Wire No.

Power supply

Indoor unit/Outdoor unit connecting

Wire No. 

×

 size (mm

2

)

Remote controller-Indoor unit

Wire No. 

×

 size (mm

2

)

Control circuit rating

RP3V

RP4, 5, 6 V

~/N (single), 50Hz, 220 - 230 - 240V/60Hz, 220V

~/N (Single)

50 Hz, 220 - 230 - 240V/60Hz, 220V

32/32

63/63

3

3

×

 2.5 Cable (polar)

Cable 2C 

×

 0.69

* This wire is accessory of remote controller (Wire length: 10 m, Non-polar)

Indoor unit-Outdoor unit: S1-S2 AC 220V-230V-240V, S2-S3 DC24V, Remote controller-Indoor unit: DC 14V

Wir

ing

Notes:
1. Wiring size must comply with the applicable local and national code.
2. Be careful about choosing the installation location for the earth leakage breaker and how it is installed as the initial electric current may cause it to malfunction.
3. Power supply cords and Indoor unit/Outdoor unit connecting cords shall not be lighter than polychloroprene sheathed flexible cord. (design 245 IEC 57)

6.3. Field electrical wiring (Power wiring specifications)

6.1. Precautions (Fig. 6-1)

• The compressor will not operate unless the power supply phase connection is cor-

rect.

• Grounding protection with a no-fuse breaker (earth leakage breaker [ELB]) is usu-

ally installed for 

D

.

• The connection wiring between the outdoor and indoor units can be extended up to

a maximum of 50 meters, and the total extension including the crossover wiring
between rooms is a maximum of 80 m.

A switch with at least 3 mm contact separation in each pole shall be provided by the
air conditioner installation.

Label each breaker according to purpose (heater, unit etc.).

A

Indoor unit

B

Outdoor unit

C

Remote controller

D

Main switch/fuse

E

Grounding

6.2. Outdoor unit wiring (Fig. 6-2)

1. Remove the service panel.
2. Wire the cables referring to the figure.

A

Earth terminal

B

Terminal block (Left: Power supply, Right: Indoor/Outdoor unit connecting wire)

C

Fasten with wiring clamp

D

Extraction direction for service panel

E

Service panel

7. Test run

7.1. Before test run

s

After completing installation and the wiring and piping of the indoor and outdoor
units, check for refrigerant leakage, looseness in the power supply or control
wiring, wrong polarity, and no disconnection of one phase in the supply.

s

Use a 500-volt megohmmeter to check that the resistance between the power
supply terminals and ground is at least 1.0M

.

s

Do not carry out this test on the control wiring (low voltage circuit) termi-
nals.
 Warning:

Do not use the air conditioner if the insulation resistance is less than 1.0M

.

Insulation resistance

After installation or after the power source to the unit has been cut for an extended
period, the insulation resistance will drop below 1 M

 due to refrigerant accumulat-

ing in the compressor. This is not a malfunction. Perform the following procedures.
1. Remove the wires from the compressor and measure the insulation resistance of

the compressor.

2. If the insulation resistance is below 1 M

, the compressor is faulty or the resist-

ance dropped due the accumulation of refrigerant in the compressor.

3. After connecting the wires to the compressor, the compressor will start to warm

up after power is supplied. After supplying power for the times indicated below,
measure the insulation resistance again.

The insulation resistance drops due to accumulation of refrigerant in the com-
pressor. The resistance will rise above 1 M

 after the compressor is warmed

up for two to three hours.
(The time necessary to warm up the compressor varies according to atmos-
pheric conditions and refrigerant accumulation.)

To operate the compressor with refrigerant accumulated in the compressor,
the compressor must be warmed up at least 12 hours to prevent breakdown.

4. If the insulation resistance rises above 1 M

, the compressor is not faulty.

 Caution:

The compressor will not operate unless the power supply phase connection
is correct.

• Turn on the power at least 12 hours before starting operation.

- Starting operation immediately after turning on the main power switch can result in

severe damage to internal parts. Keep the power switch turned on during the op-
erational season.

s

The followings must be checked as well.

• The outdoor unit is not faulty. LED1 and LED2 on the control board of the outdoor

unit flash when the outdoor unit is faulty.

• Both the gas and liquid stop valves are completely open.
• A protective sheet covers the surface of the DIP switch panel on the control board of

the outdoor unit. Remove the protective sheet to operate the DIP switches easily.

• Make sure that the all of the SW5 DIP switches for function changes on the control

board of the outdoor unit are set to OFF. If all of the SW5 switches are not set to
OFF, record the settings and then set all of the switches to OFF. Begin recovering
the refrigerant. After moving the unit to a new location and completing the test run,
set the SW5 switches to the previously recorded settings.

A

B

C

D

E

A

C

B

D

S3

S3

S2

S1

S2

S1

L N

D

E

C

B

A

A

A

Fig. 6-1

Fig. 6-2

Содержание Mr.Slim PUNZ-RP-HA-A

Страница 1: ...Air Conditioners PUHZ RP HA A English INSTALLATION MANUAL For safe and correct use please read this installation manual thoroughly before installing the air conditioner unit FOR INSTALLER ...

Страница 2: ...ant pipes If the pipes are not connected correctly the unit will not be properly grounded and electric shock may result Use only specified cables for wiring The connections must be made securely without tension on the terminals If the cables are connected or installed in correctly overheating or fire may result The terminal block cover panel of the outdoor unit must be firmly attached If the cover...

Страница 3: ...e rioration or compressor breakdown may result Use ester oil ether oil alkylbenzene oil small amount as the refrigeration oil applied to the flared sections If mineral oil is mixed in the refrigeration oil oil deterioration may result Do not use refrigerant other than R410A refrigerant If another refrigerant is used the chlorine will cause the oil to deteriorate Use the following tools specificall...

Страница 4: ...nal air outlet guides for upward airflow 3 Obstacles at front only Fig 2 14 When using an optional air outlet guide the clearance for RP4 6 models is 1000 mm or more 4 Obstacles at front and rear only Fig 2 15 When using an optional air outlet guide the clearance for RP4 6 models is 1000 mm or more 5 Single parallel unit arrangement Fig 2 16 When using an optional air outlet guide installed for up...

Страница 5: ...Model RP3 6 Liquid ODø9 52 3 8 Gas ODø15 88 5 8 Drainage piping PVC ODø32 1 1 4 Table 1 Fig 4 2 Fig 4 1 A A B Fig 4 2 4 1 Precautions for devices that use R410A refrigerant Refer to page 3 for precautions not included below on using air conditioners with R410A refrigerant Use ester oil ether oil alkylbenzene oil small amount as the refrigeration oil applied to the flared sections Use C1220 copper ...

Страница 6: ... method 1 Gas side Fig 4 5 1 Remove the cap pull the handle toward you and rotate 1 4 turn in a counterclock wise direction to open 2 Make sure that the stop valve is open completely push in the handle and rotate the cap back to its original position 2 Liquid side Fig 4 6 1 Remove the cap and turn the valve rod counterclockwise as far as it will go with the use of a 4 mm hexagonal wrench Stop turn...

Страница 7: ...inutes do a pump down work Use a refrigerant collecting device to collect the refrigerant Check the oil condition when collecting the refrigerant Oil is clean Oil is dirty When the compressor bearings are glazed rotation scratches are present or the compressor breaks down iron particles or oil deterioration will blacken the oil Disconnect the existing air conditioner from the pipes Disconnect the ...

Страница 8: ... 1 0MΩ Ω Ω Ω Ω s Do not carry out this test on the control wiring low voltage circuit termi nals Warning Do not use the air conditioner if the insulation resistance is less than 1 0MΩ Ω Ω Ω Ω Insulation resistance After installation or after the power source to the unit has been cut for an extended period the insulation resistance will drop below 1 MΩ due to refrigerant accumulat ing in the compre...

Страница 9: ... down Perform the following procedures to collect the refrigerant when moving the indoor unit or the outdoor unit 1 Before collecting the refrigerant first make sure that the all of the SW5 DIP switches for function changes on the control board of the outdoor unit are set to OFF If all of the SW5 switches are not set to OFF record the settings and then set all of the switches to OFF Start collecti...

Страница 10: ......

Страница 11: ...0 1500 300 500 Max 500 200 300 1000 1500 300 500 1000 1500 Max 300 1000 1500 1000 1500 300 500 500 1000 400 600 1000 2000 100 150 1000 1500 500 800 150 1000 1500 400 600 2000 3000 300 500 Fig 2 6 Fig 2 7 Fig 2 8 Fig 2 9 Fig 2 10 Fig 2 11 Fig 2 12 Fig 2 13 Fig 2 14 Fig 2 15 Fig 2 16 Fig 2 17 Fig 2 18 ...

Страница 12: ... sure to put the contact address telephone number on this manual before handing it to the customer HEAD OFFICE MITSUBISHI DENKI BLDG 2 2 3 MARUNOUCHI CHIYODA KU TOKYO 100 8310 JAPAN Printed in Japan BG79U130H01 ...

Отзывы: