30
Error Code
Abnormal point and detection method
Judgment and action
Case
UP
(4210)
E0
or
E4
Remote controller transmission error (E0)/
signal receiving error (E4)
1
Abnormal if main or sub remote
controller cannot receive normally
any transmission from indoor unit of
refrigerant address “0” for 3 minutes.
(Error code : E0)
2
Abnormal if sub remote controller could
not receive any signal for 2 minutes.
(Error code: E0)
1
Abnormal if indoor controller board can
not receive normally any data from
remote controller board or from other
indoor controller board for 3 minutes.
(Error code: E4)
2
Indoor controller board cannot receive
any signal from remote controller for 2
minutes. (Error code: E4)
1
Check disconnection or looseness of indoor
unit or transmission wire of remote controller.
2
Set one of the remote controllers “main” if
there is no problem with the action above.
3
Check wiring of remote controller.
• Total wiring length: Max. 500m
(Do not use cable
o
3 or more.)
• The number of connecting indoor units:
Max. 16 units
• The number of connecting remote
controller: Max. 2 units
When it is not the above-mentioned problem of
1
~
3
4
Diagnose remote controllers.
a) When “RC OK” is displayed,
Remote controllers have no problem.
Turn the power off, and on again to check.
If abnormality generates again, replace
indoor controller board.
b) When “RC NG” is displayed,
Replace remote controller.
c) When "RCE3" or "ERC00-66" is displayed,
noise may be causing abnormality.
* If the unit is not normal after replacing
indoor controller board in group control,
indoor controller board of address “0”
may be abnormal.
1
Contact failure at transmission
wire of remote controller
2
All remote controllers are set
as “sub” remote controller.
In this case, E0 is displayed
on remote controller, and E4
is displayed at LED (LED1,
LED2) on the outdoor controller
circuit board.
3
Miswiring of remote controller
4
Defective transmitting receiving
circuit of remote controller
5
Defective transmitting receiving
circuit of indoor controller board
of refrigerant address “0”
6
Noise has entered into the
transmission wire of remote
controller.
Compressor overcurrent interruption
Abnormal if overcurrent DC bus or
compressor is detected after compressor
starts operating for 30 seconds.
1
Stop valve of outdoor unit is
closed.
2
Decrease of power supply
voltage
3
Looseness, disconnection or
converse of compressor wiring
connection
4
Defective fan of indoor/outdoor
units
5
Short cycle of indoor/outdoor
units
6
Defective input circuit of
outdoor controller board
7
Defective compressor
8
Defective outdoor power circuit
board
9
Dip switch setting difference of
outdoor controller circuit board
1
Open stop valve.
2
Check facility of power supply.
3
Correct the wiring (U·V·W phase) to
compressor. Refer to 9-9 (Outdoor power
circuit board).
4
Check indoor/outdoor fan.
5
Solve short cycle.
6
Replace outdoor controller circuit board.
* Before the replacement of the outdoor
controller circuit board, disconnect the wiring
to compressor from the outdoor power circuit
board and check the output voltage among
phases, U, V, W, during test run.
No defect on board if voltage among phases
(U-V, V-W and W-U) is same. Make sure
to perform the voltage check with same
performing frequency.
7
Check compressor. Refer to 9-6.
8
Replace outdoor power circuit board.
9
Check the dip switch setting of outdoor
controller circuit board.
E1
or
E2
Remote controller control board
1
Abnormal if data cannot be normally
read from the nonvolatile memory of the
remote controller control board.
(Error code: E1)
2
Abnormal if the clock function of remote
controller cannot be normally operated.
(Error code: E2)
1
Defective remote controller
1
Replace remote controller.
OCH526