15
8
REFRIGERANT SYSTEM DIAGRAM
PUHZ-SHW80VHA PUHZ-SHW112VHA
PUHZ-SHW112YHA PUHZ-SHW140YHA
Distributor
Thermistor TH7
(Ambient)
Heat exchanger
Refrigerant
GAS pipe
connection
(5/8 inch)
Refrigerant
LIQUID pipe
connection
(3/8 inch)
Stop valve
(with service port)
Strainer
#100
Power
receiver
Linear
expansion valve B
Linear
expansion valve C
Linear expansion valve A
Strainer
#100
Strainer
#100
Thermistor
TH6
(2-phase pipe)
Thermistor TH3
(Liquid)
Charge plug
(Low pressure)
Charge plug
(High pressure)
Heat interchange circuit
Thermistor TH4
(Discharge)
Thermistor TH34
(Comp. surface)
Compressor
Injection port
Strainer
#50
Solenoid valve
(Four-way valve)
Strainer
#100
Strainer
#100
Muffler
Ball valve
Thermistor TH33
(Ref. check)
Thermistor
TH32
(Suction)
Low pressure
switch 63L
High pressure
switch 63H
Refrigerant flow in cooling
Refrigerant flow in heating
High pressure sensor (63HS)
Symbol
Part name
Detail
COMP
Compressor
DC inverter scroll compressor (Mitsubishi Electric Corporation)
H/P SW
High pressure switch (63H)
For protection (OFF: 4.15MPa)
L/P SW
Low pressure switch (63L)
For protection (OFF: -0.03MPa)
REV/V
Reversing (4-way) valve (21S4)
Change the refrigerant circuit (Heating / Cooling) and for Defrosting
Charge plug
Charge plug
High pressure / Low pressure / For production test use
P-Sensor
Pressure sensor (63HS)
For calculation of the condensing temperature from high pressure
LEV-A
Linear expansion valve -A
Heating:Secondary LEV Cooling:Primary LEV
LEV-B
Linear expansion valve -B
Heating:Primary LEV Cooling:Secondary LEV
LEV-C
Linear expansion valve -C
For HIC (heating only)
TH32
Suction temperature thermistor
For LEV control
TH33
Refrigerant leakage detection
(Ref. check) thermistor
For refrigerant leakage detection
TH3
Liquid temperature thermistor
Heating:Evaporating temperature Cooling:Sub cool liquid temperature
TH4
Discharge temperature thermistor
For LEV control and for compressor protection
TH6
2-phase pipe temperature thermistor
Outdoor 2-phase pipe temperature
TH7
Ambient temperature thermistor
For fan control and for compressor frequency control
TH34
Comp. surface temperature thermistor For protection
Power Receiver Power Receiver
For accumulation of refrigerant
HIC
Heat interchange circuit
For high heating capacity
Plate HEX
Plate Heat Exchanger
MWA2-38PA (MITSUBISHI)
<Reference>
System example
TH1
Outlet water temperature thermistor
For fl ow temp. controller
TH2
Liquid pipe temperature thermistor
For fl ow temp. controller
OCH526