background image

4

2. Installation location

A

B

2.4. Ventilation and service space

2.4.1. Windy location installation

When installing the outdoor unit on a rooftop or other location unprotected from the
wind, situate the air outlet of the unit so that it is not directly exposed to strong winds.
Strong wind entering the air outlet may impede the normal airflow and a malfunction
may result.
The following shows three examples of precautions against strong winds.

1

Face the air outlet towards the nearest available wall about 50 cm away from the
wall. (Fig. 2-3)

2

Install an optional air outlet guide and air guide if the unit is installed in a location
where strong winds from a typhoon, etc. may directly enter the air outlet. (Fig. 2-4)

A

Air outlet guide

3

Position the unit so that the air outlet blows perpendicularly to the seasonal wind
direction, if possible. (Fig. 2-5)

B

Wind direction

2.4.2. When installing a single outdoor unit (Refer to the last page)

Minimum dimensions are as follows, except for Max., meaning Maximum dimensions,
indicated.
The figure in parentheses are for RP4-6 models.
Refer to the figures for each case.

1

Obstacles at rear only (Fig. 2-6)

2

Obstacles at rear and above only (Fig. 2-7)

3

Obstacles at rear and sides only (Fig. 2-8)

4

 Obstacles at front only (Fig. 2-9)

When using an optional air outlet guide, the clearance for RP4-6 models is 500 mm or more.

5

 Obstacles at front and rear only (Fig. 2-10)

When using an optional air outlet guide, the clearance for RP4-6 models is 500 mm or more.

6

 Obstacles at rear, sides, and above only (Fig. 2-11)

*

Do not install the optional air outlet guides for upward airflow.

2.4.3. When installing multiple outdoor units (Refer to the last page)

Leave a 10 mm space or more between the units.

1

 Obstacles at rear only (Fig. 2-12)

2

 Obstacles at rear and above only (Fig. 2-13)

*

No more than three units must be installed side by side. In addition, leave space as shown.

*

Do not install the optional air outlet guides for upward airflow.

3

 Obstacles at front only (Fig. 2-14)

When using an optional air outlet guide, the clearance for RP4-6 models is 1000 mm or
more.

4

 Obstacles at front and rear only (Fig. 2-15)

When using an optional air outlet guide, the clearance for RP4-6 models is 1000 mm or
more.

5

 Single parallel unit arrangement (Fig. 2-16)

When using an optional air outlet guide installed for upward airflow, the clearance is 500
(1000) mm or more.

6

 Multiple parallel unit arrangement (Fig. 2-17)

When using an optional air outlet guide installed for upward airflow, the clearance is 1000
(1500) mm or more.

7

 Stacked unit arrangement (Fig. 2-18)

*

The units can be stacked up to two units high.

*

No more than two stacked units must be installed side by side. In addition, leave space as
shown.

3. Installing the outdoor unit

Max.30

B

A

C

600

600

Min. 360

175

175

Min. 10

950

25

330

370

D

(mm)

• Be sure to install the unit in a sturdy, level surface to prevent rattling noises during

operation. (Fig. 3-1)

<Foundation specifications>

Foundation bolt

M10 (3/8")

Thickness of concrete

120 mm

Length of bolt

70 mm

Weight-bearing capacity

320 kg

• Make sure that the length of the foundation bolt is within 30 mm of the bottom

surface of the base.

• Secure the base of the unit firmly with four-M10 foundation bolts in sturdy locations.

Installing the outdoor unit

• Do not block the vent. If the vent is blocked, operation will be hindered and break-

down may result.

• In addition to the unit base, use the installation holes on the back of the unit to attach

wires, etc., if necessary to install the unit. Use self-tapping screws (ø5 

×

 15 mm or

more) and install on site.

 Warning:

• The unit must be securely installed on a structure that can sustain its weight.

If the unit is mounted on an unstable structure, it may fall down and cause
damage or injuries.

• The unit must be installed according to the instructions in order to minimize

the risk of damage from earthquakes, typhoons, or strong winds. An incor-
rectly installed unit may fall down and cause damage or injuries.

Fig. 3-1

Fig. 2-4

Fig. 2-5

Fig. 2-3

A

M10 (3/8") bolt

B

Base

C

As long as possible.

D

Vent

Содержание Mr.Slim PUNZ-RP-HA-A

Страница 1: ...Air Conditioners PUHZ RP HA A English INSTALLATION MANUAL For safe and correct use please read this installation manual thoroughly before installing the air conditioner unit FOR INSTALLER ...

Страница 2: ...ant pipes If the pipes are not connected correctly the unit will not be properly grounded and electric shock may result Use only specified cables for wiring The connections must be made securely without tension on the terminals If the cables are connected or installed in correctly overheating or fire may result The terminal block cover panel of the outdoor unit must be firmly attached If the cover...

Страница 3: ...e rioration or compressor breakdown may result Use ester oil ether oil alkylbenzene oil small amount as the refrigeration oil applied to the flared sections If mineral oil is mixed in the refrigeration oil oil deterioration may result Do not use refrigerant other than R410A refrigerant If another refrigerant is used the chlorine will cause the oil to deteriorate Use the following tools specificall...

Страница 4: ...nal air outlet guides for upward airflow 3 Obstacles at front only Fig 2 14 When using an optional air outlet guide the clearance for RP4 6 models is 1000 mm or more 4 Obstacles at front and rear only Fig 2 15 When using an optional air outlet guide the clearance for RP4 6 models is 1000 mm or more 5 Single parallel unit arrangement Fig 2 16 When using an optional air outlet guide installed for up...

Страница 5: ...Model RP3 6 Liquid ODø9 52 3 8 Gas ODø15 88 5 8 Drainage piping PVC ODø32 1 1 4 Table 1 Fig 4 2 Fig 4 1 A A B Fig 4 2 4 1 Precautions for devices that use R410A refrigerant Refer to page 3 for precautions not included below on using air conditioners with R410A refrigerant Use ester oil ether oil alkylbenzene oil small amount as the refrigeration oil applied to the flared sections Use C1220 copper ...

Страница 6: ... method 1 Gas side Fig 4 5 1 Remove the cap pull the handle toward you and rotate 1 4 turn in a counterclock wise direction to open 2 Make sure that the stop valve is open completely push in the handle and rotate the cap back to its original position 2 Liquid side Fig 4 6 1 Remove the cap and turn the valve rod counterclockwise as far as it will go with the use of a 4 mm hexagonal wrench Stop turn...

Страница 7: ...inutes do a pump down work Use a refrigerant collecting device to collect the refrigerant Check the oil condition when collecting the refrigerant Oil is clean Oil is dirty When the compressor bearings are glazed rotation scratches are present or the compressor breaks down iron particles or oil deterioration will blacken the oil Disconnect the existing air conditioner from the pipes Disconnect the ...

Страница 8: ... 1 0MΩ Ω Ω Ω Ω s Do not carry out this test on the control wiring low voltage circuit termi nals Warning Do not use the air conditioner if the insulation resistance is less than 1 0MΩ Ω Ω Ω Ω Insulation resistance After installation or after the power source to the unit has been cut for an extended period the insulation resistance will drop below 1 MΩ due to refrigerant accumulat ing in the compre...

Страница 9: ... down Perform the following procedures to collect the refrigerant when moving the indoor unit or the outdoor unit 1 Before collecting the refrigerant first make sure that the all of the SW5 DIP switches for function changes on the control board of the outdoor unit are set to OFF If all of the SW5 switches are not set to OFF record the settings and then set all of the switches to OFF Start collecti...

Страница 10: ......

Страница 11: ...0 1500 300 500 Max 500 200 300 1000 1500 300 500 1000 1500 Max 300 1000 1500 1000 1500 300 500 500 1000 400 600 1000 2000 100 150 1000 1500 500 800 150 1000 1500 400 600 2000 3000 300 500 Fig 2 6 Fig 2 7 Fig 2 8 Fig 2 9 Fig 2 10 Fig 2 11 Fig 2 12 Fig 2 13 Fig 2 14 Fig 2 15 Fig 2 16 Fig 2 17 Fig 2 18 ...

Страница 12: ... sure to put the contact address telephone number on this manual before handing it to the customer HEAD OFFICE MITSUBISHI DENKI BLDG 2 2 3 MARUNOUCHI CHIYODA KU TOKYO 100 8310 JAPAN Printed in Japan BG79U130H01 ...

Отзывы: